Permit NumberFIR05-00272
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 2460 -2502 N BOGUS BASIN RD
Project NameSPR HIGHLANDS VILLAGE BLD 8
Customer Number 
ePlanReview 
Description
HIGHLANDS VILLAGE BLD #8 * 2460, 2462, 2502 N. Bogus Basin Rd. To install approximately 90'-0" of 4" C-900 PVC on the north and around the east side south, and up with a 4" D.I. riser piece to approximately 6" above concrete floor grade and to install overhead fire sprinkler protection throughout a new 13,266-ft/2 three story, four unit apartment building. The first floor is 4,346-ft/2 of which 2,912-ft/2 is for the garages (protected to Ordinary Group design) and the remaining is common area, (Light Hazard design). The second floor is 4,440-ft/2 and the third floor is 4,440-ft/2. These residential floors will be protected with a 13R design. Each unit on the second and third floors are single story units. This building is fire sprinklered per NFPA 13R for story increase. The fire sprinkler system work shall comply with the IFC 2000, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work. This permit is attached to building permit: BLD04-0943.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection10/9/200610/10/200610/10/2006APASS
DetailsTroy Cobbley
permit finaled
INSP-Final Inspection10/5/200610/6/200610/6/2006ACANC
DetailsTroy Cobbley
No time left in day for inspection
INSP-Sprinkler Rough-in/Hydro9/8/20069/11/20069/11/2006PPART
DetailsForrest France
AG hydrostatic test passed.
INSP-Sprinkler Rough-in/Hydro9/7/20069/8/20069/8/2006PCANC
DetailsTroy Cobbley
No time for the hydro test today
INSP-Sprinkler Rough-in4/11/20064/12/20064/13/2006APART
DetailsForrest France
Reducing bushing near the first floor riser and above the 3rd floor southeast master bathroom are not engaged properly in the fitting socket , elevator shaft heads are not installed at this time, the 2nd floor riser main is exposed in a closet-need to conceal or provide protection, possible light fixture obstruction at the 2nd floor west elevator lobby, no cover is allowed on the 3rd floor until a tenting inspection has been completed for cold cavity protection.
INSP-Sprinkler Rough-in4/10/20064/11/20064/11/2006PCANC
DetailsForrest France
No time available for this inspection today, to be rescheduled per agreement with contractor.
INSP-Sprinkler Rough-in/Hydro6/30/20056/30/20056/30/2005PPART
DetailsForrest France
UG rough-in resubmit, hydro test, and flushing preformed satisfactory.
INSP-Supply line flush6/30/20056/30/20056/30/2005PPART
DetailsForrest France
UG flush is okay.
CHANGE STATUS TO (ISS)  6/30/2005 DONE
(F) Reprint permit  6/30/2005 DONE
Sprinkler Plan Check6/24/2005 6/29/2005 PASS
DetailsBill Alexander
Modifications to undergroun on building #8.
R-2 Garage piping modified to protected CPVC.
Plan assigned to (Bill)6/24/2005 6/29/2005 DONE
PLANS/APPL TAKEN TO FRONT DESK  6/29/2005 DONE
Permit Ready to Issue  6/29/2005 DONE
Telephone call  6/29/2005 DONE
tlk to brodie ###-#### that permit and fees are ready to picked up
Plan resubmittals received  6/24/2005  
INSP-Supply line flush6/15/20056/16/20056/16/2005PFAIL
DetailsForrest France
Installation does not match approved plans, pipe routing has been changed significantly.
Issue and Print Permit  6/7/2005 DONE
Sprinkler Plan Check5/26/2005 6/6/2005 PASS
DetailsBill Alexander
Plan assigned to (Bill)5/26/2005 6/6/2005 DONE
DetailsBill Alexander
PLANS/APPL TAKEN TO FRONT DESK  6/6/2005 DONE
Permit Ready to Issue  6/6/2005  
Plan resubmittals received  5/26/2005 DONE
Plan assigned to (Bill)5/6/2005 5/17/2005 DONE
Sprinkler Plan Check5/6/2005 5/17/2005 PART
DetailsBill Alexander
1. The elevator shaft pits on the first floor is not located within a residential occupancy, but a "U-1" occupancy and shall be sprinklered per requirements of NFPA 13-8.14.5.1*. (BMC 7-01-50 -901.2)

2. Plans submitted are incomplete. Designer does not provide size of concealed spaces, attics, closets, and bathrooms or any small enclosures in which no sprinklers are to be installed. (NFPA 13R-6.1.7[9, 10])
Any assumption provided is not accepted. Revise and resubmit plans that meet requirements for verification of required fire protection. (BMC 7-01-50 -901.2)

3. Many restrooms which include showers and toilet spaces under this submittal will be considered part of the "restroom", since the designer does not address size or required separation on the plans. With lack of information, several restrooms on the 2nd and 3rd floors will require added fire sprinkler protection. Bathroom: Within a dwelling unit, any room or compartment containing a lavatory dedicated to personal hygiene, or a water closet, or bathing capability such as a shower or tub, or any combination of facilities thereof. A room is still considered a bathroom if it contains just a toilet. Bathroom compartments can be considered separate rooms provided they are enclosed with the required level of construction. (NFPA 13R-3.3.1*, A-3.3.1)
Any assumption provided is not accepted. Revise and resubmit plans that meet requirements for verification of required fire protection. (BMC 7-01-50 -901.2)

4. Manufacturer's data submittals provided for the Reliable Model F-1 Res 49 CCP Pendant, Reliable Model F3QR Q.R. Dry Pendant, and Reliable Model F1FR Q.R. sprinklers are all obsolete. Provide current manufacturers data submittals for all sprinkler heads submitting. (NFPA 13-3.3.1*)

5. Are the stair enclosures headed since you are installing residential heads in the same on the second and 3rd floors? Address this issue on the plans. (BMC 7-01-50 -901.2)

6. Residential sprinklers are currently listed for use under flat, smooth, horizontal ceilings. Sloped, beamed, and pitched ceilings could require special design features such as larger flows or a design for five or more sprinklers to operate in the compartment.
a. Has the designer verified slope/pitch requirements since it appears these heads are being installed outside there listing on the 3rd floor?
b.
c. Has the design spacing being measured on along the slope and not the floor, which means the actual floor coverage area will be less than the listed area.
Provide plans that address fire protection installation code and listed requirements issues and please reference Reliable's bulletin "035C" for correct listed installation practices.
PLANS/APPL TAKEN TO FRONT DESK  5/17/2005 DONE
Permit Ready to Issue  5/17/2005 DONE
Inspection Record Card- Fire5/17/2005 5/17/2005 DONE
Telephone call  5/17/2005 DONE
called told brodie permit is ready and fees
Issue and Print Permit  5/17/2005 DONE
Application received  5/6/2005