Permit Information
Permit NumberFIR05-00369
StatusFinaled
Name ALARM SYSTEMS INTEGRATION INC
Site Address 1017 E PARK BLVD
Project NamealmPark Blvd Office Park-Bld D
Customer Number 
ePlanReview 
Description
To provide a required manual fire alarm system with manual fire boxes at all exits and total coverage notification throughout.

The associated building permit (BLD05-01345) is to create a private school for kindergarten through 6th grade within an existing 2,214 square foot, one story building. The school will occupy the entire building. Work is to include 2 restrooms accessible to the disabled, 4 exterior doors, interior nonbearing walls, millwork, and finishes. All work shall comply with the approved drawings, the plan review report, and all applicable codes. CUP05-00022 **CJW**2 (ARROWROCK CLASSICAL SCHOOL) This building is NOT fire sprinklered.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection11/21/200511/22/200511/22/2005APASS
DetailsForrest France
The duct detectors have been relocated and tested satisfactory, fire alarm permit finaled.
INSP-Alarm Testing9/6/20059/6/20059/7/2005APART
DetailsMary Froemke
kevin ###-####

Fire alarm system tested out fine. Two (2) duct detectors are installed incorrectly and need to be relocated. The duct detectors will need to be installed per the manufacturer's installation details and NFPA 72, 5.14.5. Re-inspection of the duct detectors, location, sampling tube orientation and testing will be required prior to 72 completion form signed and this permit finaled.
Alarm Plan Check  9/6/2005 PASS
Plan Modification. Approved pending field inspection of fire alarm permit comments.
PLANS/APPL TAKEN TO FRONT DESK  9/6/2005 DONE
CHANGE STATUS TO (ISS)  9/6/2005 DONE
per mary fromenke change status
Case Summary  9/6/2005 DONE
Case Summary  9/6/2005 DONE
Plan resubmittals received  9/6/2005 DONE
INSP-Alarm Testing9/1/20059/2/20059/2/2005PFAIL
DetailsForrest France
This inspection to be completed by Mary Froemke.

FAS does not match approved plans, incorrect candela ratings throughout the building and NAC panel does not match plans. Comments and cut sheets not on site for referral. Batteries are "swapped" from what the plans indicate.
Plan assigned to (Mary)6/24/2005 7/5/2005 DONE
Telephone call  7/5/2005 DONE
Left a message for Jack Schmidt regarding the "security access door release" and require a compatibility sheet for the ESL 521 smoke to the DMP panel.
Alarm Plan Check  7/5/2005 PASS
Approved pending field inspection of fire alarm permit comments.
PLANS/APPL TAKEN TO FRONT DESK  7/5/2005 DONE
Permit Ready to Issue  7/5/2005  
Inspection Record Card- Fire7/5/2005 7/5/2005 DONE
Telephone call  7/5/2005 DONE
Called and spoke with Jack and told him that permit is ready & fees///7/5/05 2:15pm BAS
CHANGE STATUS TO (ISS)  7/5/2005 DONE
Telephone call  6/30/2005 DONE
Left a message for Jack Schmidt regarding the height of the coat racks in the class rooms. Asked that he call me with the information. Jack returned my phone call, the coat racks are 36" tall.
Application received  6/24/2005  
Case Summary  6/24/2005