Permit Information
Permit NumberFIR05-00426
StatusFinaled
Name SIMPLEX/GRINNELL
Site Address 391 S 8TH ST
Project NameBODO BLDG #4 - ALM
Customer NumberBODO 4
ePlanReview 
Description
To provide total notification, HVAC shutdown and cooking hood monitoring in the TI space located on the ground level (first floor). This permit shall not be finaled until the shell and core Building Permit (BLD04-01323) and the Fire Alarm Permit (FIR05-00075) has been satisfactorily inspected and "finaled" by the PDS Fire inspector. The existing required manual fire alarm system includes sprinkler monitoring, HVAC shutdown, fire/smoke damper control, elevator recall/shutdown, cooking hood monitoring and notification throughout.

The associated building permit (BLD 05-00626) is to construct a 7,500 square foot restaurant tenant space (3,315 square feet for interior dining, 1,015 square feet for covered exterior dining, 2,720 square feet for the kitchen, 450 square feet for the restrooms) within a new 2 story building. Work is to include 2 restrooms accessible to the disabled, interior nonbearing walls, suspended ceilings, 4 grease hoods, millwork, and interior finishes. All work shall comply with the approved drawings, the plan review report, and all applicable codes. The fire sprinkler system shall comply with 2002 NFPA 13 as regulated by the Fire Department. **CJW** (P. F. CHANG'S CHINA BISTRO - BODO BLDG 4) This building is fire sprinklered for building area increase and for fire area.

Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection4/6/20064/7/20064/7/2006APASS
DetailsForrest France
Corrections have been verified, alarm permit finaled.
INSP-Final Inspection3/10/20063/13/20063/13/2006AFAIL
DetailsForrest France
Two 180 cd strobes as shown on approved plans are not installed at the patio dining area, will need to install and test for functionality at next inspection. The remainder of items on c/n have been completed including resubmitted plans, EOL changes, added and relocated devices shown on approved plans, final pending test of 180 cd strobe notification devices.
INSP-Final Inspection2/27/20062/28/20062/28/2006AFAIL
DetailsForrest France
Need to provide the resubmitted approved plans showing relocated EOL, added devices, and relocated devices.
Telephone call  11/28/2005 DONE
Spoke with Ronnie and told him that permit is ready & fees///11/28/05 @8:30am BAS
CHANGE STATUS TO (ISS)  11/28/2005 DONE
(F) Reprint permit  11/28/2005 DONE
Inspection Record Card- Fire11/25/2005 11/25/2005 DONE
Permit Ready to Issue  11/25/2005 DONE
Permit Ready to Issue  11/25/2005  
Alarm Plan Check  11/23/2005 PASS
Plan Modification. Approved pending field inspection of fire alarm permit comments.
PLANS/APPL TAKEN TO FRONT DESK  11/23/2005 DONE
Plan resubmittals received  11/4/2005  
INSP-Sprinkler Rough-in10/27/200510/27/200510/27/2005 CANC
DetailsForrest France
Wrong inspection type called in.
Override - Parcel Holds1/1/19001/1/190010/27/2005  
need insp for fire
Override - Parcel Holds  10/27/2005  
INSP-Alarm Testing10/24/200510/25/200510/25/2005AFAIL
DetailsForrest France
Provide resubmittals for added devices, relocated strobe in kitchen, 180 cd strobes outside and EOL changes, verify locations and correct size sample tubes in all duct detectors, provide approved locations for duct detectors and results of the proposed magnahelic test, re-test duct detectors, obtain signal verification, exterior horns are not synched with the inetrior horns.
INSP-Alarm Testing10/24/200510/24/200510/24/2005AFAIL
DetailsForrest France
Provide resubmittals for changes( added strobe, 180cd strobes at outside seating area, moved 75cd strobe in the kitchen) some duct smoke detectors are mounted incorrectly.
INSP-Alarm Testing10/21/200510/21/200510/21/2005PFAIL
DetailsForrest France
Provide correct sample tubes for the duct width intended, verify correct location for duct detectors, strobe in seating area is overspaced and installed on the wrong column, one 75cd strobe in the kitchen area is blocked, the strobes for outside seating area do not match approved plan, no other items tested at this time.
INSP-Alarm Testing10/20/200510/20/200510/20/2005ACANC
DetailsForrest France
The shell permit must be finaled prior to final acceptance of the TI permit, no time for this inspection today.
Plan assigned to (Mary)7/15/2005 8/10/2005 DONE
Alarm Plan Check  8/10/2005 PASS
Approved pending field inspection of fire alarm permit comments.
PLANS/APPL TAKEN TO FRONT DESK  8/10/2005 DONE
Inspection Record Card- Fire8/10/2005 8/10/2005 DONE
Permit Ready to Issue  8/10/2005 DONE
Issue and Print Permit  8/10/2005 DONE
Plan resubmittals received  8/1/2005 DONE
Alarm Plan Check  7/22/2005 FAIL
Resubmittal Required. Faxed comments to Ronnie Zahm.
Application received  7/15/2005  
Inspection Record Card- Fire11/25/2005