INSP-Final Inspection | 8/22/2005 | 8/22/2005 | 8/22/2005 | P | PASS |
Forrest France
|
|
|
Fire alarm permit is finaled.
|
Issue and Print Permit | | | 8/11/2005 | | DONE |
|
|
|
|
Alarm Plan Check | 8/10/2005 | | 8/10/2005 | | PASS |
Troy Cobbley
|
|
|
Plan Modification. Approved with comments
|
PLANS/APPL TAKEN TO FRONT DESK | | | 8/10/2005 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 8/10/2005 | | 8/10/2005 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 8/10/2005 | | DONE |
|
|
|
|
Plan resubmittals received | | | 8/9/2005 | | |
|
|
|
|
INSP-Final Inspection | 7/21/2005 | 7/22/2005 | 7/22/2005 | A | PART |
Forrest France
|
|
|
Final pending relocation of wall mounted strobe fire alarm notification devices to within code required heights AFF.
|
INSP-Final Inspection | 7/21/2005 | 7/21/2005 | 7/21/2005 | A | FAIL |
Forrest France
|
|
|
The entire lens of wall mounted strobe devices must be installed between 80" and 96" AFF to meet code requirements, see fire alarm plan review notes.
|
Alarm Plan Check | 7/6/2005 | | 7/6/2005 | | PASS |
Troy Cobbley
|
|
|
7/6/2005-Plan modifications
|
PLANS/APPL TAKEN TO FRONT DESK | | | 7/6/2005 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 7/6/2005 | | 7/6/2005 | | DONE |
|
|
|
|
Telephone call | | | 7/6/2005 | | DONE |
|
|
|
called and told her permit is ready and no fees
|
Permit Ready to Issue | | | 7/6/2005 | | DONE |
|
|
|
|
CHANGE STATUS TO (ISS) | | | 7/6/2005 | | DONE |
|
|
|
|
(F) Reprint permit | | | 7/6/2005 | | DONE |
|
|
|
|
Plan resubmittals received | | | 7/5/2005 | | DONE |
|
|
|
|
Issue and Print Permit | | | 5/20/2005 | | DONE |
|
|
|
|
Plan assigned to (Mary) | 5/3/2005 | | 5/11/2005 | | DONE |
|
|
|
|
Alarm Plan Check | 5/11/2005 | | 5/11/2005 | | PASS |
Troy Cobbley
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 5/11/2005 | | DONE |
Troy Cobbley
|
|
|
|
Permit Ready to Issue | | | 5/11/2005 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 5/11/2005 | | 5/11/2005 | | DONE |
|
|
|
|
Telephone call | | | 5/11/2005 | | DONE |
|
|
|
Called and told that permit is ready & no fees due///5/11/05 12:27pm BAS
|
Case Summary | | | 5/3/2005 | | DONE |
|
|
|
|
Application received | | | 5/3/2005 | | |
|
|
|
|