Permit Information
Permit NumberFIR05-00306
StatusFinaled
Name VIKING AUTOMATIC SPRINKLER CO
Site Address 403 S 11TH ST Unit: 300
Project NameSPR DR MICHAEL BAILEY
Customer Number 
ePlanReview 
Description
(DR MICHAEL BAILEY - 11TH & MYRTLE-3RD FLR-STE 300) To modify and existing shell fire sprinkler system installed under FIR05-00111 and add fire sprinkler protection in a new 3,164-ft/2 dental office tenant shell space located on the third floor north end. The fire sprinkler work is related to new interior walls a new one-hour rated medical gas closet, two new accessible restrooms, a shower and new suspended ceilings. This building is fully fire sprinklered for area increase. The fire sprinkler system work shall comply with the IFC 2003, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to building permit: BLD05-00463.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection7/25/20057/25/20057/25/2005PPASS
DetailsForrest France
Fire sprinkler permit finaled.
INSP-Final Inspection7/19/20057/21/20057/21/2005APART
DetailsForrest France
Work is satisfactory, final pending sign-off on shell permit FIR05-00111.
INSP-Sprinkler Rough-in/Hydro7/5/20057/6/20057/6/2005AFAIL
DetailsForrest France
Provide proper temp. head at location directly in front at soffit above recessed fireplace to meet req. of NFPA table 6.2.5.1.
INSP-Sprinkler Rough-in/Hydro6/30/20057/5/20057/5/2005ACANC
DetailsForrest France
Scheduled by a contractor via Hello! on 6/30/2005 at 3:27:53 PM. Contact: ###-####. Disp set to [CANC] by a contractor via Hello! on Jul 5 2005 7:07AM.
INSP-Sprinkler Rough-in/Hydro6/22/20056/23/20056/23/2005AFAIL
DetailsForrest France
Attatch missing retaining straps at two locations, clamp down retaining strap at end line east side, need 200 degree head in medical gas storage closet.
Issue permit  6/22/2005  
Sprinkler Plan Check6/7/2005 6/14/2005 PASS
DetailsBill Alexander
This is the tenant fire sprinkler design modification.

6/13/2005 - Entire 3rd floor resubmittal modifications does not include nodes (for verification of revised calculations). Called Steven Johnson (designer) and requested a corrected plan.

6/14/2005 - Provided
Miscellaneous action  6/14/2005 DONE
DetailsBill Alexander
Took revised approved plans/documents to permit desk for issuing.
Telephone call  6/14/2005 DONE
Left voice message for Steven and told him that permit is ready & fees///6/14/05 3:10pm BAS
Plan resubmittals received  6/7/2005  
Plan assigned to (Bill)5/20/2005 5/27/2005 DONE
Sprinkler Plan Check5/20/2005 5/27/2005 PASS
DetailsBill Alexander
PLANS/APPL TAKEN TO FRONT DESK  5/27/2005 DONE
Inspection Record Card- Fire5/27/2005 5/27/2005 DONE
Permit Ready to Issue  5/27/2005 DONE
Telephone call  5/27/2005 DONE
lft vm with steve johnson ###-#### that permit and fees are ready to be picked up
Case Summary  5/20/2005  
Application received  5/20/2005