Permit Information
Permit NumberFIR05-00296
StatusFinaled
Name SIMPLEX/GRINNELL
Site Address 3100 S VISTA AVE Unit: 140
Project Namealm - ICRMP BLDG-1ST FLR
Customer Number 
ePlanReview 
Description
To relocate one horn/strobe and one smoke detector into the open area from the remodeled area on the first floor. The fire alarm system beyond the permit area has not been reviewed for code compliance. No written comments. The PDS Fire Inspector to field verify functionality of the horn/strobe and smoke detector.

The associated building permit (BLD05-00894) is to remodel an existing 9,700 sq.ft. office by constructing a 200 sq.ft. office with entry vestibule per approved plans. Work to include, construction of approximately 40 lf of interior nonbearing, noncombustible partition, installation of a new door with lever hardware and side lite, modification to the ceiling area, lighting is being relocated, Dual Switching or occupancy sensor required, and miscellaneous related finishes, This building is fully fire sprinklered, any alterations the fire sprinkler system will require a separate permit. Rmh (APPLIED MATERIALS)(ICRMP BLDG-STE 140)
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection6/2/20056/3/20056/3/2005APASS
DetailsForrest France
Fire alarm finaled.
Plan assigned to (Mary)5/17/2005 5/27/2005 DONE
Alarm Plan Check  5/27/2005 PASS
Approved pending PDS Fire Inspector field verification. No comments written.
PLANS/APPL TAKEN TO FRONT DESK  5/27/2005 DONE
Inspection Record Card- Fire5/27/2005 5/27/2005 DONE
Telephone call  5/27/2005 DONE
tlk charlie bayne ###-#### that permit is ready to be picked up
Permit Ready to Issue  5/27/2005 DONE
Issue and Print Permit  5/27/2005 DONE
Alarm Plan Check  5/26/2005 FAIL
Resubmittal required. The first floor is a single tenant. In discussion with Ron Hill, (Bldg Plan reviewer) no "corridor" is required. UBC 1991, 3305 (g,5) to allow non-rated corridors, smoke detectors required in the corridor and sprinklers throughout. The annunciation was defined as "zoned" and in areas required by the chief. Discussion with Charlie Bayne, Simplex, the first floor smoke detectors and H/S are no longer code compliant.
Application received  5/17/2005  
Case Summary  5/17/2005 DONE