Permit Information
Permit NumberFIR05-00315
StatusFinaled
Name VIKING AUTOMATIC SPRINKLER CO
Site Address 1100 S VISTA AVE
Project NameSPR UG VISTA VILLAGE-PHASED
Customer Number 
ePlanReview 
Description
VISTA VILLAGE SHOPPING CENTER-PHASED (BUILDING "E" UNDERGROUND) * Phase 1 is to stub out 5'-0" of 6" C-900 CPVC underground fire service supply and install a 6" underground riser located in the North East corner of a new, single story 6,135-ft/2 retail multi-tenant shell building with a 800-ft/2 covered entry facade. Phase 2 is to continue north 20'-0" then 90° west approximately 190'-0" with two 45º offsets and connect to the (United Water) tap at the property line at Vista. This building will be fully fire sprinklered. The fire sprinkler underground work shall comply with NFPA 13-2002, NFPA 24-2002, AWWA, the IFC-2000, attached review comment and conditions list, as regulated by the Fire Chief. These notes, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum fire code. This permit is attached to building permit: BLD05-00315.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection1/19/20061/19/20061/19/2006PPASS
DetailsForrest France
UG permit finaled.
INSP-Final Inspection1/19/20061/19/20061/19/2006PPASS
DetailsForrest France
UG fire supply line permit passed final inspection.
INSP-Supply line flush9/8/20059/8/20059/8/2005PPART
DetailsForrest France
Underground fire supply line flush is satisfactory.
INSP-Sprinkler Rough-in/Hydro8/8/20058/8/20058/8/2005PPART
DetailsForrest France
UG fire supply hydrostatic test passed.
INSP-Sprinkler Rough-in8/5/20058/5/20058/5/2005PPART
DetailsForrest France
Underground fire supply is acceptable to cover.
INSP-Supply line flush8/3/20058/4/20058/4/2005PFAIL
DetailsForrest France
Inspection was for an UG hydrostatic test and phase two UG cover inspection. Two 45 degree joints, the testing blank and a thrust block at the 90 are buried, preventing inspection The hydrostatic test was not ready.
Inspection Record Card- Fire7/18/2005 7/18/2005 DONE
Issue and Print Permit  7/18/2005 DONE
Sprinkler Plan Check7/8/2005 7/15/2005 PASS
DetailsBill Alexander
2nd phase
Miscellaneous action  7/15/2005 DONE
Took plan to permit desk for issuing. 2nd review no fee
Plan resubmittals received  7/8/2005  
INSP-Sprinkler Rough-in6/10/20056/10/20056/10/2005PPART
DetailsForrest France
Fire supply UG stub out and riser piece OK to cover. Verify seismic clearance and that no C900 is exposed above floor slab at a later date.
Issue and Print Permit  6/8/2005 DONE
Inspection Record Card- Fire6/7/2005 6/7/2005 DONE
Permit Ready to Issue  6/7/2005  
Telephone call  6/7/2005 DONE
left mess that permit is ready
Plan assigned to (Bill)5/25/2005 6/6/2005 DONE
Sprinkler Plan Check5/25/2005 6/6/2005 PASS
DetailsBill Alexander
1st Phase
6/3/2005 - 10:00am returned answer attached.

6/3/2005 - 8:15am - Emailed
1. The building permit submitted for this work to be attached too is related to the existing Building "D"? This work should be associated with new Building "E", BLD05-00315 (per your drawing)?

2. Is this 5'-0" out underground work the complete scope of work under this permit requesting? Will you be doing any more underground work on this line in the future?

3. I cannot accept your underground riser since it does not meet AWWA, Building and Plumbing Code. You are exposing a critical and required system with PVC piping in this facility without correct and approved "barrier protection/separation". I will lay this submittal to the side temporarily. Modify the riser with an approved carbon steel and resubmit and fax the modified riser to: ###-#### with transmittal letter, revised permit application, which includes the correct BLD number (ASAP), or I must deny the work and you will be required to submit through the normal channels.
PLANS/APPL TAKEN TO FRONT DESK  6/6/2005 DONE
Miscellaneous action  6/3/2005 DONE
Emailed designer for clarification and corrections for immediate response to continue the review. Will wait this day and then fail it if no response is provided.
Application received  5/25/2005