Permit Information
Permit NumberFIR05-00458
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 850 W GOWEN RD
Project NameSPR UG NORCO
Customer Number 
ePlanReview 
Description
NORCO ACETYLENE COMPRESSING PLANT - To install approximately 205' of 8" C-900 PVC underground fire service. Contractor will start at the property line in the north side of Gowen Rd., traveling north approximately 150', then west, just under the outside wall building footing and up through the finished floor approximately 6" with a 8" Ductile Iron and a 8 X 13½" M.J. adapter and blank flange. The supply is for a new 8,260-ft/2, one story, steel framed industrial building to be used as an acetylene gas compressing plant, of which will be fire sprinklered with the exception of a 1,360-ft/2 Equipment Room #104. The underground fire sprinkler work shall comply with NFPA 13-2002, NFPA 24-2002 the IFC-2000, attached review comment and conditions list, as regulated by the Fire Chief. These notes, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum fire code. This permit is attached to building permit: BLD05-00978.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection2/1/20062/1/20062/1/2006PPASS
DetailsForrest France
UG fire supply permit finaled.
INSP-Supply line flush1/31/20062/1/20062/1/2006APART
DetailsForrest France
UG fire supply line flush is satisfactory.
INSP-Supply line flush1/31/20061/31/20061/31/2006PCANC
DetailsForrest France
To be rescheduled per agreement with contractor per conversation.
INSP-Sprinkler Rough-in/Hydro1/31/20061/31/20061/31/2006PPART
DetailsForrest France
UG supply line hydrostatic test passed.
INSP-Sprinkler Rough-in9/9/20059/12/20059/12/2005PPART
DetailsForrest France
The remainder of the UG fire supply line installation is acceptable, okay to cover.
Override - Parcel Holds1/1/19001/1/19009/9/2005  
fire inspection
INSP-Sprinkler Rough-in8/24/20058/25/20058/25/2005PPART
DetailsForrest France
Underground fire supply line riser and stub out are good for cover, the top of pipe to grade at top of stem wall is 4'-5", will verify at next inspection min. depth of bury has been met.
Override - Parcel Holds1/1/19001/1/19008/24/2005  
Issue and Print Permit  8/3/2005 DONE
Plan assigned to (Bill)7/29/2005 8/2/2005 DONE
Sprinkler Plan Check7/29/2005 8/2/2005 PASS
DetailsBill Alexander
Faxed Permit Application
PLANS/APPL TAKEN TO FRONT DESK  8/2/2005 DONE
Permit Ready to Issue  8/2/2005 DONE
Inspection Record Card- Fire8/2/2005 8/2/2005 DONE
Telephone call  8/2/2005 DONE
Spoke with Jeff Anderson and told him that permit is ready & fees///8/2/05 4:02pm BAS
Application received  7/29/2005