INSP-Final Inspection | 7/8/2005 | 7/11/2005 | 7/11/2005 | A | PASS |
Troy Cobbley
|
|
|
fire sprinkler finaled
|
INSP-Sprinkler Rough-in/Hydro | 7/5/2005 | 7/5/2005 | 7/5/2005 | P | PART |
Troy Cobbley
|
|
|
Retaining strap over men's restroom needs bent around truss and plans indicate 200 degree heads to be used but 155 have been used everywhere except they are mixed in the office and in the women's restroom. Piping is ok to cover
|
INSP-Sprinkler Rough-in/Hydro | 6/27/2005 | 6/28/2005 | 6/28/2005 | A | FAIL |
Troy Cobbley
|
|
|
No approved plans on site. No inspection done.
|
Override - Parcel Holds | | | 5/19/2005 | | |
|
|
|
|
Issue and Print Permit | | | 5/19/2005 | | DONE |
|
|
|
|
Plan assigned to (Bill) | 5/6/2005 | | 5/18/2005 | | DONE |
|
|
|
|
Sprinkler Plan Check | 5/6/2005 | | 5/18/2005 | | PASS |
Bill Alexander
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 5/18/2005 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 5/18/2005 | | 5/18/2005 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 5/18/2005 | | DONE |
|
|
|
|
Telephone call | | | 5/18/2005 | | DONE |
|
|
|
tlk to receptionist ###-#### that permit and fees are ready to be picked up
|
Application received | | | 5/6/2005 | | |
|
|
|
|