INSP-Final Inspection | 7/25/2005 | 7/25/2005 | 7/25/2005 | P | PASS |
Forrest France
|
|
|
Fire sprinkler permit finaled.
|
INSP-Final Inspection | 7/19/2005 | 7/21/2005 | 7/21/2005 | A | PART |
Forrest France
|
|
|
Work is satisfactory, final pending sign-off on shell permit FIR05-00111.
|
INSP-Sprinkler Rough-in/Hydro | 7/5/2005 | 7/6/2005 | 7/6/2005 | A | FAIL |
Forrest France
|
|
|
Provide proper temp. head at location directly in front at soffit above recessed fireplace to meet req. of NFPA table 6.2.5.1.
|
INSP-Sprinkler Rough-in/Hydro | 6/30/2005 | 7/5/2005 | 7/5/2005 | A | CANC |
Forrest France
|
|
|
Scheduled by a contractor via Hello! on 6/30/2005 at 3:27:53 PM. Contact: ###-####. Disp set to [CANC] by a contractor via Hello! on Jul 5 2005 7:07AM.
|
INSP-Sprinkler Rough-in/Hydro | 6/22/2005 | 6/23/2005 | 6/23/2005 | A | FAIL |
Forrest France
|
|
|
Attatch missing retaining straps at two locations, clamp down retaining strap at end line east side, need 200 degree head in medical gas storage closet.
|
Issue permit | | | 6/22/2005 | | |
|
|
|
|
Sprinkler Plan Check | 6/7/2005 | | 6/14/2005 | | PASS |
Bill Alexander
|
|
|
This is the tenant fire sprinkler design modification.
6/13/2005 - Entire 3rd floor resubmittal modifications does not include nodes (for verification of revised calculations). Called Steven Johnson (designer) and requested a corrected plan.
6/14/2005 - Provided
|
Miscellaneous action | | | 6/14/2005 | | DONE |
Bill Alexander
|
|
|
Took revised approved plans/documents to permit desk for issuing.
|
Telephone call | | | 6/14/2005 | | DONE |
|
|
|
Left voice message for Steven and told him that permit is ready & fees///6/14/05 3:10pm BAS
|
Plan resubmittals received | | | 6/7/2005 | | |
|
|
|
|
Plan assigned to (Bill) | 5/20/2005 | | 5/27/2005 | | DONE |
|
|
|
|
Sprinkler Plan Check | 5/20/2005 | | 5/27/2005 | | PASS |
Bill Alexander
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 5/27/2005 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 5/27/2005 | | 5/27/2005 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 5/27/2005 | | DONE |
|
|
|
|
Telephone call | | | 5/27/2005 | | DONE |
|
|
|
lft vm with steve johnson ###-#### that permit and fees are ready to be picked up
|
Case Summary | | | 5/20/2005 | | |
|
|
|
|
Application received | | | 5/20/2005 | | |
|
|
|
|