Permit Information
Permit NumberFIR05-00356
StatusFinaled
Name CRANE ALARM COMPANY
Site Address 5272 W IRVING ST
Project Namealm - WESTERN POWER SPORTS
Customer Number 
ePlanReview 
Description
To provide a voluntary manual fire alarm system in the two story office portion of the building only. The manual fire alarm system includes sprinkler monitoring, HVAC shutdown and notification throughout.

The associated building permit (BLD 04-01255) is to remodel the 1st floor and mezzanine office area of this existing warehouse tenant per approved plans. Total building is 24,000 sq.ft; 1st floor office area is 3,807 sq.ft. and mezzanine office area is 2,882 sq.ft. Work to include, interior demo, removal of bearing wall and installation of new footings, columns and beam, construction of four new accessible restrooms, construction of new stairway, installation of new guards and handrails on existing stairway, installation of a suspended ceiling system, new exterior sidewalk and stripping of parking lot, this building is fully fire sprinklered for area increase any alterations to the sprinkler system shall be per NFPA #13 as regulated by the fire department. (rmh) (WESTERN POWER SPORTS WAREHOUSE)
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection5/22/20065/23/20065/23/2006APASS
DetailsTroy Cobbley
permit finaled
Issue permit  10/26/2005 DONE
Permit Ready to Issue  10/18/2005 DONE
Inspection Record Card- Fire10/18/2005 10/18/2005 DONE
Telephone call  10/18/2005 DONE
left mess that permit is ready
Telephone call  10/18/2005 DONE
left mess that permit is ready
Alarm Plan Check  10/17/2005 PASS
Plan Modification. Approved pending field inspection of fire alarm permit comments.
PLANS/APPL TAKEN TO FRONT DESK  10/17/2005 DONE
Telephone call  9/12/2005 DONE
Received phone message from Brent Crane that the security system did not include mag locks, therefore no interface for the FA system is required.
Telephone call  8/24/2005 DONE
Brent Crane called, I explained that there are possible issues of security system and racking (extra sprinkler monitoring issues?) impacting the FA system. He stated that he will check on it and get back to me. I stated that I would "hold" these plans until I hear from him.
Miscellaneous action  8/24/2005 DONE
PLANS ON HOLD, pending additional information from Brent Crane.
Telephone call  8/23/2005 DONE
Left a message for Brent Crane regarding The Security Group's electrical permit to install a security system. Simply stated that I was trying to be proactive and letting them know in hopes of getting their final inspection completed the next time.
INSP-Final Inspection8/19/20058/19/20058/19/2005PPART
DetailsTroy Cobbley
A temporary occupancy was given with Jennifer's permission until all items on the correction notice have been corrected.
Plan resubmittals received  8/19/2005  
INSP-Alarm Testing8/15/20058/17/20058/17/2005AFAIL
DetailsTroy Cobbley
Resubmit plans showing the PIV. Device has been tested and comes in as point 20. Update map with the PIV and hilight the initiating devices for easier locating. Provide signage on the door to the fire alarm control panel.
Issue and Print Permit  6/23/2005 DONE
Plan assigned to (Mary)6/16/2005 6/22/2005 DONE
Alarm Plan Check  6/22/2005 PASS
Approved pending field inspection of fire alarm permit comments.
PLANS/APPL TAKEN TO FRONT DESK  6/22/2005 DONE
Inspection Record Card- Fire6/22/2005 6/22/2005 DONE
Telephone call  6/22/2005 DONE
lft vm with brent crane ###-#### that permit and fees are ready to be picked up
Permit Ready to Issue  6/22/2005 DONE
Case Summary  6/16/2005 DONE
Application received  6/16/2005