Permit Information
Permit NumberFIR05-00266
StatusFinaled
Name COMMERCIAL FIRE PROTECTION
Site Address 111 S 6TH ST
Project NameSPR BOARDING HOUSE
Customer Number 
ePlanReview 
Description
(BOARDING HOUSE-EAST SIDE) This is a limited Scope of Work Permit. The east building will be fully fire sprinklered throughout with a NFPA 13 system for the conversion of an existing historic building to a boarding house (bed & breakfast). Fire sprinkler work includes a 6" C-900 PVC underground fire service supply from South Street, with an outside PIV, running into the basement of the west side building (restaurant). The inside fire sprinkler work includes the riser only in the restaurant and overhead supply main feed into the east side basement, with another system separation control for 5 sleeping units, a porch, entry, 3 bathroom some closets and common areas throughout. This fire protection work shall comply with the IFC 2003 and the permit review comments; each regulated by the Fire Chief. The review comments, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to BLD05-00011.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection12/22/200512/22/200512/22/2005PPASS
DetailsForrest France
Fire sprinkler permit finaled.
INSP-Final Inspection12/22/200512/22/200512/22/2005PPASS
DetailsForrest France
Fire sprinkler passed final inspection, c/n items are complete.
INSP-Sprinkler Rough-in/Hydro11/17/200511/18/200511/18/2005APART
DetailsForrest France
Overhead hydrostatic test passed inspection.
INSP-Sprinkler Rough-in/Hydro11/17/200511/17/200511/17/2005PFAIL
DetailsForrest France
Hydrostatic test started but failed midway due to pipe breakage per phone call from the GC.
INSP-Sprinkler Rough-in/Hydro11/9/200511/10/200511/10/2005PCANC
DetailsTroy Cobbley
No time for inspection
INSP-Sprinkler Rough-in8/24/20058/24/20058/24/2005PPART
DetailsForrest France
Underground fire supply line stub out to 8' of building is good for cover.
INSP-Sprinkler Rough-in8/17/20058/17/20058/17/2005APART
DetailsForrest France
Underground fire supply line between the restaurant and the boarding house is acceptable to cover with the sleeve installed per Bill Alexander.
INSP-Sprinkler Rough-in8/16/20058/16/20058/16/2005PFAIL
DetailsForrest France
Provide the correct set of approved drawings for this inspection, steel pipe is not allowed for underground fire service applications unless specifically listed.
Inspection Record Card- Fire8/10/2005 8/10/2005 DONE
Telephone call  8/10/2005 DONE
tlk to john warnick ###-#### that permit and fees are ready to be picked up
Sprinkler Plan Check7/28/2005 8/9/2005 PART
DetailsBill Alexander
1. Provide Backflow manufacturer, make and model data submittals with graphs. (BMC 7-01-50-901.2, NFPA 13-14.1.3 (41)

2. Detail the underground pipe type entering this (restaurant) basement. (BMC 7-01-50-901.2)

3. Plan FP-0 shows some rods connected of which is not identified on the plans? Provide detailed clarification of materials and appurtenances used for the prevention of acting thrust force on the underground entering in this project. (BMC 7-01-50-901.2)

4. Plan FP-1 address the sprinkler head blocked in the basement near the stairs. (BMC 7-01-50-901.2)

5. Provide required auxiliary drains of all trapped mains. Show the type, location and where draining on the plans. (BMC 7-01-50-901.2)

6. 7. Plans are incomplete. Provide detailed locations and area/s of calculation zone represented of the pipe being braced (on the plan) addressing and correlated with the sway brace calculation provided. If incorporating only one zone and similar bracing, then that zone must be shown to be the worst case within the structure/building. Include correlating earthquake-bracing details with their locations represented on the floor plan incorporating. The locations shall be coordinated with item #8 following. (IFC 105.4.2, 901.2, NFPA 13-9.3.5.2.1, 14.1.3 (39)

7. 8. Plans are incomplete. Provide type and location of joints. Include flexible pipe couplings where individual sections of piping 2½" or larger must be provided to move differentially with the individual sections of the building. Include the connection between the system piping and underground supply piping. Couplings shall be arranged to coincide with building structural separations. (NFPA 13-9.3.2*, 9.3.3*, A.9.3.3, A.9.3.2, 14.1.3 (21)

8. Plans are incomplete. The system pipe fittings and flexible couplings, etc. shall also be shown on the plans that correlate with locations for earthquake bracing. Eathquake brcing is completely missing. (BMC 7-01-50-901.2)

9. Plans are incomplete. Provide clarification of dry upright sprinklers protecting the attic.
a. This construction information for the roof supporting system which shall include structural member information. Provide section cut through north to south that show the truss system, and the spacing between (required to clarify spacing issues). (BMC 7-01-50-901.2, NFPA 13 Table 8.6.2.2.1)
b. Include maximum length of dry upright (within maximum manufacturers listing verification and possible restraint requirements). (BMC 7-01-50-901.2)
c. Provide information on separation of fire areas with piping penetrations (attic and second floor).

10. Plans are incomplete. Include the hydraulically designed system information on the hydraulic data nameplate and outline the area of test application verifying, on the plan FP-3. (NFPA 13-14.1.3[31])

11. Provide dimensioning and pipe size on the plans between nodes 9 & 10.

12. Designer shall separate both facilities from dual shutdowns for an individual service or repair. In the design provided, shutting off the Leku Restaurant will also shut down the Boarding House. Provide a corrected design that will isolate system controls for each facility. Revise and resubmit.

13. All changes must be clouded and referenced by a revision number as addressed in the bulleted items above, for easy identification and verification with submittals.

For details on the above, review comments, attached to permit (FIR05-00266FAILED2)
Miscellaneous action  8/9/2005 DONE
Returned 2 submittals to permit desk for required revisions.
Plan resubmittals received  7/28/2005  
Permit Ready to Issue  5/16/2005  
Telephone call  5/16/2005 DONE
lft message with message company ###-#### - no contact with john warnick
Inspection Record Card- Fire5/16/2005 5/16/2005 DONE
Issue and Print Permit  5/16/2005  
Sprinkler Plan Check5/5/2005 5/13/2005 PART
DetailsBill Alexander
The data has been moved to a Word document attached to this case.
PLANS/APPL TAKEN TO FRONT DESK  5/13/2005 DONE
Application received  5/5/2005  
INSP-Sprinkler Rough-in8/16/20058/17/2005 A 
DetailsForrest France
###-#### - bruce Note: after morning 9:00 ish
Plan assigned to (Bill)5/5/2005