INSP-Final Inspection | 6/2/2005 | 6/3/2005 | 6/3/2005 | A | PASS |
Forrest France
|
|
|
Fire alarm finaled.
|
Plan assigned to (Mary) | 5/17/2005 | | 5/27/2005 | | DONE |
|
|
|
|
Alarm Plan Check | | | 5/27/2005 | | PASS |
|
|
|
Approved pending PDS Fire Inspector field verification. No comments written.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 5/27/2005 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 5/27/2005 | | 5/27/2005 | | DONE |
|
|
|
|
Telephone call | | | 5/27/2005 | | DONE |
|
|
|
tlk charlie bayne ###-#### that permit is ready to be picked up
|
Permit Ready to Issue | | | 5/27/2005 | | DONE |
|
|
|
|
Issue and Print Permit | | | 5/27/2005 | | DONE |
|
|
|
|
Alarm Plan Check | | | 5/26/2005 | | FAIL |
|
|
|
Resubmittal required. The first floor is a single tenant. In discussion with Ron Hill, (Bldg Plan reviewer) no "corridor" is required. UBC 1991, 3305 (g,5) to allow non-rated corridors, smoke detectors required in the corridor and sprinklers throughout. The annunciation was defined as "zoned" and in areas required by the chief. Discussion with Charlie Bayne, Simplex, the first floor smoke detectors and H/S are no longer code compliant.
|
Application received | | | 5/17/2005 | | |
|
|
|
|
Case Summary | | | 5/17/2005 | | DONE |
|
|
|
|