Permit Information
Permit NumberFIR05-00401
StatusFinaled
Name VIKING AUTOMATIC SPRINKLER CO
Site Address 1100 S VISTA AVE
Project NameSPR VISTA VILLAGE-PHASE I
Customer Number 
ePlanReview 
Description
VISTA VILLAGE SHOPPING CENTER (RITE AID-BUILDING D) * To add fire sprinklers from an added antifreeze system, connected to the existing system for a new front facade/canopy being constructed on an existing, single story, CMU exterior wall, Type V-B, retail building. The old canopy protection piping was demoed under FIR05-00242. This building is fire sprinklered for area increase. The fire sprinkler system work shall comply with the IFC 2000, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to building permit: BLD05-02461.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection2/16/20102/16/20102/16/2010APASS
DetailsForrest France
Fire sprinkler permit okay for final- required alarm work finished via project related FIR07-00116.
INSP-Final Inspection1/17/20061/17/20061/18/2006PNR
DetailsForrest France
Per contractor not ready for final inspection. The control valves for the antifreeze system must be monitored by the fire alarm panel, connection will require a FA permit.
INSP-Sprinkler Rough-in/Hydro7/27/20057/27/20057/27/2005PPART
DetailsForrest France
Overhead rough-in for antifreeze system at front canopy is acceptable to cover.
INSP-Sprinkler Rough-in/Hydro7/27/20057/27/20057/27/2005PPART
DetailsForrest France
Overhead hydrostatic test of antifreeze system at front canopy is satisfactory.
INSP-Sprinkler Rough-in/Hydro7/26/20057/26/20057/26/2005PFAIL
DetailsForrest France
Pendent heads along storefront canopy do not meet OH2 spacing requirements dictated by this occupant type and use for this specific area (see review notes- re-submittals req. for any changes), EQ attatchments in wood truss members must be through bolted, attic heads along sloped ceilings must orient deflector with the slope, perform hydrostatic test when system is complete and changes have been made.
Issue and Print Permit  7/18/2005 DONE
Inspection Record Card- Fire7/18/2005 7/18/2005 DONE
Plan assigned to (Bill)7/8/2005 7/15/2005 DONE
Sprinkler Plan Check7/8/2005 7/15/2005 PART
DetailsBill Alexander
Re-Submittals Of The Following Items Are Required:
1. This building is classified as an "M" occupancy. Anti-freeze system would appear to be under-designed. Canopy cover protection beneath is will probably require OH-2, (depending on the commodity/use) protection required. Provide a letter from the building owner which states that the area beneath the canopy structure will not be used for "Mercantile" use, displays and/or (sidewalk type) sales, etc. Signage will also be required to be posted at eye level along building wall every 20'-0" which states: "By order of the Fire Chief, this covered canopy shall have no combustible merchandise displayed or stored beneath for any reason, at anytime. IFC 102.8." Redesign or address the option and resubmit. (BMC 7-01-50 IFC 901.2, IFC 105.4.2)

2. Section view "C-C" provides minimal construction dimensions or information to verify fire sprinkler placement and design requirements:

a. No slope of ceiling provided,
b. No truss spacing and if construction meets 8.6.4.1.3 sprinkler are designed as such,
c. If combustible, unobstructed with members less than 3'-0" on centers the maximum upright sprinkler spacing is 130-ft/2 per 8.6.2.2.1,
d. Or if 8.6.4.1.4 applies, fire sprinkler do not,
e. Heads placement as provided would indicate applying 8.6.4.1.3, of which (by scaling) they are not within 3'-0" from the peak, etc., per requirements of 8.6.4.1.3.1,
Clarify construction and design, apply it to the plans and resubmit with enough information for verification of meeting fire sprinkler installation code requirements. (BMC 7-01-50 IFC 901.2, IFC 105.4.2)

3. Hanger detail (side beam, and trapeze) are detailed incorrectly. Screws in the side of a timber or joist shall be not less than 2½" from the lower edge where supporting branch lines and not less than 3" where supporting main lines. (NFPA 13-9.1.5.6.1)

4. Provide manufacturers data submittal for expansion chamber along with model identified. (BMC 7-01-50 IFC 901.2, IFC 105.4.2)
PLANS/APPL TAKEN TO FRONT DESK  7/15/2005 DONE
DetailsBill Alexander
Application received  7/8/2005