Permit Information
Permit NumberFIR05-00317
StatusFinaled
Name MICRON TECHNOLOGY INC FP
Site Address 8000 S FEDERAL WAY
Project NameSPR MICRON BUILDING 80 OFFICE
Customer Number 
ePlanReview 
Description
MICRON BUILDING #80 - To alter the existing fire sprinkler system to create a new 200-ft/2 office along the north wall. Fire sprinkler protection modifications are related to new walls (penetrate the ceiling grid by 6") ceiling modification, lights and HVAC. This fire protection work shall comply with the IFC 2003 and the permit review comments; each regulated by the Fire Chief. The review comments, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to BLD04-01407.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection7/13/20057/14/20057/14/2005APASS
DetailsTroy Cobbley
Fire sprinkler pemit finaled
INSP-Final Inspection7/11/20057/12/20057/12/2005AFAIL
DetailsTroy Cobbley
sprinkler pendants are overspaced.
INSP-Final Inspection7/6/20057/7/20057/7/2005AFAIL
DetailsTroy Cobbley
No approved plans on site.
Issue and Print Permit  6/6/2005 DONE
Plan assigned to (Bill)5/26/2005 6/3/2005 DONE
Case Summary  6/3/2005 DONE
Sprinkler Plan Check5/26/2005 6/3/2005 PASS
DetailsBill Alexander
Per modified plan changes.
PLANS/APPL TAKEN TO FRONT DESK  6/3/2005 DONE
Application received  5/26/2005