INSP-Final Inspection | 2/6/2006 | 2/6/2006 | 2/6/2006 | P | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Final Inspection | 10/6/2005 | 10/7/2005 | 10/7/2005 | A | PART |
Forrest France
|
|
|
Access door with signage and signage for the aux. drain valve in the sw stairwell have been installed as required.
|
INSP-Final Inspection | 9/21/2005 | 9/21/2005 | 9/21/2005 | P | FAIL |
Troy Cobbley
|
|
|
mike; Phone #: ###-#### Still need access door with signage and signage on the aux. drain valve on the north stairwell as per plans.
|
INSP-Sprinkler Rough-in | 8/5/2005 | 8/5/2005 | 8/5/2005 | P | PASS |
Troy Cobbley
|
|
|
Sprinkler rough-in is ok except for aux. drains have not been installed yet and will need looked at. Also hanger rods will need to be shortened or eq bracing added on the 3" main that has been raised and the 2"x1 1/2" hex bushing used in the south below mezzanine piping cannot be used per nfpa 13. Sprinkler piping can be covered. Access door at the north stairs will be needed as stated on approved drawings.
|
Sprinkler Plan Check | 8/2/2005 | | 8/4/2005 | | PASS |
|
|
|
Plan modifications:
1. Removed upright heads under seating cavities due to construction changes.
2. Changed head legends.
3. Data submittals for changed sprinklers from recessed to flush sprinklers.
|
Telephone call | | | 8/4/2005 | | DONE |
|
|
|
per bill a. 2nd review no fee
|
Override - Parcel Holds | | | 8/4/2005 | | |
|
|
|
|
Inspection Record Card- Fire | 8/4/2005 | | 8/4/2005 | | DONE |
|
|
|
|
Override - Parcel Holds | | | 8/2/2005 | | |
|
|
|
|
Issue and Print Permit | | | 8/2/2005 | | DONE |
|
|
|
|
Plan resubmittals received | | | 8/2/2005 | | DONE |
Bill Alexander
|
|
|
|
Override - Parcel Holds | | | 7/28/2005 | | |
|
|
|
|
Inspection Record Card- Fire | 7/28/2005 | | 7/28/2005 | | DONE |
|
|
|
|
Override - Parcel Holds | | | 7/28/2005 | | |
|
|
|
|
Permit Ready to Issue | | | 7/28/2005 | | DONE |
|
|
|
|
Telephone call | | | 7/28/2005 | | DONE |
|
|
|
tlk to jeff packham ###-#### that permit and fees are ready to be picked up
|
Plan assigned to (Bill) | 7/19/2005 | | 7/27/2005 | | DONE |
|
|
|
|
Sprinkler Plan Check | 7/19/2005 | | 7/27/2005 | | PASS |
Bill Alexander
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 7/27/2005 | | DONE |
|
|
|
|
Application received | | | 7/19/2005 | | |
|
|
|
|