Information based on query as of Sunday, August 18, 2024.
Permit Information
Permit NumberFIR05-00472
StatusFinaled
Name FIRE SENTRY SYSTEMS
Site Address 3210 E AMITY RD
Project Namealm - Stock Components
Customer Number 
ePlanReview 
Description
This permit has been issued to allow inspection of an expired fire alarm permit (FIR01-00406). Comments from FIR01-00406 are attached. The system has been modified somewhat, resubmittal will be at PDS Fire Inspectors request. Provide a revised building map to the PDS Fire Inspector at time of inspection.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection10/5/200510/7/200510/7/2005APASS
DetailsForrest France
Items on correction notice have been completed, fire alarm finaled.
INSP-Final Inspection9/15/20059/15/20059/15/2005PFAIL
DetailsForrest France
Outside bells at both risers failed to function, duct smoke detectors tested okay, need record of signal verification at next inspection, still need sd cut sheet.
INSP-Final Inspection9/12/20059/13/20059/13/2005PFAIL
DetailsForrest France
Provide cut sheet for smoke detector at FACP to determine wall mounted listing, provide sign at door to FACP room, zone 18 and 19 tampers report as waterflow, provide updated map with matching addressing at panel, verify lock and label at breaker to FACP, need sprinkler contractor to facilitate testing of flow switches, pump run, phase reversal etc., still need to test four duct smoke detectors, no access provided at this inspection.
Application received  8/4/2005  
Plan assigned to (Mary)8/4/2005 8/4/2005 DONE
Case Summary  8/4/2005 DONE
Alarm Plan Check  8/4/2005 PASS
Approved pending field inspection of fire alarm permit comments. Based upon Sam Rogers comments on FIR01-00406.
PLANS/APPL TAKEN TO FRONT DESK  8/4/2005 DONE
Issue and Print Permit  8/4/2005 DONE
Inspection Record Card- Fire8/4/2005 8/4/2005 DONE