INSP-Final Inspection | 10/9/2006 | 10/9/2006 | 10/9/2006 | P | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Supply line flush | 9/1/2005 | 9/2/2005 | 9/2/2005 | A | PART |
Forrest France
|
|
|
UG fire line flush is satisfactory. Advised contractor that the depth of bury still appears too shallow, however, site work is not complete. Will verify before final approval that the depth of cover is sufficient.
|
INSP-Sprinkler Rough-in/Hydro | 9/1/2005 | 9/2/2005 | 9/2/2005 | A | PART |
Forrest France
|
|
|
Hydrostatic test of the underground fire supply line passed. Although the site work is not completed, depth of bury still appears too shallow as evidenced by my mark on an adjacent concrete vault.
|
INSP-Sprinkler Rough-in | 8/26/2005 | 8/29/2005 | 8/29/2005 | A | FAIL |
Forrest France
|
|
|
Underground fire supply line installation does not match the approved drawings. Need to resubmit plans reflecting added 45's and change of directions for approval prior to field inspection. In addition, the minimum 4'-6" depth of bury is not met in several locations.
|
INSP-Sprinkler Rough-in | 8/26/2005 | 8/26/2005 | 8/26/2005 | P | CANC |
Forrest France
|
|
|
Canceled inspection, will schedule for monday the 29th.
|
Telephone call | | | 7/27/2005 | | DONE |
|
|
|
called told Trent permit ready for pickup and no fees
|
Inspection Record Card- Fire | 7/27/2005 | | 7/27/2005 | | DONE |
|
|
|
|
Plan resubmittals received | | | 7/26/2005 | | DONE |
|
|
|
|
Sprinkler Plan Check | 7/26/2005 | | 7/26/2005 | | PASS |
Bill Alexander
|
|
|
6" C-900 PVC underground change due to relocation of U.W. main tap, requiring an 30'-0" +- 45 degree offset to the north in the parking lot.
|
Miscellaneous action | | | 7/26/2005 | | DONE |
|
|
|
Took (faxed) approved changes to the permit desk for distributing.
|
Plan assigned to (Bill) | 6/8/2005 | | 6/20/2005 | | DONE |
|
|
|
|
Sprinkler Plan Check | 6/8/2005 | | 6/20/2005 | | PASS |
Bill Alexander
|
|
|
6/16/2005 - Conflict between Plan and permit scope of work. Called and emailed for correction.
6/17/2005 - Trent Bice responded by email that underground will be sized 6" and not 8" as indicated in the permit scope of work.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 6/20/2005 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 6/20/2005 | | 6/20/2005 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 6/20/2005 | | DONE |
|
|
|
|
Telephone call | | | 6/20/2005 | | DONE |
|
|
|
tlk to shilo ###-#### that permit and fees are readyto be picked up
|
Issue and Print Permit | | | 6/20/2005 | | DONE |
|
|
|
|
Application received | | | 6/8/2005 | | |
|
|
|
|