Permit Information
Permit NumberFIR05-00349
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 950 W BANNOCK ST
Project NameSPR UG 10TH & BANNOCK
Customer Number 
ePlanReview 
Description
10TH & BANNOCK BUILDING (SHELL & CORE-SOUTH UNDERGROUND SUPPLY) - To install a minimal length of 8" C-900 PVC fire service supply from the property line, located on the north side of Bannock Street and run under a footing in a proposed fire sprinkler riser room on the southeast area of this building, then up through the floor with 8" Ductile Iron to approximately 6" above finished floor grade with a 8" X 11½" adapter and Blind flange. This is a fire service supply for a new 182,950-ft/2, twelve story concrete and steel framed office and retail, high rise shell and core building. (Grading, Drainage and Foundation permitted under BLD04-01632) This fire sprinkler underground work shall comply with NFPA 13-2002, NFPA 24-2002 the IFC-2000, attached review comment and conditions list, as regulated by the Fire Chief. These notes, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum fire code. This permit is attached to building permit: BLD04-02348.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection4/24/20064/24/20064/24/2006PPASS
DetailsForrest France
Flush and hydro test completed under inspection requests for the project related overhead system permit number. UG fire supply line permit finaled.
INSP-Sprinkler Rough-in2/13/20062/13/20062/13/2006PPART
DetailsForrest France
UG supply stub-in and riser are good for cover, need to provide method for seismic clearance at the ductile riser and the approved stamped UG plan set at next inspection.
Plan assigned to (Bill)6/14/2005 6/15/2005 DONE
Sprinkler Plan Check6/14/2005 6/15/2005 PASS
DetailsBill Alexander
PLANS/APPL TAKEN TO FRONT DESK  6/15/2005 DONE
Inspection Record Card- Fire6/15/2005 6/15/2005 DONE
Permit Ready to Issue  6/15/2005 DONE
Telephone call  6/15/2005 DONE
lft ms with receptionist for gerald ###-#### that permit and fees are ready to be picked up
Issue and Print Permit  6/15/2005 DONE
Application received  6/14/2005