INSP-Final Inspection | 10/6/2006 | 10/9/2006 | 10/9/2006 | P | PASS |
Troy Cobbley
|
|
|
permit finaled
|
INSP-Final Inspection | 10/5/2006 | 10/6/2006 | 10/6/2006 | P | CANC |
Troy Cobbley
|
|
|
waiting on fire alarm
|
INSP-Final Inspection | 10/4/2006 | 10/5/2006 | 10/5/2006 | P | CANC |
Troy Cobbley
|
|
|
waiting on alarm
|
INSP-Final Inspection | 10/3/2006 | 10/4/2006 | 10/4/2006 | P | CANC |
Troy Cobbley
|
|
|
Waiting on fire alarm
|
INSP-Sprinkler Rough-in/Hydro | 9/6/2005 | 9/7/2005 | 9/7/2005 | A | PART |
Forrest France
|
|
|
Overhead hydrostatic test passed. Overhead rough-in missing retaining strap on one hanger which was installed while on site, one head appears to be overspaced at the east end from the exterior shell wall, will verify spacing at final.
|
Issue and Print Permit | | | 7/14/2005 | | DONE |
|
|
|
|
Plan assigned to (Bill) | 6/24/2005 | | 7/13/2005 | | DONE |
|
|
|
|
Sprinkler Plan Check | 7/7/2005 | | 7/13/2005 | | PASS |
Bill Alexander
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 7/13/2005 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 7/13/2005 | | 7/13/2005 | | DONE |
|
|
|
|
Telephone call | | | 7/13/2005 | | DONE |
|
|
|
called told lilly permit is ready and fees
|
Permit Ready to Issue | | | 7/13/2005 | | DONE |
|
|
|
|
Plan resubmittals received | | | 7/7/2005 | | DONE |
|
|
|
|
Telephone call | | | 6/28/2005 | | DONE |
|
|
|
Left message for trent that plans failed and need picked up///6/28/05 12:30pm BAS
|
Sprinkler Plan Check | 6/24/2005 | | 6/27/2005 | | FAIL |
Bill Alexander
|
|
|
1. Fire sprinkler systems installed in warehouse type buildings commonly referred to as "Spec" warehouses; where storage heights of combustible materials are possible over 12'-0" elevation, (Reference IFC Chapter 23), AND exact commodity, height of storage and storage system is unknown; shall be designed and installed according to the following criteria:
A. Minimum fire sprinkler system design shall be for a Class IV commodity, to the maximum available storage height, allowing for in-rack fire sprinklers, with "High Temperature Sprinklers" installed at the roof. It should be noted that if the warehouse is used to store a higher Class Commodity, upgrades to the sprinkler system shall be required.
B. It shall be the responsibility of the Fire Chief to evaluate all requests for a design meeting the requirements for a lower hazard storage configuration. Contact Mr. Dave Miller for approval/ acceptance at: ###-####.
The maximum clear height from floor to bottom of 2' deep trusses is approximately 15-16 feet. Provide revised plans and calculations addressing this minimum required system protection per BMC 7-01-56-903.1.6.
|
Miscellaneous action | | | 6/27/2005 | | DONE |
|
|
|
Returned failed plans to permit desk for returning and corrections.
|
Application received | | | 6/24/2005 | | |
|
|
|
|