INSP-Final Inspection | 7/25/2005 | 7/25/2005 | 7/25/2005 | P | PASS |
Forrest France
|
|
|
Fire sprinkler permit finaled.
|
INSP-Final Inspection | 7/20/2005 | 7/20/2005 | 7/20/2005 | P | CANC |
Forrest France
|
|
|
Cancel per Troy with Treasure Valley Sprinkler, project not ready for final inspection.
|
INSP-Sprinkler Rough-in/Hydro | 6/20/2005 | 6/20/2005 | 6/20/2005 | A | PART |
Forrest France
|
|
|
Overhead hydrostatic test passed inspection.
|
INSP-Sprinkler Rough-in | 6/20/2005 | 6/20/2005 | 6/20/2005 | P | FAIL |
Forrest France
|
|
|
Verify correct size orfice on inspectors test, verify sammy screw size is listed for 2 1/2" pipe attatched vertically, overspaced longitudinal EQ brace, SSU above break room is too far below deck, provide as-builts for added head at entry and in accounting room, verify uprights after paint paper is removed, check L09 for blockage per. NFPA 8.6.5.1.2 at exposed beam- possibly not meeting density req. from L08.
|
INSP-Sprinkler Rough-in/Hydro | 6/16/2005 | 6/16/2005 | 6/16/2005 | P | CANC |
Forrest France
|
|
|
Wrong permit number called in. This inspection was for UG hydro and flush under permit fir05-00206 at the same address under the same building permit.
|
Issue and Print Permit | | | 5/27/2005 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 5/25/2005 | | 5/25/2005 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 5/25/2005 | | DONE |
|
|
|
|
Telephone call | | | 5/25/2005 | | DONE |
|
|
|
tlk to jeff anderson - ###-#### that permit and fees are ready to be picked up
|
Plan assigned to (Bill) | 5/10/2005 | | 5/24/2005 | | DONE |
|
|
|
|
Sprinkler Plan Check | 5/10/2005 | | 5/24/2005 | | PASS |
Bill Alexander
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 5/24/2005 | | DONE |
|
|
|
|
Miscellaneous action | | | 5/23/2005 | | DONE |
|
|
|
Plans are lacking information. Requested (email to Jeff T. Anderson) verification of construction information and the provided fire sprinkler spacing to verifiy requirements of NFPA 13-8.6.2.2.1.
|
Application received | | | 5/10/2005 | | |
|
|
|
|