INSP-Final Inspection | 7/26/2005 | 7/26/2005 | 7/26/2005 | P | PASS |
Troy Cobbley
|
|
|
Fire sprinkler finaled
|
INSP-Final Inspection | 7/25/2005 | 7/26/2005 | 7/26/2005 | A | FAIL |
Troy Cobbley
|
|
|
See approved plans for areas where the sprinkler pendants are still overspaced.
|
INSP-Sprinkler Rough-in | 7/22/2005 | 7/25/2005 | 7/25/2005 | P | CANC |
Troy Cobbley
|
|
|
Todd said they are not ready for inspection
|
INSP-Final Inspection | 7/22/2005 | 7/22/2005 | 7/22/2005 | P | FAIL |
Forrest France
|
|
|
A sprinkler head is not installed or shown on plans in a closet at the NE corner, missing hanger at arm over in office north side, heads in several offices on the west side are overspaced from adjacent walls, no further items inspected at this time. Contractor to re-schedule inspection when ready.
|
Issue and Print Permit | | | 7/12/2005 | | DONE |
|
|
|
|
Plan assigned to (Bill) | 6/30/2005 | | 7/11/2005 | | DONE |
|
|
|
|
Sprinkler Plan Check | 6/30/2005 | | 7/11/2005 | | PASS |
Bill Alexander
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 7/11/2005 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 7/11/2005 | | 7/11/2005 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 7/11/2005 | | DONE |
|
|
|
|
Telephone call | | | 7/11/2005 | | DONE |
|
|
|
lft ms with secretary ###-#### that permit and fees are ready
|
Application received | | | 6/30/2005 | | |
|
|
|
|