Permit NumberFIR05-00262
StatusFinaled
Name ALLIED GENERAL FIRE & SECURITY
Site Address 403 S 11TH ST
Project Name11th & Myrtle Professional Cen
Customer Number 
ePlanReview 
Description
To install a new fire alarm system in a new shell and core building. System will consist of fire sprinkler monitoring, elevator recall, hvac monitoring and fire/smoke damper control.

The associated building permit (BLD 04-02153) is to construct a 25,488 sq. ft. three story Type IIIB fully fire sprinklered office shell building. Other work includes all site improvements, landscaping and paving per approved plans and attachments, DRH04-51, CUP04-00025. No occupancy is authorized under this permit. Separate plans and permits are required to complete each tenant space. Fire sprinklers are used for area. 1st floor 8496 sq ft, 2nd 8496 sq ft, 3rd 8496 sq. ft.7/6/2005-Plan modification. The existing and previously approved Silent Knight 5496 power supplies have been changed to new Silent Knight 5495 power supplies. This change is to provide synchronization for the visual notification devices. Voltage drop calculations and battery calculations appear to be adequate. 7ah batteries to be provided for power supplies. See approved plans for clouded locations.

Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/22/20058/22/20058/22/2005PPASS
DetailsForrest France
Fire alarm permit is finaled.
Issue and Print Permit  8/11/2005 DONE
Alarm Plan Check8/10/2005 8/10/2005 PASS
DetailsTroy Cobbley
Plan Modification. Approved with comments
PLANS/APPL TAKEN TO FRONT DESK  8/10/2005 DONE
Inspection Record Card- Fire8/10/2005 8/10/2005 DONE
Permit Ready to Issue  8/10/2005 DONE
Plan resubmittals received  8/9/2005  
INSP-Final Inspection7/21/20057/22/20057/22/2005APART
DetailsForrest France
Final pending relocation of wall mounted strobe fire alarm notification devices to within code required heights AFF.
INSP-Final Inspection7/21/20057/21/20057/21/2005AFAIL
DetailsForrest France
The entire lens of wall mounted strobe devices must be installed between 80" and 96" AFF to meet code requirements, see fire alarm plan review notes.
Alarm Plan Check7/6/2005 7/6/2005 PASS
DetailsTroy Cobbley
7/6/2005-Plan modifications
PLANS/APPL TAKEN TO FRONT DESK  7/6/2005 DONE
Inspection Record Card- Fire7/6/2005 7/6/2005 DONE
Telephone call  7/6/2005 DONE
called and told her permit is ready and no fees
Permit Ready to Issue  7/6/2005 DONE
CHANGE STATUS TO (ISS)  7/6/2005 DONE
(F) Reprint permit  7/6/2005 DONE
Plan resubmittals received  7/5/2005 DONE
Issue and Print Permit  5/20/2005 DONE
Plan assigned to (Mary)5/3/2005 5/11/2005 DONE
Alarm Plan Check5/11/2005 5/11/2005 PASS
DetailsTroy Cobbley
PLANS/APPL TAKEN TO FRONT DESK  5/11/2005 DONE
DetailsTroy Cobbley
Permit Ready to Issue  5/11/2005 DONE
Inspection Record Card- Fire5/11/2005 5/11/2005 DONE
Telephone call  5/11/2005 DONE
Called and told that permit is ready & no fees due///5/11/05 12:27pm BAS
Case Summary  5/3/2005 DONE
Application received  5/3/2005