INSP-Final Inspection | 12/6/2005 | 12/6/2005 | 12/6/2005 | P | PASS |
Forrest France
|
|
|
All c/n items are complete, fire sprinkler permit finaled.
|
INSP-Sprinkler Rough-in | 10/26/2005 | 10/26/2005 | 10/26/2005 | P | FAIL |
Forrest France
|
|
|
One head at sauna room is blocked by an adjacent cabinet, no escutcheons are installed at this time, discussed head location in laundry room and kitchen.
|
INSP-Sprinkler Rough-in | 7/29/2005 | 7/29/2005 | 7/29/2005 | P | PART |
Forrest France
|
|
|
Overhead fire sprinkler rough-in is satisfactory. Final pending installation of escutcheons, SW verification below catwalk, spare heads in headbox, verify current annual inspection on system.
|
INSP-Sprinkler Rough-in | 7/28/2005 | 7/28/2005 | 7/28/2005 | P | FAIL |
Forrest France
|
|
|
Minimum spacing requirements for the installed residential heads in storage room 103, bathroom closet 207, and master bedroom 201 are not met as required, (see plan review note #17).
|
Issue permit | | | 7/25/2005 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 7/22/2005 | | 7/22/2005 | | DONE |
|
|
|
|
Telephone call | | | 7/22/2005 | | DONE |
|
|
|
lft ms with secretary for jeff anderson ###-#### that permit and fees are ready to be picked up
|
Permit Ready to Issue | | | 7/22/2005 | | DONE |
|
|
|
|
Plan assigned to (Bill) | 7/15/2005 | | 7/21/2005 | | DONE |
|
|
|
|
Sprinkler Plan Check | 7/15/2005 | | 7/21/2005 | | PASS |
Bill Alexander
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 7/21/2005 | | DONE |
|
|
|
|
Application received | | | 7/15/2005 | | |
|
|
|
|