Permit Information
Permit NumberFIR05-00373
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 420 W MAIN ST Unit: 201
Project NameSPR VELTEX BLDG-2ND FLR
Customer Number 
ePlanReview 
Description
(ERSTAD THORNTON ARCHITECTS)(VELTEX BLDG-STE 201) This is a limited Scope of Work permit only. To relocate two fire sprinklers in an unfinished area for a 1,528-ft/2 office space. The building permit includes adding interior walls for 168-ft/2 conference room and 120-ft/2 for work area. Suspended ceiling system will be added in the lobby, conference and work room areas only. Other areas are open to structure above. This fire protection work shall comply with the IFC 2003 and the permit review comments; each regulated by the Fire Chief. The review comments, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to BLD05-1316.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/31/20059/1/20059/1/2005APASS
DetailsForrest France
Ceiling tile at the heads, escutcheons, and spare heads in the head box have been installed. Fire sprinkler permit finaled.
INSP-Sprinkler Rough-in/Hydro8/31/20059/1/20059/1/2005APART
DetailsForrest France
Overhead rough-in is okay to cover.
INSP-Final Inspection8/30/20058/31/20058/31/2005PCANC
DetailsForrest France
Jonathan is the contact on this job. Thank you; Phone #: ###-#### Internet Inspection Request from: Trent Bice
Contractor not available at site.
CHANGE STATUS TO (ISS)  8/30/2005 DONE
ok to change to ISS status per Bill A., not done when given back to Shiloh
Plan assigned to (Bill)8/12/2005 8/24/2005 DONE
DetailsBill Alexander
Sprinkler Plan Check8/18/2005 8/24/2005 PASS
DetailsBill Alexander
Per attached review comments
PLANS/APPL TAKEN TO FRONT DESK  8/24/2005 DONE
Inspection Record Card- Fire8/24/2005 8/24/2005 DONE
Permit Ready to Issue  8/24/2005 DONE
Telephone call  8/24/2005 DONE
tlk to trent bice ###-#### that permit and fees are ready to be picked up
Plan resubmittals received  8/19/2005 DONE
Telephone call  8/18/2005 DONE
called Trent on cell ###-#### told him need to pick up plans per failed, no fees
Sprinkler Plan Check8/12/2005 8/18/2005 FAIL
DetailsBill Alexander
08/15/2005-Sprinklers installing are E.C. heads not L.O.
Telephone call  8/15/2005 DONE
8/15/2005 - Contacted Trent Bice and indicated that sprinklers installing are E.C. heads not L.O.'s as originally installed by DeBest Fire Protection. Said he would check into it.

8/18/2005 - No response. Failed review and returned documents to permit desk for returning.
Plan resubmittals received  8/12/2005  
INSP-Final Inspection8/9/20058/10/20058/10/2005AFAIL
DetailsTroy Cobbley
Plans do not match floor layout. Resubmittals required. Per Bill Alexander coverage not required above the soffit as discussed.
Plan assigned to (Bill)6/28/2005 6/29/2005 DONE
Sprinkler Plan Check6/28/2005 6/29/2005 PASS
DetailsBill Alexander
PLANS/APPL TAKEN TO FRONT DESK  6/29/2005 DONE
Inspection Record Card- Fire6/29/2005 6/29/2005 DONE
Permit Ready to Issue  6/29/2005 DONE
Telephone call  6/29/2005 DONE
tlk to bill ###-#### - that permit and fees are ready to be picked up
Issue and Print Permit  6/29/2005 DONE
Application received  6/28/2005