INSP-Final Inspection | 10/26/2005 | 10/27/2005 | 10/27/2005 | A | PASS |
Forrest France
|
|
|
Fire sprinkler passed inspection.
|
INSP-Final Inspection | 10/26/2005 | 10/26/2005 | 10/26/2005 | A | FAIL |
Forrest France
|
|
|
Review notes were not available on site for inspection, escutcheons are missing in three locations
|
INSP-Sprinkler Rough-in/Hydro | 10/13/2005 | 10/13/2005 | 10/13/2005 | P | PART |
Forrest France
|
|
|
Hydrostatic test of antifreeze system passed inspection.
|
INSP-Sprinkler Rough-in/Hydro | 10/10/2005 | 10/11/2005 | 10/11/2005 | P | CANC |
Troy Cobbley
|
|
|
Contact: Brian - Hydro Test; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley
|
INSP-Sprinkler Rough-in | 10/10/2005 | 10/11/2005 | 10/11/2005 | A | PART |
Troy Cobbley
|
|
|
Provide 200 degree pendant in the utility room, finish installing ceiling and canopies, provide longitudinal bracing on the antifreeze main under canopy. Per Bill the 130 sq. ft. max spacing is a type error. 225 sq. ft. is allowed in the light hazard areas.
|
INSP-Sprinkler Rough-in | 9/22/2005 | 9/22/2005 | 9/22/2005 | P | PART |
Forrest France
|
|
|
Overhead rough-in is okay for cover in the grid ceiling areas, will verify proper spacing and head temp. ratings at heat sources in the kitchen after all drops have been cut in. One branch line is directly over an electrical panel, this will need to be relocated per electrical code.
|
INSP-Sprinkler Rough-in | 8/19/2005 | 8/19/2005 | 8/19/2005 | A | PART |
Forrest France
|
|
|
Rough-in areas above hard lids are okay to cover, need to cut head in southwest soffit as discussed, GC to provide drop ceiling in storage room, antifreeze system is not complete or inspected at this time.
|
Sprinkler Plan Check | 7/6/2005 | | 7/7/2005 | | PASS |
Bill Alexander
|
|
|
Response to review comments item #16.
Manufacturer expansion chamber submittal provided. The contractor/installer shall provide appropriate data submittal documents on demand to the IFC Fire/Life Safety Inspector, addressing the installation of the listed expansion chamber being of appropriate size and provided with precharged air pressure (required to compensate for thermal expansion of the antifreeze solution as illustrated in Figure 7.5.3.2). appropriate size and correct (NDPA 13-7.5.3.3 )
|
Plan resubmittals received | | | 7/6/2005 | | |
|
|
|
Anti-freeze expansion tank.
|
Plan assigned to (Bill) | 6/29/2005 | | 7/5/2005 | | DONE |
|
|
|
|
Sprinkler Plan Check | 6/29/2005 | | 7/5/2005 | | PASS |
Bill Alexander
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 7/5/2005 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 7/5/2005 | | 7/5/2005 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 7/5/2005 | | |
|
|
|
|
Telephone call | | | 7/5/2005 | | DONE |
|
|
|
left mess that permit is ready
|
Issue permit | | | 7/5/2005 | | |
|
|
|
|
Case Summary | | | 6/29/2005 | | DONE |
|
|
|
|
Application received | | | 6/29/2005 | | |
|
|
|
|
INSP-Sprinkler Rough-in/Hydro | 8/18/2005 | 8/19/2005 | | A | |
Unknown
|
|
|
Contact: Jim - Cover Inspection; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley
|
INSP-Sprinkler Rough-in/Hydro | 8/10/2005 | 8/12/2005 | | A | |
Unknown
|
|
|
Contact: Brian Calkins - Rough In; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley
|
Inspection Record Card- Fire | 7/5/2005 | | | | |
|
|
|
|