INSP-Final Inspection | 10/6/2005 | 10/6/2005 | 10/6/2005 | P | PASS |
Troy Cobbley
|
|
|
Fire alarm permit finaled
|
INSP-Final Inspection | 9/28/2005 | 9/28/2005 | 9/28/2005 | P | FAIL |
Troy Cobbley
|
|
|
###-#### - matt
Four additional duct detectors were installed incorrectly, they will need to be relocated. Three will be in the crawl space, one in the attic and one will need to be added in the basement. RTS will be required and will need to be shown on the building map.
|
Issue and Print Permit | | | 9/28/2005 | | DONE |
|
|
|
|
Plan resubmittals received | | | 9/14/2005 | | DONE |
|
|
|
|
Alarm Plan Check | | | 9/14/2005 | | PASS |
|
|
|
Plan Modification. Approved pending field inspection of fire alarm permit comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 9/14/2005 | | DONE |
|
|
|
|
(F) Reprint permit | | | 9/14/2005 | | DONE |
|
|
|
|
INSP-Final Inspection | 9/12/2005 | 9/13/2005 | 9/13/2005 | P | PART |
Troy Cobbley
|
|
|
Tested all fire smoke dampers which functioned correctly. Need to resubmit plans showing the four additional duct detectors required. Need signage on fire alarm room door.
|
Issue permit | | | 7/19/2005 | | DONE |
|
|
|
|
Plan assigned to (Mary) | 7/8/2005 | | 7/18/2005 | | DONE |
|
|
|
|
Alarm Plan Check | | | 7/18/2005 | | PASS |
|
|
|
Approved pending field inspection of fire alarm permit comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 7/18/2005 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 7/18/2005 | | 7/18/2005 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 7/18/2005 | | |
|
|
|
|
Telephone call | | | 7/18/2005 | | DONE |
|
|
|
left mess that permit is ready
|
Case Summary | | | 7/8/2005 | | DONE |
|
|
|
|
Application received | | | 7/8/2005 | | |
|
|
|
|