Information based on query as of Sunday, August 18, 2024.
Permit Information
Permit NumberFIR05-00355
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 2537 W STATE ST
Project NameSPR UG ST MARYS CROSSING BLD 1
Customer Number 
ePlanReview 
Description
ST MARY'S CROSSING BUILDING #1 (UNDERGROUND SHELL & CORE) - To install approximately 244'-0" of 6" PVC C-900 in a new 16,870-ft/2, two story, wood frame office shell and core building. The service tap is at the property line off 27th Street, running 114'-0" south, then, 110'-0" east with a PIV in a planter and continuing to a 45º. Then north approximately 20'-0" under the footing, then rising up through a fire sprinkler riser room approximately 6" above finish grade with 6" class 50 D.I., transitioned with a 6 X 10½" adapter and blank flange. This fire sprinkler underground work shall comply with NFPA 13-2002, NFPA 24-2002 the IFC-2003, attached review comment and conditions list, as regulated by the Fire Chief. These notes, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum fire code. This permit is attached to building permit: BLD05-00355.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection1/5/20061/5/20061/5/2006PPASS
DetailsForrest France
UG fire supply line passed inspection.
INSP-Final Inspection10/18/200510/18/200510/18/2005PPART
DetailsForrest France
Underground fire supply line flush is satisfactory.
INSP-Supply line flush8/30/20058/30/20058/31/2005PPART
DetailsForrest France
This inspection was for an underground hydrostatic test which passed.
INSP-Sprinkler Rough-in7/18/20057/19/20057/19/2005APART
DetailsForrest France
UG fire supply is good for cover.
Sprinkler Plan Check6/29/2005 6/30/2005 PASS
DetailsBill Alexander
Miscellaneous action  6/30/2005 DONE
3:05 pm. Took revised submittal to permit desk for reprinting, reissuing and returning.
Inspection Record Card- Fire6/30/2005 6/30/2005 DONE
Issue and Print Permit  6/30/2005 DONE
Telephone call  6/30/2005 DONE
tlk to jeff anderson -###-#### that permit is ready to be picked no fees
Plan resubmittals received  6/29/2005 DONE
INSP-Sprinkler Rough-in6/22/20056/22/20056/22/2005PPART
DetailsForrest France
Ductile iron riser piece and 8' stub out good for cover.
Issue permit  6/21/2005  
Plan assigned to (Bill)6/16/2005 6/20/2005 DONE
Sprinkler Plan Check6/16/2005 6/20/2005 PASS
DetailsBill Alexander
PLANS/APPL TAKEN TO FRONT DESK  6/20/2005 DONE
Inspection Record Card- Fire6/20/2005 6/20/2005 DONE
Telephone call  6/20/2005 DONE
tlk to brad ###-#### that permit and fees are ready to be picked up
Permit Ready to Issue  6/20/2005 DONE
Application received  6/16/2005  
Inspection Record Card- Fire6/30/2005