Permit Information
Permit NumberFIR05-00377
StatusFinaled
Name PROTEX
Site Address 420 W MAIN ST Unit: 201
Project Namealm - VELTEX BLDG-2ND FLR; 201
Customer Number 
ePlanReview 
Description
To provide total coverage notification for the remodeled space on the 2nd floor. FIR05-00253 shall be completed prior to occupancy for this permit. (FIR05-00253 is to provide total coverage notification in the egress corridors on the 2nd floor to the stairwells). The required manual fire alarm system includes sprinkler monitoring, HVAC shutdown, fire/smoke damper control. Door release, elevator recall/shutdown and notification throughout.

The associated building permit (BLD 05-01316) is to finish a 1,528 sq.ft. office space and add interior walls for 168 sq.ft. conference room and 120 sq.ft. for work area. Work to include installation of suspended ceiling in the lobby, conference and work room areas. Other areas are open to structure above. Separate permits will be required for electrical, mechanical, plumbing, and fire sprinkler installation. All construction per the approved plans. Any alterations to the fire sprinkler system shall comply with NFPA #13 as regulated by the fire department. MJP (ERSTAD THORNTON ARCHITECTS)(VELTEX BLDG-STE 201)

Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection9/8/20059/9/20059/9/2005APASS
DetailsForrest France
Cd rating on one strobe which did not match plan was adjusted while on site, fire alarm permit finaled.
Inspection Record Card- Fire7/11/2005 7/11/2005 DONE
Permit Ready to Issue  7/11/2005 DONE
Telephone call  7/11/2005 DONE
tlk to rob ahten that permit and fees are ready to be picked up
Issue and Print Permit  7/11/2005 DONE
Telephone call  7/8/2005 DONE
Discussion with Rob Ahten, he would like to shift the 30 cd to the north to cover the work space. Acceptable per the conversation, I will mark up the drawings per his instruction.
Alarm Plan Check  7/8/2005 PASS
Approved pending field inspection of fire alarm permit comments.
PLANS/APPL TAKEN TO FRONT DESK  7/8/2005 DONE
Alarm Plan Check  7/7/2005 FAIL
Resubmittal or clarification is required. Faxed comments to Rob Ahten.
Telephone call  7/5/2005 DONE
Left a message for Rob regarding the qualifications of the architect as a PE.
Case Summary  6/29/2005  
Application received  6/29/2005  
Plan assigned to (Mary)6/29/2005