Permit Information
Permit NumberFIR05-00332
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 119 N 9TH ST
Project NameSPR ESTRELLA RESTAURANT
Customer Number 
ePlanReview 
Description
(ESTRELLA RESTAURANT - PLAZA 121 - BASEMENT AND 1ST FLR) To modify the existing fire sprinkler system for the tenant improvement work and the creation of a restaurant tenant space on the 1st story (3,479 square feet) and in the basement (1,433 square feet) of an existing 6 story building. All public areas are located on the 1st story with a kitchen in the basement and a kitchen on the 1st story. Fire sprinkler work is related to 2 restrooms, new interior nonbearing walls and suspended ceilings. This building is fire sprinklered in lieu of opening protection at the alley, rated corridors, basement enclosure, elevator lobbies, etc. It is also fire sprinklered because it has occupied floors more than 55 feet above the sidewalk and to allow one stairway to egress through a nonrated lobby on the 1st floor. This fire protection work shall comply with the IFC 2000 and the permit review comments; each regulated by the Fire Chief. The review comments, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to BLD05-00521.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection5/14/20095/15/20095/15/2009APASS
DetailsForrest France
Fire sprinkler permit okay for final status.
INSP-Final Inspection11/25/200511/25/200511/25/2005PPART
DetailsForrest France
Fire sprinkler passed inspection, final pending completion of the shell sprinkler permits.
INSP-Sprinkler Rough-in11/15/200511/16/200511/16/2005APART
DetailsForrest France
Basement kitchen area rough-in is good for cover.
INSP-Sprinkler Rough-in11/8/200511/8/200511/8/2005PPART
DetailsForrest France
The first floor rough-in is acceptable for cover.
Issue permit  8/25/2005 DONE
Sprinkler Plan Check8/15/2005 8/24/2005 PASS
DetailsBill Alexander
PLANS/APPL TAKEN TO FRONT DESK  8/24/2005 DONE
Inspection Record Card- Fire8/24/2005 8/24/2005 DONE
Permit Ready to Issue  8/24/2005 DONE
Telephone call  8/24/2005 DONE
tlk to gerald ebeling ###-#### that permit and fees are ready to be picked up
Plan assigned to (Bill)6/6/2005 8/24/2005 DONE
Plan resubmittals received  8/15/2005 DONE
Case Summary  8/15/2005 DONE
Telephone call  6/10/2005 DONE
plans failed customer took with him
Sprinkler Plan Check6/6/2005 6/9/2005 FAIL
DetailsBill Alexander
1. Previous pump test report indicates the shutoff is 191-psi. Maximum system operating pressure allowed for this pipe and fittings is: 175-psi. This facilities fire protection designs areas must fall within this limit or system modifications will be required and calculations reverified.

2. The kitchen and storage areas on the first floor and in the basement are considered Ordinary Hazard Group 1. The pipe sizing used for these areas does not match any previously hydraulically verified areas. The Hurtado TI was hydraulically calculated for OH-2 with the 1 ΒΌ" branch lines. The branch lines for the kitchen and storage reduce to 1". Provide pipe sizing to match the previously calculated OH-2 area or provide additional hydraulic calculations.

3. Dry pendants are shown in two rooms in the basement. It does not appear that the walls for these rooms extend to the ceiling. Provide information as to how high the walls are. Will these rooms be subject to temperatures lower than 40 degrees and this is the reason for the dry pendants?

4. On the floor plans there are two spaces with no fire sprinkler coverage between column lines H and G.9 and between 9 and 10 and just to the left of column line 8. Are these spaces non-combustible and non accessible?

5. Pendant heads in the Women's and Men's restrooms have two pendant heads piped from a single 1" outlet. See requirements of Note #18 below.

6. Are there two levels of pendant sprinkler heads in Dining II, Room 106? Provide section view/information for clarification.
Miscellaneous action  6/9/2005 DONE
Returned failed plans to permit desk for corrections.
Telephone call  6/9/2005 DONE
tlk to gerald ebeling ###-#### that permit has failed to picked up
Case Summary  6/6/2005 DONE
Application received  6/6/2005