Permit Information
Permit NumberFIR05-00462
StatusFinaled
Name ALARM STAR
Site Address 3201 W AIRPORT WAY
Project Namealm - Airport Parking Structur
Customer Number 
ePlanReview 
Description
To replace a fire alarm control panel that is affording elevator recall (implementing relay bases on the associated smoke detectors), HVAC shutdown and fire/smoke damper control utilizing full area coverage on both sides of the fire/smoke dampers.

There is no associated building permit.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection4/18/20084/18/20084/18/2008PPASS
DetailsForrest France
Fire alarm permit finaled, see site inspection comments 10/20/05.
Case Summary  1/10/2006 DONE
INSP-Sprinkler Rough-in/Hydro10/19/200510/20/200510/20/2005PPASS
DetailsForrest France
This inspection was for a final on the alarm permit which passed.
INSP-Final Inspection10/18/200510/19/200510/19/2005PFAIL
DetailsForrest France
The manual pull station has not yet been replaced, the zoning has not been corrected, a lock at the FACP breaker has not been installed, inspection does not allow for time to amend these items while waiting on site, inspection to be rescheduled for 10/20 p.m.
Issue and Print Permit  10/18/2005 DONE
PLANS/APPL TAKEN TO FRONT DESK  10/6/2005 PASS
Plan Modification. Approved pending field inspection of fire alarm permit comments.
Permit Ready to Issue  10/6/2005 DONE
Inspection Record Card- Fire10/6/2005 10/6/2005 DONE
Telephone call  10/6/2005 DONE
Spoke with Rand and told him that permit is ready & fees///10/06/05 8:45am BAS
INSP-Final Inspection9/22/20059/23/20059/23/2005PFAIL
DetailsForrest France
The pull station installed does not match submittals and is mounted too high, provide lock at breaker to FACP, two smoke alarms are installed on a different zone than approved plans show, restroom smoke alarms report as office smoke zone 1, provide resubmittals reflecting correct zoning, phone lines, battery, smoke at panel, restroom smoke tested okay, no other items tested at this time.
Plan resubmittals received  9/23/2005 DONE
Issue and Print Permit  9/12/2005 DONE
Plan assigned to (Mary)8/1/2005 8/25/2005 DONE
Alarm Plan Check  8/25/2005 PASS
Approved pending field inspection of fire alarm permit comments.
PLANS/APPL TAKEN TO FRONT DESK  8/25/2005 DONE
Inspection Record Card- Fire8/25/2005 8/25/2005 DONE
Permit Ready to Issue  8/25/2005 DONE
Telephone call  8/25/2005 DONE
TLK TO RAND ###-#### THAT PERMIT AND FEES ARE READY TO BE PICKED UP
Plan resubmittals received  8/23/2005 DONE
Alarm Plan Check  8/16/2005 FAIL
Resubmittal required. Faxed comments to Rand Gruber.
Plan resubmittals received  8/10/2005  
Alarm Plan Check  8/3/2005 FAIL
Resubmittal required.
Application received  8/1/2005  
Case Summary  8/1/2005 DONE
Alarm Plan Check10/6/2005