Permit Information
Permit NumberFIR05-00394
StatusFinaled
Name PROTEX
Site Address 121 N 9TH ST Unit: 300
Project Namealm - PLAZA 121;Lebois Partner
Customer Number 
ePlanReview 
Description
Fire alarm permit FIR04-00658 (shell and core) must be completed prior to occupancy for this permit (FIR05-00229).

To provide a new NAC extender panel (located 3rd floor east corridor), total notification and six (6) duct smoke detectors and relay modules for HVAC shutdown to the new TI space located on the third floor. The required manual fire alarm system includes sprinkler monitoring, HVAC shutdown, elevator recall/shutdown and notification throughout.

The associated building permit (BLD 05-01283) is to construct a 3,997 square foot office tenant space located on the 3rd story of an existing 6 story building. A non-rated common corridor will also be constructed. Work is to include interior nonbearing walls, suspended ceilings, interior doors, interior windows, and finishes. The work shall comply with the approved drawings, the plan review report, and all applicable codes. The fire sprinkler system shall comply with NFPA 13 as regulated by the Fire Department. **CJW** (LEBOIS PARTNERS INC. - STE 300) This building is required to be fully fire sprinklered.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection9/2/20059/2/20059/2/2005PPASS
DetailsForrest France
Fire alarm finaled.
INSP-Final Inspection8/31/20059/1/20059/1/2005ADEFR
DetailsForrest France
This inspection to be performed by Mary Froemke due to scheduling conflicts.
INSP-Final Inspection8/30/20058/31/20058/31/2005AFAIL
DetailsForrest France
The strobe in the confrence room is mounted too low for code requirements, duct smoke detectors tested okay, no other items inspected.
INSP-Final Inspection8/30/20058/30/20058/30/2005PCANC
DetailsForrest France
No time for inspection, Grant will reschedule for tomorrow per our conversation.
INSP-Final Inspection8/26/20058/29/20058/29/2005PNR
DetailsForrest France
Cancel inspection per Grant with Protex, not ready for inspection.
Override - Parcel Holds  7/11/2005  
Override - Parcel Holds  7/11/2005  
Inspection Record Card- Fire7/11/2005 7/11/2005 DONE
Override - Parcel Holds  7/11/2005  
Permit Ready to Issue  7/11/2005  
Telephone call  7/11/2005 DONE
tlk to rob ahten ###-#### that permit and fees are ready to be picked up
Override - Parcel Holds  7/11/2005  
Issue and Print Permit  7/11/2005 DONE
Plan assigned to (Mary)7/7/2005 7/8/2005 DONE
Alarm Plan Check  7/8/2005 PASS
Approved pending field inspection of fire alarm permit comments.
PLANS/APPL TAKEN TO FRONT DESK  7/8/2005 DONE
Telephone call  7/7/2005 DONE
Resubmittal required because the voltage drop calculations on circuit #13 are incorrect. Talked to Terry, she'll let Rob know, I said I would give 2 days before I deny them.
Application received  7/6/2005  
Case Summary  7/6/2005 DONE
Inspection Record Card- Fire7/11/2005