Information based on query as of Sunday, August 18, 2024.
Permit Information
Permit NumberFIR05-00383
StatusFinaled
Name AIC SOLUTIONS INC
Site Address 3110 S BOWN WAY
Project Namealm BOWN CROSSING MARKET PLACE
Customer Number 
ePlanReview 
Description
To provide a provide monitoring for a cooking hood to an existing sprinkler monitoring fire alarm system. The existing horn/strobe (installed under FIR03-00738) is not required by code and will be removed. (It has already been removed. A double fee will apply for work without a permit). The HVAC unit that feeds the space has been relocated and the duct smoke detector reconnected. (also without a permit) Battery calculations appear to be sufficient. No written comments. The PDS Fire Inspector to field verify the alarm signal for the cooking hood, the supervisory signal with HVAC shutdown and red annotations on sheet FP-1.

The associated building permit (BLD04-02505) is to create a 2,308 sq.ft. restaurant on the entire first floor of an existing shell & core space (BLD03-02190) per approved plans. Work includes construction of new interior walls to create a kitchen / food prep area; walk in cooler; new type I hood & exhaust system with U.L. listed duct wrap assembly; finish interior side of exterior walls (energy code for envelope under S&C permit); suspended ceiling grid system in kitchen / scullery & gypsum board otherwise; provide electrical, plumbing, mechanical, fire sprinkler and alarm systems to meet tenant needs and comply with adopted current codes and ordinances. Reviewed plans include red-line comments on plans and all attached plan review conditions of reviewing agencies as part of the approved plans. drs At this time the space is vacant. Future tenant will require either a MIS or building permit. (KESSLER'S RESTAURANT)(BOWN CROSSING MARKET PLACE-BLDG 'B'-1ST FLR)
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection7/6/20057/6/20057/6/2005APASS
DetailsForrest France
HVAC units shut down upon smoke detection, fire alarm finaled.
INSP-Final Inspection7/1/20057/1/20057/1/2005PFAIL
DetailsForrest France
HVAC unit did not shut down upon smoke detection.
Issue and Print Permit  7/1/2005 DONE
Plan assigned to (Mary)6/30/2005 7/1/2005 DONE
Alarm Plan Check  7/1/2005 PASS
Approved pending PDS Fire Inspector field verification. No comments written.
PLANS/APPL TAKEN TO FRONT DESK  7/1/2005 DONE
Inspection Record Card- Fire7/1/2005 7/1/2005 DONE
Permit Ready to Issue  7/1/2005 DONE
Case Summary  6/30/2005 DONE
Application received  6/30/2005