Permit Information
Permit NumberFIR05-00265
StatusFinaled
Name COMMERCIAL FIRE PROTECTION
Site Address 6710 SUPPLY WAY
Project NameSPR UG WESTERN TRAILER SHOP
Customer Number 
ePlanReview 
Description
WESTERN TRAILERS UNDERGROUND - To install approximately 90'-0" of C-900 PVC for a new 22,300-ft/2, one story, pre-engineered steel "Butler" shop building. The tap is connected off of Supply Way traveling northeast and east into some point in the building. The fire sprinkler underground work shall comply with NFPA 13-2002, NFPA 24-2002 the IFC-2000, attached review comment and conditions list, as regulated by the Fire Chief. These notes, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum fire code. This permit is attached to building permit: BLD05-00672.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection12/5/200512/5/200512/5/2005APASS
DetailsForrest France
UG fire supply finaled.
INSP-Alarm Testing11/2/200511/2/200511/2/2005PPASS
DetailsForrest France
Underground fire supply line permit finaled.
INSP-Final Inspection11/2/200511/2/200511/2/2005PCANC
DetailsForrest France
Duplicate inspection already called in.
INSP-Sprinkler Rough-in9/14/20059/15/20059/16/2005PPART
DetailsForrest France
First floor lower office sprinkler rough-in is good for cover, also discussed uprights above drop ceiling at second level and garage door coverage in the warehouse area.
INSP-Sprinkler Rough-in/Hydro6/28/20056/29/20056/29/2005APART
DetailsForrest France
Underground fire supply passed hydrostatic test. Still need to perform UG flushing.
INSP-Sprinkler Rough-in6/22/20056/23/20056/23/2005APART
DetailsForrest France
Underground fire supply line is approved for cover.
INSP-Sprinkler Rough-in6/21/20056/22/20056/22/2005AFAIL
DetailsForrest France
Fail, underground pipe has been buried prior to inspection for cover. Expose pipe and call for a re-inspect.
INSP-Sprinkler Rough-in6/16/20056/16/20056/16/2005PFAIL
DetailsForrest France
Underground piping must meet min. depth of bury req. NFPA 10.4.1, backfill at rock per 10.9.4, support per 10.7.9, distance from embankment per 10.5.4, and meet deflection requirements. The pipe laid over the large section of embeded rock in the trench fails to meet code standards and requirements.
INSP-Sprinkler Rough-in6/13/20056/13/20056/13/2005PPART
DetailsForrest France
Underground fire supply line riser piece and 5' stub out OK to cover. Still need provision for EQ clearance through floor slab.
Issue permit  6/6/2005  
Plan assigned to (Bill)5/3/2005 6/2/2005 DONE
Plan resubmittals received  6/2/2005  
Sprinkler Plan Check6/2/2005 6/2/2005 PASS
DetailsBill Alexander
Miscellaneous action  6/2/2005 DONE
Returned documents to the permit desk for returning to sender.
PLANS/APPL TAKEN TO FRONT DESK  6/2/2005 DONE
Permit Ready to Issue  6/2/2005 DONE
Inspection Record Card- Fire6/2/2005 6/2/2005 DONE
Telephone call  6/2/2005 DONE
called left messge permit is ready and fees
Sprinkler Plan Check5/3/2005 5/10/2005 FAIL
DetailsBill Alexander
1. Provide information on building underground riser through the floor of the proposed building which includes:
a. Provide pipe type and size of the underground riser extending through the floor of this building.
b. Provide clarification of all fitting, including any installing on the top of the riser.
c. Provide required thrust blocking information (in detail) installing on the riser piping and fitting/s.
d. Include how the piping will pass through the buildings footing or the distance of the top of pipe to bottom of footing.
(BMC 7-01-53-901.2 and IFC 901.2)

2. Provide clarification on why this designer is not including an outside control valve as required in BMC 7-01-53-903.1.3 or addressing an allowed alternative since outside controls should be installed under this type of permit.
Telephone call  5/10/2005 DONE
left message for John that plans failed and need picked up///5/10/005 1:25pm BAS
Application received  5/3/2005