Permit Information
Permit NumberFIR05-00260
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 165 W THORNBERRY CT
Project NameSPR STIPP RESIDENCE
Customer Number 
ePlanReview 
Description
STIPP RESIDENCE * To install a life safety fire sprinkler system in a new 2,949-ft/2 three story single family dwelling with a 628-ft/2 attached two car garage provided with barrier (sprinkler) protection on walls facing the living spaces. The sprinkler flow alarm shall be equipped with an alarm initiating device, commonly referred to as a flow switch, and an outside alarm system. All fire sprinkler work and related, which includes dual service, single service water supply, the system backflow prevention device (provided by others), shall be per NFPA 13D, approved plans, engineering/red-lining and attached review comments, under direction of the Fire Chief. This permit is attached to: BLD04-00907.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection1/12/20061/12/20061/12/2006PPASS
DetailsForrest France
This was a combination inspection including an UG flush witness, overhead final inspection which was conducted while the supply was connected to the overhead, and a final alarm test. All items tested satisfactory, permit finaled.
INSP-Sprinkler Rough-in6/10/20056/13/20056/13/2005APART
DetailsForrest France
Overhead rough-in OK for cover. Need to provide watts backflow preventer as submitted or prove calcs on installed wilkins model are the same.
Sprinkler Plan Check5/25/2005 5/25/2005 PASS
DetailsBill Alexander
Miscellaneous action  5/25/2005 DONE
Took approved plans to front desk for returning. 2nd review/no fee.
Inspection Record Card- Fire5/25/2005 5/25/2005 DONE
Telephone call  5/25/2005 DONE
left mess that permit is ready
Issue and Print Permit  5/25/2005 DONE
Plan resubmittals received  5/16/2005  
Issue and Print Permit  5/12/2005 DONE
Plan assigned to (Bill)4/29/2005 5/10/2005 DONE
Sprinkler Plan Check4/29/2005 5/10/2005 PART
DetailsBill Alexander
1. Hydraulic reference and plans do not correlate:
a. Riser is calced with a C-factor of 150 and plans show "steel" (120)? CPVC will not be accepted since designer does not address listing requirements for the same. Domestic tee tap up through node #6 cannot incorporate unprotected (exposed) Poly, PVC or similar, etc.
b. Calcs are missing friction losses for the following fittings:
i. The domestic control valve,
ii. Flow switch (in pipes 2" or less in size). (NFPA 13D-8.4.4*, NFPA 13-14.4.4.5 [Friction Loss])
iii. Butterfly valve. Please note that the "slow close" valves are not required in domestic 13D systems.
c. Plans show an 1¼" backflow. Data submittals provided (Watts Series 007) does not include a 1¼" model. Identify the type and size installing that matches the data submittals, and friction loss included in the calcs provided.

2. The "Upper Floor" "Master Bathroom" shower is part of the "RESTROOM" and will require protection, (no exception is allowed under the code). (NFPA 13D-8.6.2)

3. The design area shall be the area that includes the two hydraulically most demanding sprinklers. This design is verified on the "Main Floor". The "Upper Floor" or the dry sidewalls may be the most demanding? Provide verification of the two hydraulically most demanding sprinklers in this residence. (NFPA 13D-8.1.2*)

4. Plan FP-1 Section is not identified on any floor plan shown? Provide a location where and which way this cut was taken in relation to the area viewing.

5. This facility is using nominal K-factor heads smaller than 5.6, so the inspector's test connections shall contain an orifice of the same size as the smallest sprinkler installed in the system. Provide clarification on the combination inspectors test/drain installing on the plan (BMC 7-01-50-901.2, IFC 105.4.2, NFPA 13D-7.2.5)

6. Provide clarification on why head #100 is at 10'-0" elevation and head #101 is at 11'-0"?
PLANS/APPL TAKEN TO FRONT DESK  5/10/2005 DONE
DetailsBill Alexander
Permit Ready to Issue  5/10/2005 DONE
Telephone call  5/10/2005 DONE
called left message on machine for jon permit ready and fees 5/10/05 8:54am LEM
Inspection Record Card- Fire5/10/2005 5/10/2005 DONE
Application received  4/29/2005