INSP-Final Inspection | 11/21/2005 | 11/22/2005 | 11/22/2005 | A | PASS |
Forrest France
|
|
|
The duct detectors have been relocated and tested satisfactory, fire alarm permit finaled.
|
INSP-Alarm Testing | 9/6/2005 | 9/6/2005 | 9/7/2005 | A | PART |
Mary Froemke
|
|
|
kevin ###-####
Fire alarm system tested out fine. Two (2) duct detectors are installed incorrectly and need to be relocated. The duct detectors will need to be installed per the manufacturer's installation details and NFPA 72, 5.14.5. Re-inspection of the duct detectors, location, sampling tube orientation and testing will be required prior to 72 completion form signed and this permit finaled.
|
Alarm Plan Check | | | 9/6/2005 | | PASS |
|
|
|
Plan Modification. Approved pending field inspection of fire alarm permit comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 9/6/2005 | | DONE |
|
|
|
|
CHANGE STATUS TO (ISS) | | | 9/6/2005 | | DONE |
|
|
|
per mary fromenke change status
|
Case Summary | | | 9/6/2005 | | DONE |
|
|
|
|
Case Summary | | | 9/6/2005 | | DONE |
|
|
|
|
Plan resubmittals received | | | 9/6/2005 | | DONE |
|
|
|
|
INSP-Alarm Testing | 9/1/2005 | 9/2/2005 | 9/2/2005 | P | FAIL |
Forrest France
|
|
|
This inspection to be completed by Mary Froemke.
FAS does not match approved plans, incorrect candela ratings throughout the building and NAC panel does not match plans. Comments and cut sheets not on site for referral. Batteries are "swapped" from what the plans indicate.
|
Plan assigned to (Mary) | 6/24/2005 | | 7/5/2005 | | DONE |
|
|
|
|
Telephone call | | | 7/5/2005 | | DONE |
|
|
|
Left a message for Jack Schmidt regarding the "security access door release" and require a compatibility sheet for the ESL 521 smoke to the DMP panel.
|
Alarm Plan Check | | | 7/5/2005 | | PASS |
|
|
|
Approved pending field inspection of fire alarm permit comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 7/5/2005 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 7/5/2005 | | |
|
|
|
|
Inspection Record Card- Fire | 7/5/2005 | | 7/5/2005 | | DONE |
|
|
|
|
Telephone call | | | 7/5/2005 | | DONE |
|
|
|
Called and spoke with Jack and told him that permit is ready & fees///7/5/05 2:15pm BAS
|
CHANGE STATUS TO (ISS) | | | 7/5/2005 | | DONE |
|
|
|
|
Telephone call | | | 6/30/2005 | | DONE |
|
|
|
Left a message for Jack Schmidt regarding the height of the coat racks in the class rooms. Asked that he call me with the information. Jack returned my phone call, the coat racks are 36" tall.
|
Application received | | | 6/24/2005 | | |
|
|
|
|
Case Summary | | | 6/24/2005 | | |
|
|
|
|