INSP-Final Inspection | 2/13/2007 | 2/14/2007 | 2/14/2007 | A | PASS |
Troy Cobbley
|
|
|
permit finaled. The last item on Dennis's correction notice, which was the head box has been corrected.
|
INSP-Final Inspection | 2/2/2007 | 2/2/2007 | 2/2/2007 | P | PART |
Forrest France
|
|
|
Signed temporary occupancy pending completion of correction notice.
|
INSP-Sprinkler Rough-in/Hydro | 1/31/2007 | 2/1/2007 | 2/1/2007 | A | PART |
Forrest France
|
|
|
Air test for the 4th floor dry system passed with a max. allowable drop of 1 1/2 psi. over 24 hrs. Noted two locations with wet ceiling tile at the head.
|
INSP-Sprinkler Rough-in/Hydro | 1/30/2007 | 1/31/2007 | 1/31/2007 | A | PART |
Forrest France
|
|
|
Begin 24 hr. air test of the 4th floor dry system at 49psi.@9:35 am.
|
INSP-Sprinkler Rough-in/Hydro | 1/29/2007 | 1/30/2007 | 1/30/2007 | A | PART |
Forrest France
|
|
|
OH hydrostatic test for the 4th floor dry system passed inspection.
|
INSP-Sprinkler Rough-in/Hydro | 1/29/2007 | 1/29/2007 | 1/29/2007 | P | PART |
Forrest France
|
|
|
Mechanical room hydrostatic test and the conclusion of the tank hydro both completed satisfactory.
|
INSP-Sprinkler Rough-in | 1/29/2007 | 1/30/2007 | 1/29/2007 | A | CANC |
Forrest France
|
|
|
Contact: Chris
Hydro - Mechanical Room Phone #: ###-#### Inspection cancelled from web by: Alicia Pauley
|
INSP-Sprinkler Rough-in/Hydro | 1/29/2007 | 1/30/2007 | 1/29/2007 | A | CANC |
Forrest France
|
|
|
Contact: Chris
Hydro 4th floor Phone #: ###-#### Inspection cancelled from web by: Alicia Pauley
|
INSP-Sprinkler Rough-in/Hydro | 1/26/2007 | 1/26/2007 | 1/26/2007 | P | PART |
Forrest France
|
|
|
Begin 72 hr. tank hydro test @ 2:40 pm (37" to water line).
|
INSP-Sprinkler Rough-in/Hydro | 1/23/2007 | 1/25/2007 | 1/26/2007 | A | PART |
Forrest France
|
|
|
Completed fire pump field acceptance test including pump curve, flow testing, controller operation, engine drive, and jockey pump. Noted some items in need of revision including removal of the ball valves in the pressure sensing lines (NFPA 20 12.5.2.1.6 B3), the exhaust pipe shall be covered or insulated per 11.5.3.3, repair the leak in the 1/2" cooling line at the engine, provide missing stop button at the controller. Also completed acceptable standpipe flow testing via fire pump and FD pumper vehicle.
|
INSP-Sprinkler Rough-in | 1/22/2007 | 1/23/2007 | 1/23/2007 | A | CANC |
Troy Cobbley
|
|
|
elisha; Phone #: ###-#### Internet Inspection Request from: Victoria Beall Inspection cancelled from web by: Alicia Pauley
|
CHANGE STATUS TO (ISS) | | | 1/22/2007 | | DONE |
|
|
|
|
Telephone call | | | 1/10/2007 | | DONE |
|
|
|
tlk to secretary for keith ###-#### that permit and fees are ready to be picked up
|
Permit Ready to Issue | | | 1/10/2007 | | DONE |
|
|
|
|
(F) Reprint permit | | | 1/10/2007 | | DONE |
|
|
|
|
CHANGE STATUS TO (ISS) | | | 1/10/2007 | | DONE |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 1/10/2007 | | |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 1/9/2007 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 1/9/2007 | | 1/9/2007 | | DONE |
|
|
|
|
Miscellaneous action | | | 1/8/2007 | | DONE |
|
|
|
Approved plans were received back from Brian Johnson today. The fee for the approval of this plan mod which began with a Denied review on Nov 30, is based on 43 hours of plan review time at $46.31/hr per Jenifer Gilliland's email of 11/28/06, which was relayed on the Keith Dilworth. Total due for this plan modification approval is $1,991.33.
|
Sprinkler Plan Check | 1/8/2007 | | 1/8/2007 | | PASS |
|
|
|
Plan review by Bryan Johnson Rev 9
|
Plan resubmittals received | | | 1/5/2007 | | |
|
|
|
|
Plan resubmittals received | | | 12/18/2006 | | |
|
|
|
|
INSP-Sprinkler Rough-in | 11/28/2006 | 11/29/2006 | 11/29/2006 | P | PART |
Forrest France
|
|
|
Overhead fire sprinkler is good for cover at the drop ceiling areas on the 4th floor as the required corrections have been verified for compliance.
|
INSP-Sprinkler Rough-in | 11/27/2006 | 11/28/2006 | 11/28/2006 | A | FAIL |
Forrest France
|
|
|
Inspection for the 4th floor drop ceiling-heads are overspaced at locations as marked on approved plans, heads at two locations are not installed, heads are shadowed by structural beams which are not indicated on plan set and create obstruction issues.
|
Override - Parcel Holds | | | 11/28/2006 | | |
|
|
|
|
Override - Parcel Holds | | | 11/28/2006 | | |
|
|
|
|
Sprinkler Plan Check | 11/15/2006 | | 11/28/2006 | | FAIL |
|
|
|
11/28/2006 -Additional Scope of Work: Revision #8
Under this revision noted as #5, several changes to the booster pump and riser manifold were submitted for review. The secondary water supply tank and supply piping was also revised. On the fifth floor, changes were made to accommodate the TI build out. The standpipe supply piping also appears to have been modified and submitted for review. Plans reviewed by B. Johnson, comments emailed to and discussed with Keith at DeBest.
An hourly plan mod fee will apply to this review per decision of J. Gilliland "Bill them $46.31 per hour for any additional review time."
email from B. Johnson: Sam, As of November 30, 2006, I have spent 25 hours on the BoDo Bldg. #8 / Hampton Inn Project. FIR06-00425. The rejected plan review comments were sent to your office and CC to DeBest on the 29th of November 2006. A resubmittal of those plans is required.
Bryan Johnson
Johnson Consulting
|
Override - Parcel Holds | | | 11/27/2006 | | |
|
|
|
|
Override - Parcel Holds | | | 11/27/2006 | | |
|
|
|
|
INSP-Sprinkler Rough-in | 11/15/2006 | 11/16/2006 | 11/16/2006 | A | PART |
Forrest France
|
|
|
Retest of the OH hydrostatic for the 6th floor passed inspeciton.
|
Plan resubmittals received | | | 11/16/2006 | | DONE |
|
|
|
received three sets of plans with application
|
Override - Parcel Holds | | | 11/15/2006 | | |
|
|
|
|
Override - Parcel Holds | | | 11/15/2006 | | |
|
|
|
|
INSP-Sprinkler Rough-in | 11/13/2006 | 11/13/2006 | 11/14/2006 | P | PART |
Forrest France
|
|
|
OH hydrostatic test of floors 5 and 7-10 completed satisfactory. The 6th floor failed due to a broken guage.
|
Override - Parcel Holds | | | 11/13/2006 | | |
|
|
|
|
Override - Parcel Holds | | | 11/13/2006 | | |
|
|
|
|
INSP-Sprinkler Rough-in/Hydro | 11/7/2006 | 11/8/2006 | 11/8/2006 | A | PART |
Forrest France
|
|
|
OH hydrostatic test of the 11th floor is acceptable.
|
Override - Parcel Holds | 1/1/1900 | 1/1/1900 | 11/7/2006 | | |
|
|
|
|
INSP-Sprinkler Rough-in | 10/19/2006 | 10/20/2006 | 10/20/2006 | A | PART |
Forrest France
|
|
|
Piping in the pool room 5th floor matches plans provided, calcs for this remote area to be verified by plan reviewer at resubmittal.
|
Override - Parcel Holds | 1/1/1900 | 1/1/1900 | 10/19/2006 | | |
|
|
|
|
INSP-Sprinkler Rough-in | 10/9/2006 | 10/10/2006 | 10/10/2006 | P | FAIL |
Troy Cobbley
|
|
|
Inspection was for the pool room. Two additional branchlines have been added at each end of the pool room. One of them is in the remote area and has been piped off of the 1 1/4" branchline. The starter pieces are now 1 1/4" instead of 1". Plans and calcs need to be resubmitted. Do not cover piping.
|
Override - Parcel Holds | 1/1/1900 | 1/1/1900 | 10/9/2006 | | |
|
|
|
|
INSP-Sprinkler Rough-in | 9/26/2006 | 9/27/2006 | 9/27/2006 | A | PART |
Forrest France
|
|
|
OH rough-in at the drop ceiling areas for the 5th floor corridors and pool room are good for cover, 11th floor corridor drop ceiling is also acceptable for cover.
|
Override - Parcel Holds | 1/1/1900 | 1/1/1900 | 9/26/2006 | | |
|
|
|
|
Sprinkler Plan Check | | | 9/19/2006 | | PASS |
|
|
|
Plan modification reviewed by B. Johnson, approved with revised comments. Modification includes 136 new heads.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 9/19/2006 | | DONE |
|
|
|
|
Telephone call | | | 9/19/2006 | | DONE |
|
|
|
spoke to liz@###-####/told permit was ready, project name & address, and fee
|
Override - Parcel Holds | | | 9/19/2006 | | |
|
|
|
|
Inspection Record Card- Fire | 9/19/2006 | | 9/19/2006 | | DONE |
|
|
|
|
Override - Parcel Holds | | | 9/19/2006 | | |
|
|
|
|
Permit Ready to Issue | | | 9/19/2006 | | DONE |
|
|
|
|
CHANGE STATUS TO (ISS) | | | 9/19/2006 | | |
|
|
|
picked up plans
|
(F) Reprint permit | | | 9/19/2006 | | DONE |
|
|
|
|
INSP-Sprinkler Rough-in/Hydro | 9/18/2006 | 9/18/2006 | 9/18/2006 | P | PART |
Forrest France
|
|
|
10th floor corridor is okay for cover at the drop ceiling areas, noted lacking proper coverage at the far corner of the electrical room, two heads are overspaced at the north end of the main corridor, discussed coverage at the elevator lobby on the 9th floor.
|
Plan resubmittals received | | | 9/13/2006 | | DONE |
|
|
|
Received re-submittals of plans for BODO # 8 Hotel( resubmittal of five pump layout sent to Fire ///DLD
|
INSP-Sprinkler Rough-in/Hydro | 9/6/2006 | 9/7/2006 | 9/7/2006 | A | PART |
Forrest France
|
|
|
9th floor is good for cover at the drop ceiling areas in the corridor, noted one location at the electrical room which is lacking coverage. 10th floor corridor is not ready for cover inspection at this time.
|
INSP-Sprinkler Rough-in/Hydro | 8/31/2006 | 8/31/2006 | 9/1/2006 | P | PART |
Forrest France
|
|
|
Drop ceiling areas in the confrence rooms, adjacent to the pool, and SE of stairs are okay to cover. Noted two overspaced heads in in the public restrooms.
|
INSP-Sprinkler Rough-in/Hydro | 8/28/2006 | 8/28/2006 | 8/28/2006 | P | PART |
Forrest France
|
|
|
8th floor corridor fire sprinklers are good for cover.
|
INSP-Sprinkler Rough-in/Hydro | 8/21/2006 | 8/21/2006 | 8/21/2006 | P | PART |
Forrest France
|
|
|
5th floor confrence rooms at the drop ceiling areas are good for cover.
|
INSP-Sprinkler Rough-in/Hydro | 8/16/2006 | 8/16/2006 | 8/16/2006 | P | PASS |
Troy Cobbley
|
|
|
The sprinkler piping in the remaining guest room on the 11th floor is ok to cover.
|
INSP-Sprinkler Rough-in/Hydro | 8/10/2006 | 8/11/2006 | 8/11/2006 | A | PART |
Forrest France
|
|
|
8th and 9th floor guest room adjacent to the temp. elevator are good for cover.
|
INSP-Sprinkler Rough-in/Hydro | 8/8/2006 | 8/9/2006 | 8/10/2006 | P | PART |
Forrest France
|
|
|
7th floor guest room rough-in and items from previous c/n on this floor are complete.
|
INSP-Sprinkler Rough-in/Hydro | 8/2/2006 | 8/3/2006 | 8/3/2006 | P | PART |
Forrest France
|
|
|
OH inspection for cover at the drop ceiling areas in the 1st floor hotel lobby are good for cover- noted corrections at this location have been completed, noted one sw at garage door west side is too low as installed. Also inspected 6th floor guest room adjacent to temp elevator for rough-in.
|
INSP-Sprinkler Rough-in/Hydro | 7/31/2006 | 7/31/2006 | 8/1/2006 | P | PART |
Forrest France
|
|
|
OH rough-in at the hotel lobby drop ceiling areas as noted are okay to cover, two heads in the hard lid above reception counter do not meet min. spacing req.
|
INSP-Sprinkler Rough-in/Hydro | 7/27/2006 | 7/28/2006 | 7/28/2006 | P | FAIL |
Forrest France
|
|
|
Inspection for cover at the drop ceiling areas in the lobby first floor failed due to architectural changes not shown on sprinkler plans which affect layout, significant field changes in head location from approved plans, lacking proper coverage at some locations. Submit approved plans reflecting changes and revised sprinkler head locaitons prior to next inspection for cover at this area.
|
INSP-Sprinkler Rough-in/Hydro | 7/20/2006 | 7/20/2006 | 7/21/2006 | P | PART |
Forrest France
|
|
|
Noted defficiencies from previous inspection on the 5th floor have been corrected.
|
Plan assigned to (Bill) | 7/19/2006 | | 7/21/2006 | | DONE |
Bill Alexander
|
|
|
|
Sprinkler Plan Check | 7/19/2006 | | 7/21/2006 | | PASS |
Bill Alexander
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 7/21/2006 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 7/21/2006 | | DONE |
|
|
|
|
Telephone call | | | 7/21/2006 | | DONE |
|
|
|
left mess that permit is ready
|
CHANGE STATUS TO (ISS) | | | 7/21/2006 | | DONE |
|
|
|
|
(F) Reprint permit | | | 7/21/2006 | | DONE |
|
|
|
|
Plan resubmittals received | | | 7/19/2006 | | |
|
|
|
|
INSP-Sprinkler Rough-in/Hydro | 7/13/2006 | 7/14/2006 | 7/14/2006 | P | PASS |
Troy Cobbley
|
|
|
The two heads and associated piping located in the first floor elevator lobby are ok to cover.
|
INSP-Sprinkler Rough-in/Hydro | 7/12/2006 | 7/12/2006 | 7/12/2006 | P | PART |
Troy Cobbley
|
|
|
5th Floor piping is ok to cover except for the areas as marked on the plans which need correcting.
|
INSP-Sprinkler Rough-in/Hydro | 7/12/2006 | 7/12/2006 | 7/12/2006 | P | CANC |
Forrest France
|
|
|
Contact: Fred; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley Inspection cancelled from web by: Alicia Pauley
|
(F) Reprint permit | | | 7/10/2006 | | DONE |
|
|
|
|
CHANGE STATUS TO (ISS) | | | 7/10/2006 | | DONE |
|
|
|
|
Plan assigned to (Bill) | 1/5/2006 | | 7/7/2006 | | DONE |
Bill Alexander
|
|
|
|
Sprinkler Plan Check | 6/20/2006 | | 7/7/2006 | | PART |
Bill Alexander
|
|
|
July 7, 2006 - Provided the Followinbg Information
iii. Provide revised hydraulic calculations for standpipe design incorporating Stair #3 and #4, (750 gpm combined flows) operating with the "Break Tank" supply design required.
iv. Resubmit complete hydraulic calcs of all most remote/demanding areas incorporating only the Break-Tank suction design. Include corrected installation plans incorporating all installation modifications with piping, etc.
v. This system incorporates a 1000 gpm pump at 150 psi pressure. 120% churn pressure will produce 180 psi on the system. Maximum allowed pressure allowed on this system (as installed) will be 175 psi. Provide clarification as to where the 5 psi will relieve/discharge.
vi. Provide setting of the system PRV valve and include "Q" water volume discharge.
vii. Provide the fire pump and jockey pressure settings on the plans incorporating this systems design.
viii. Leak detection is to be provided in the elevator pits in lieu of leak containment around the tank. Fire alarm contractor is not aware of this responsibility as indicated in April 7, 2006 response. This has also not been included on any plans. This requirement will be verified under the Final Fire Alarm Plan Review with testing provided prior to final system acceptance.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 7/7/2006 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 7/7/2006 | | DONE |
|
|
|
|
Telephone call | | | 7/7/2006 | | DONE |
|
|
|
spoke to keith@###-####/told permit was ready and fee associated with it
|
INSP-Sprinkler Rough-in/Hydro | 6/29/2006 | 6/30/2006 | 6/30/2006 | A | PART |
Forrest France
|
|
|
OH rough-in for the 11th floor is acceptable for cover at the hard lid areas.
|
INSP-Sprinkler Rough-in/Hydro | 6/27/2006 | 6/29/2006 | 6/29/2006 | P | PART |
Forrest France
|
|
|
Cover inspection for the hotel lobby hard lid entry area is good for cover.
|
Plan resubmittals received | | | 6/20/2006 | | |
|
|
|
|
INSP-Sprinkler Rough-in/Hydro | 6/5/2006 | 6/6/2006 | 6/7/2006 | A | PART |
Forrest France
|
|
|
Overhead inspection for the 1st floor hotel lobby soffits, 9th floor main, 10th and 11th floors performed today. The 1st floor soffits are okay to cover-corrections have been completed, 9th floor is acceptable to cover, 10th floor installation is okay-still need to fire caulk wall penetrations prior to cover. The 11th floor failed due to missing EQ brace, overspaced heads at three locations, missing upright at SE stair landing.
|
INSP-Sprinkler Rough-in/Hydro | 6/2/2006 | 6/2/2006 | 6/5/2006 | P | FAIL |
Forrest France
|
|
|
Overhead inspection performed for the 1st floor hard lid soffit areas at the hotel lobby-some areas are overspaced, heads not roughed in as shown on plans, be aware of obstructions by adjacent soffits to to higher drop ceiling areas. Also inspected the 9th floor rough-in, installation appears acceptable except for the west main which is still concealed by sheetrock lids- this area will need to be exposed for inspection before approval for cover can be granted for the 9th floor.
|
INSP-Sprinkler Rough-in/Hydro | 5/31/2006 | 6/1/2006 | 6/1/2006 | A | FAIL |
Forrest France
|
|
|
Overhead rough-in inspection for cover at the 9th floor failed due to nearly all the piping having been concealed above the ceiling by sheetrock hard lids previous to inspection. No inspection could be performed, notified general contractor of the need to expose the pipe for viewing prior to next inspection request. See note #255 on fire code plan review.
|
INSP-Sprinkler Rough-in/Hydro | 5/30/2006 | 5/31/2006 | 5/31/2006 | A | CANC |
Troy Cobbley
|
|
|
Contact: Fred; Phone #: ###-#### I called listed phone number twice and left two messages. No inspection performed. Will need to be rescheduled.
|
INSP-Sprinkler Rough-in/Hydro | 5/12/2006 | 5/15/2006 | 5/15/2006 | A | FAIL |
Forrest France
|
|
|
One pendent head in a soffit at a south guest room is overspaced, missing a lateral EQ brace at the end of SW main, need to provide stamped plans showing field modifications at next inspection, all remaining areas on the 8th floor are acceptable for rough-in cover except as noted.
|
INSP-Sprinkler Rough-in/Hydro | 4/28/2006 | 5/1/2006 | 5/1/2006 | A | PART |
Forrest France
|
|
|
Overhead fire sprinkler rough-in for the 7th floor is good for cover, need to relocate two overspaced uprights at the SE stair landing, one pendent in SW guest room is overspaced, need to provide approved plans showing design changes and added heads at guest room soffits.
|
INSP-Sprinkler Rough-in/Hydro | 4/13/2006 | 4/14/2006 | 4/14/2006 | A | PART |
Forrest France
|
|
|
6th floor cover inspection related to the fire sprinklers at the hard lid areas is acceptable.
|
INSP-Sprinkler Rough-in/Hydro | 4/7/2006 | 4/10/2006 | 4/10/2006 | A | PART |
Forrest France
|
|
|
Overhead rough-in inspection for the 6th floor is good for cover at the hard lid areas as discussed, items addressed include missing 4-way EQ brace, blocked ssu at south stair #1, fire caulking not complete in some areas, added lines in guest room soffits must be shown on plan, be aware of possible light fixture and soffit obstructions, some SW heads are not cut in at this time, laundry chute head is not piped.
|
INSP-Sprinkler Rough-in/Hydro | 3/20/2006 | 3/21/2006 | 3/21/2006 | P | PART |
Forrest France
|
|
|
Standpipe flow test performed satisfactory with the required flow and residual pressure required.
|
INSP-Final Inspection | 3/13/2006 | 3/13/2006 | 3/13/2006 | P | FAIL |
Forrest France
|
|
|
Provide functional alarm pressure switch at the third floor dry system, repair air compressor at the third floor, provide annual tags on risers, repair stop button at pump controller, secure drum drip assemblies to structure, perform final walkthrough for dry systems code compliance.
|
INSP-Final Inspection | 3/8/2006 | 3/10/2006 | 3/10/2006 | P | FAIL |
Forrest France
|
|
|
Standpipe flow test failed to supply the required flow and residual pressure needed. Some c/n items related to the fire pump inspected including test of low fuel supervision device, aux. tank valves have been installed, lock provided on fuel line, heads above aux. tank. Still need flow performance curve data, missing stop button, tags on risers, dry system air compressors set, perform the remainder of alarm testing related to fire sprinkler systems.
|
INSP-Sprinkler Rough-in/Hydro | 3/8/2006 | 3/10/2006 | 3/10/2006 | A | PART |
Forrest France
|
|
|
Two hour hydrostatic test for the standpipes in stairwells one and two passed inspection.
|
INSP-Sprinkler Rough-in/Hydro | 3/3/2006 | 3/9/2006 | 3/9/2006 | A | FAIL |
Forrest France
|
|
|
Several c/n items from the previous day's inspections have not been completed including installation of the aux. tank valves, lock at the fuel line valve, repaired stop button at controller, flow chart data, controller monitoring of fuel levels per NFPA 20 2003 11.4.5.7 and 12.4.1.3 (11). Need to finish branch line above the tank at mech. room, install heads with wrench and NFPA 25 in the head box, install air compressors and re-set dry system air values, installation/inspection tags on the riser.
|
INSP-Sprinkler Rough-in/Hydro | 3/8/2006 | 3/9/2006 | 3/9/2006 | P | FAIL |
Forrest France
|
|
|
Hydrostatic test of the standpipes in stair 1 and 2 failed due to pressures below 200 psi at several levels.
|
INSP-Sprinkler Rough-in/Hydro | 3/7/2006 | 3/8/2006 | 3/9/2006 | P | PART |
Forrest France
|
|
|
Acceptance test for the fire pump is partially completed, need to verify controller supervisory conditions including overspeed, overtemp, battery charger failure, low fuel, engine trouble, items on review note 31, replace casing drain line with non-corrosive pipe, replace broken controller stop button, install valving to the auxillary tank, lock fuel line valve open, supply performance flow charts for verification, still need to perform the tank suction test, churn psi is above the working pressure limits of the system. Flow test, starts/stops, controller settings, run time, battery switching, rpm, prv have been tested.
|
INSP-Sprinkler Rough-in/Hydro | 3/6/2006 | 3/8/2006 | 3/9/2006 | A | FAIL |
Forrest France
|
|
|
Standpipe flow test performed today did not include all required points of flow for testing approval (only the northwest stair tower at parking garage level 4 was tested).
|
INSP-Final Inspection | 3/3/2006 | 3/10/2006 | 3/8/2006 | A | CANC |
Forrest France
|
|
|
Contact Charles - TOC inspection; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley Inspection cancelled from web by: Alicia Pauley
|
INSP-Sprinkler Rough-in/Hydro | 3/6/2006 | 3/7/2006 | 3/8/2006 | P | FAIL |
Forrest France
|
|
|
Items lacking for pump test approval include verification of flow test performance curve data, jockey pump controller repair, all items required per NFPA 20 for acceptance testing including a pump mfg. representative who shall be present for the field test (NFPA 20 2003 14.2.1).
|
INSP-Sprinkler Rough-in/Hydro | 3/3/2006 | 3/7/2006 | 3/7/2006 | A | PART |
Forrest France
|
|
|
Witnessed trip test functionality only (no alarm) of the 2nd and 1st floor dry systems, the air pressure may need to be adjusted per recommendation in manufacturer data sheets, the automatic air compressors must meet requirements of NFPA 13 7.2.6.6.
|
INSP-Sprinkler Rough-in/Hydro | 3/6/2006 | 3/6/2006 | 3/6/2006 | P | PASS |
Troy Cobbley
|
|
|
200lb hydro on the 1st floor wet system passed. 3rd floor dry system trip test passed at 1:30 seconds(less than 500gallons). 1st floor dry system 24 hour air test started at 11:30 with approx. 45psi showing on the guage.
|
INSP-Conference | 3/2/2006 | 3/6/2006 | 3/6/2006 | A | DONE |
Forrest France
|
|
|
Contractor called in the wrong permit number, was intended for a BLD life safety confrence to discuss fire code review notes with respect to a temp. occupancy request for the parking garage.
|
INSP-Sprinkler Rough-in/Hydro | 3/1/2006 | 3/2/2006 | 3/2/2006 | A | PASS |
Troy Cobbley
|
|
|
200 LB hydro Test on 1st Flr dry System passed.
|
INSP-Sprinkler Rough-in/Hydro | 2/28/2006 | 2/28/2006 | 2/28/2006 | P | PART |
Forrest France
|
|
|
Hydrostatic test for the standpipe completed for the north and southwest stair towers, not all portions of the standpipe tested at this time.
|
Permit Ready to Issue | | | 2/27/2006 | | |
|
|
|
|
Inspection Record Card- Fire | 2/27/2006 | | 2/27/2006 | | DONE |
|
|
|
|
Telephone call | | | 2/27/2006 | | |
|
|
|
Informed Alicia (DeBest Fire Protection) ###-#### to pick up permit 2-27-06 eus
|
CHANGE STATUS TO (ISS) | | | 2/27/2006 | | |
|
|
|
|
(F) Reprint permit | | | 2/27/2006 | | DONE |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 2/24/2006 | | DONE |
|
|
|
|
Sprinkler Plan Check | 2/17/2006 | | 2/24/2006 | | PART |
Bill Alexander
|
|
|
Secondary Water Supply
1. This re-modified secondary water supply system for the new 235,965-ft/2, eleven story high rise structure is currently not a standard secondary water storage holding system. Under IFC 104.7.2, this reviewing authority shall require the following minimum requirements:
A. Obtain and submit approval incorporating (wet) stamped plan/s and reviewing comment letter from an approved, current, registered certified Fire Protection Engineer, of a design meeting the minimum requirements in regard to the associated current adopted NFPA 13, 20, 22 and 72 pamphlets, with approval of the secondary water supply "tank" that includes, (but may not be limited to) associated sizing's, locations, fire pump connection/s, fill line/s, overflow and associated (listed) manufacturer's controls, sensing and related devices and appurtenances being incorporated in the required automatic secondary water supply system in this facility.
February 10, 2006 - Provided revised tank and piping plans. Several issues found under this submittal which need addressed, verified and corrected:
i) Possible pump cavitation problem relating to the upper tank draw down level equal to the "0" head level of the lower tank allowing suction (entrance) of air being drawn into the pump suction line. Provide a design which will verify and prevent possible pump cavitation and failure.
February 24, 2006 - Designers revised plan include a "P" trap on the suction line for the 2nd (upper) tank. There is no design verification data provided to address the draft characteristics of each tank, but it would appear the combined tank draw down would draft air since the "P" trap is still above the level of the tank floor (where the level of the required draw down is designed for). This would still enable the suction (entrance) of air in the suction piping and thus create fire booster pump cavitation. Revise and resubmit corrected drawings.
|
INSP-Sprinkler Rough-in/Hydro | 2/17/2006 | 2/17/2006 | 2/17/2006 | A | PART |
Forrest France
|
|
|
24 hour air test of the 2nd floor dry system passed.
|
INSP-Sprinkler Rough-in/Hydro | 2/15/2006 | 2/16/2006 | 2/17/2006 | A | FAIL |
Forrest France
|
|
|
Today's inspection was for the 1st floor shell wet system at the north and east perimeter areas for future TI spaces and the start of the 24 hr. air test for 2nd floor dry system, one branch line is overspaced at the south end from a wall as noted on plans, heads in the pump room must be properly spaced for 130ft/2, changes in branch line routing at the electrical room to be shown on resubmittals with all other field changes on this floor, two TI spaces facing Broad St. have been completed prior to shell inspection at these locations, discussed hydro testing requirements for the first floor partial areas, began the 24 hr. air test of the 2nd floor dry system at 10:30 @ 43psi.
|
Plan resubmittals received | | | 2/17/2006 | | |
|
|
|
Tank piping modifications
|
Miscellaneous action | | | 2/10/2006 | | DONE |
|
|
|
Took plans back to Building Department for returning and corrections.
|
INSP-Sprinkler Rough-in/Hydro | 1/25/2006 | 1/26/2006 | 1/26/2006 | P | CANC |
Forrest France
|
|
|
Inspection for the fire pump flow test canceled due to lack of approved plans for the pump and the associated secondary supply tank approvals.
|
INSP-Sprinkler Rough-in/Hydro | 1/25/2006 | 1/25/2006 | 1/25/2006 | P | NR |
Forrest France
|
|
|
Contractor intended inspection to be performed on 1/26 in the pm per telephone conversation.
|
INSP-Sprinkler Rough-in/Hydro | 1/10/2006 | 1/10/2006 | 1/10/2006 | A | DEFR |
Forrest France
|
|
|
Duplicate inspection request for hydro completed on 1/9.
|
INSP-Sprinkler Rough-in/Hydro | 1/6/2006 | 1/9/2006 | 1/10/2006 | A | PART |
Forrest France
|
|
|
Overhead hydrostatic test for the dry systems on levels 2, 3 and 4 passed inspection.
|
Plan resubmittals received | | | 1/5/2006 | | FAIL |
Bill Alexander
|
|
|
Secondary Water Supply
1. This re-modified secondary water supply system for the new 235,965-ft/2, eleven story high rise structure is currently not a standard secondary water storage holding system. Under IFC 104.7.2, this reviewing authority shall require the following minimum requirements:
A. Obtain and submit approval incorporating (wet) stamped plan/s and reviewing comment letter from an approved, current, registered certified Fire Protection Engineer, of a design meeting the minimum requirements in regard to the associated current adopted NFPA 13, 20, 22 and 72 pamphlets, with approval of the secondary water supply "tank" that includes, (but may not be limited to) associated sizing's, locations, fire pump connection/s, fill line/s, overflow and associated (listed) manufacturer's controls, sensing and related devices and appurtenances being incorporated in the required automatic secondary water supply system in this facility.
February 10, 2006 - Provided revised tank and piping plans. Several issues found under this submittal which need addressed, verified and corrected:
i) Possible pump cavitation problem relating to the upper tank draw down level equal to the "0" head level of the lower tank allowing suction (entrance) of air being drawn into the pump suction line. Provide a design which will verify and prevent possible pump cavitation and failure.
ii) The tank fill lines have butterfly separation valves located on the discharge sides of the "Cla-Val" valves? It would be wise to relocate these "butterfly" valves to the supply sides of these valves for separate isolation of the same. This will accommodate individual deactivation instead of both if either required repair.
B. Any structural related issues possibly affected by the F.P.E.'s reviewing design (which have not been incorporated in these resubmitted structural tank plans/documents), shall be fully coordinated and under the full responsibility of DEVCON and it's Architect for the same.
February 10, 2006 - Not addressed under this permit submittal. The wall extensions, tank load of one over the other, pipe penetrations, modification of tank floor, etc., will require written approval verification by an approved structural engineer by prior to IFC final tank approval.
|
INSP-Sprinkler Rough-in/Hydro | 12/29/2005 | 12/30/2005 | 12/30/2005 | A | PART |
Forrest France
|
|
|
3rd and 4th level parking garage dry system 24 hr air test passed, discussed UG flush and testing schedule for next week.
|
INSP-Sprinkler Rough-in/Hydro | 12/28/2005 | 12/29/2005 | 12/29/2005 | P | FAIL |
Forrest France
|
|
|
Air test failed, some items on rough-in c/n for the dry garage systems not complete including two EQ braces, high temp head, branch lines not installed, hanger, listing for valves at one drum drip.
|
INSP-Sprinkler Rough-in/Hydro | 12/27/2005 | 12/28/2005 | 12/28/2005 | P | PART |
Forrest France
|
|
|
Inspected dry system overhead at 1st floor, begin 24hr air test of 2nd and 3rd floors dry systems at 47psi each, missing two lines under HVAC 1st floor dry system.
|
INSP-Sprinkler Rough-in/Hydro | 12/16/2005 | 12/19/2005 | 12/19/2005 | A | FAIL |
Forrest France
|
|
|
See approved plans for areas defficient including spacing, non-listed valves, coated heads, seismic bracing, signs, missing inspectors test, hanger issues, and areas not inspected at this time-todays inspection was for rough-in at 2nd, 3rd, 4th, floors parking garage dry systems and 1st floor 6" main in soffit. 6" main in the 1st floor soffit is okay to cover except at one lateral brace next to mech. room.
|
Sprinkler Plan Check | 12/1/2005 | | 12/1/2005 | | PASS |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 12/1/2005 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 12/1/2005 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 12/1/2005 | | 12/1/2005 | | DONE |
|
|
|
|
Telephone call | | | 12/1/2005 | | DONE |
|
|
|
Spoke with Alisha and told her that permit is ready & fees///12/01/05 1:30pm BAS
|
Issue and Print Permit | | | 12/1/2005 | | DONE |
|
|
|
|
Plan resubmittals received | | | 11/16/2005 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 10/28/2005 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 10/28/2005 | | 10/28/2005 | | DONE |
|
|
|
|
Telephone call | | | 10/28/2005 | | DONE |
|
|
|
left mess that permit is ready
|
Issue permit | | | 10/28/2005 | | DONE |
|
|
|
|
Plan assigned to (Bill) | 7/15/2005 | | 10/27/2005 | | DONE |
|
|
|
|
Sprinkler Plan Check | 10/18/2005 | | 10/27/2005 | | PART |
Bill Alexander
|
|
|
Reference attached "Failed" review comments attached for clarification of requirements.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 10/27/2005 | | DONE |
|
|
|
|
Plan resubmittals received | | | 10/18/2005 | | DONE |
|
|
|
|
Case Summary | | | 10/18/2005 | | DONE |
|
|
|
|
Meeting | | | 8/2/2005 | | DONE |
|
|
|
9:30AM-Bill Alexander & Forrest France met with Wil Northup (Project Manager) regarding the secondary water supply tank not being permitted, approved and undersized. Tank is above ground concrete vault, constructed by Devcon Construction. Requested permit with submittals meeting minimum requirements of NFPA 22, structural and seismic requirements to be submitted through a license fire sprinkler contractor.
|
Sprinkler Plan Check | 7/15/2005 | | 7/29/2005 | | FAIL |
Bill Alexander
|
|
|
The data has been moved to a Word document attached to this case.
|
Telephone call | | | 7/29/2005 | | DONE |
|
|
|
left mess that plans failed & need to pickup
|
Miscellaneous action | | | 7/26/2005 | | DONE |
|
|
|
9:00am. De Best requested to swap this permit review with BMHC T.I. FIR05-00431.
|
Application received | | | 7/15/2005 | | |
|
|
|
|