INSP-Final Inspection | 3/7/2007 | 3/7/2007 | 3/7/2007 | P | PASS |
Forrest France
|
|
|
Fire sprinkler passed final inspection, permit finaled.
|
INSP-Final Inspection | 2/22/2007 | 2/23/2007 | 2/23/2007 | A | PART |
Forrest France
|
|
|
Fire sprinkler permit work is ready for final pending satisfactory test of the riser supervisory and alarm devices per project related FA permit.
|
INSP-Sprinkler Rough-in | 10/10/2006 | 10/10/2006 | 10/10/2006 | P | PASS |
Troy Cobbley
|
|
|
third floor sprinkler piping can be covered
|
INSP-Conference | 10/3/2006 | 10/4/2006 | 10/4/2006 | A | FAIL |
Troy Cobbley
|
|
|
Insulation was not done yet.
|
INSP-Sprinkler Rough-in/Hydro | 9/11/2006 | 9/12/2006 | 9/12/2006 | P | PART |
Forrest France
|
|
|
OH hydrostatic test passed inspection.
|
INSP-Sprinkler Rough-in | 9/8/2006 | 9/11/2006 | 9/11/2006 | A | PART |
Forrest France
|
|
|
OH rough-in is good for cover on the first and second floors only, third floor will require a tenting inspection prior to cover.
|
INSP-Sprinkler Rough-in | 9/7/2006 | 9/8/2006 | 9/8/2006 | P | FAIL |
Troy Cobbley
|
|
|
The piping sizing in the end garage where the remote area is does not match plan. Plan shows 1" piping but 2" is installed. Also the 3rd floor remote area has a piping size problem as well and has been marked on the plans. No tenting has been done yet either. I gave Kennie permision to cover everything but the end garage and entire third floor until revised hydraulic calculations are provided and a tenting inspection is done.
|
FIR-Aging Inspection | 5/23/2006 | 5/23/2006 | 5/23/2006 | | DONE |
Forrest France
|
|
|
Building is still under construction, work in progress.
|
Issue and Print Permit | | | 7/21/2005 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 7/19/2005 | | DONE |
|
|
|
|
Telephone call | | | 7/19/2005 | | DONE |
|
|
|
left mess that permit is ready
|
Plan assigned to (Bill) | 7/8/2005 | | 7/18/2005 | | DONE |
|
|
|
|
Sprinkler Plan Check | 7/18/2005 | | 7/18/2005 | | PASS |
Bill Alexander
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 7/18/2005 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 7/18/2005 | | 7/18/2005 | | DONE |
|
|
|
|
Application received | | | 7/8/2005 | | |
|
|
|
|