INSP-Final Inspection | 4/6/2006 | 4/7/2006 | 4/7/2006 | A | PASS |
Forrest France
|
|
|
Corrections have been verified, alarm permit finaled.
|
INSP-Final Inspection | 3/10/2006 | 3/13/2006 | 3/13/2006 | A | FAIL |
Forrest France
|
|
|
Two 180 cd strobes as shown on approved plans are not installed at the patio dining area, will need to install and test for functionality at next inspection. The remainder of items on c/n have been completed including resubmitted plans, EOL changes, added and relocated devices shown on approved plans, final pending test of 180 cd strobe notification devices.
|
INSP-Final Inspection | 2/27/2006 | 2/28/2006 | 2/28/2006 | A | FAIL |
Forrest France
|
|
|
Need to provide the resubmitted approved plans showing relocated EOL, added devices, and relocated devices.
|
Telephone call | | | 11/28/2005 | | DONE |
|
|
|
Spoke with Ronnie and told him that permit is ready & fees///11/28/05 @8:30am BAS
|
CHANGE STATUS TO (ISS) | | | 11/28/2005 | | DONE |
|
|
|
|
(F) Reprint permit | | | 11/28/2005 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 11/25/2005 | | 11/25/2005 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 11/25/2005 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 11/25/2005 | | |
|
|
|
|
Alarm Plan Check | | | 11/23/2005 | | PASS |
|
|
|
Plan Modification. Approved pending field inspection of fire alarm permit comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 11/23/2005 | | DONE |
|
|
|
|
Plan resubmittals received | | | 11/4/2005 | | |
|
|
|
|
INSP-Sprinkler Rough-in | 10/27/2005 | 10/27/2005 | 10/27/2005 | | CANC |
Forrest France
|
|
|
Wrong inspection type called in.
|
Override - Parcel Holds | 1/1/1900 | 1/1/1900 | 10/27/2005 | | |
|
|
|
need insp for fire
|
Override - Parcel Holds | | | 10/27/2005 | | |
|
|
|
|
INSP-Alarm Testing | 10/24/2005 | 10/25/2005 | 10/25/2005 | A | FAIL |
Forrest France
|
|
|
Provide resubmittals for added devices, relocated strobe in kitchen, 180 cd strobes outside and EOL changes, verify locations and correct size sample tubes in all duct detectors, provide approved locations for duct detectors and results of the proposed magnahelic test, re-test duct detectors, obtain signal verification, exterior horns are not synched with the inetrior horns.
|
INSP-Alarm Testing | 10/24/2005 | 10/24/2005 | 10/24/2005 | A | FAIL |
Forrest France
|
|
|
Provide resubmittals for changes( added strobe, 180cd strobes at outside seating area, moved 75cd strobe in the kitchen) some duct smoke detectors are mounted incorrectly.
|
INSP-Alarm Testing | 10/21/2005 | 10/21/2005 | 10/21/2005 | P | FAIL |
Forrest France
|
|
|
Provide correct sample tubes for the duct width intended, verify correct location for duct detectors, strobe in seating area is overspaced and installed on the wrong column, one 75cd strobe in the kitchen area is blocked, the strobes for outside seating area do not match approved plan, no other items tested at this time.
|
INSP-Alarm Testing | 10/20/2005 | 10/20/2005 | 10/20/2005 | A | CANC |
Forrest France
|
|
|
The shell permit must be finaled prior to final acceptance of the TI permit, no time for this inspection today.
|
Plan assigned to (Mary) | 7/15/2005 | | 8/10/2005 | | DONE |
|
|
|
|
Alarm Plan Check | | | 8/10/2005 | | PASS |
|
|
|
Approved pending field inspection of fire alarm permit comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 8/10/2005 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 8/10/2005 | | 8/10/2005 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 8/10/2005 | | DONE |
|
|
|
|
Issue and Print Permit | | | 8/10/2005 | | DONE |
|
|
|
|
Plan resubmittals received | | | 8/1/2005 | | DONE |
|
|
|
|
Alarm Plan Check | | | 7/22/2005 | | FAIL |
|
|
|
Resubmittal Required. Faxed comments to Ronnie Zahm.
|
Application received | | | 7/15/2005 | | |
|
|
|
|
Inspection Record Card- Fire | 11/25/2005 | | | | |
|
|
|
|