INSP-Final Inspection | 10/13/2005 | 10/13/2005 | 10/13/2005 | P | PASS |
Forrest France
|
|
|
Fire sprinkler permit finaled.
|
INSP-Final Inspection | 10/10/2005 | 10/11/2005 | 10/11/2005 | A | FAIL |
Troy Cobbley
|
|
|
Canopies are all on but one sprinkler pendant in the northwest end of the building was installed using the small room rule. The room the pendant is in is not separated from the ajoining corridor by a wall or lintel therefore the corridor is considered part of the room which makes it exceed 800 sq. ft. An additional pendant will be required.
|
INSP-Sprinkler Rough-in | 9/22/2005 | 9/23/2005 | 9/23/2005 | A | PART |
Forrest France
|
|
|
Overhead sprinkler rough-in is good for cover, will final when ceiling tile and escutcheons are installed and verification is made at closet that shelving has been installed to the ceiling and a sprinkler is indeed not required.
|
INSP-Sprinkler Rough-in | 8/22/2005 | 8/22/2005 | 8/22/2005 | P | FAIL |
Forrest France
|
|
|
Two arm overs in the lobby area have overspaced hangers, one pendent head in the lobby is overspaced from the adjacent wall.
|
Issue and Print Permit | | | 8/18/2005 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 8/16/2005 | | |
|
|
|
|
Inspection Record Card- Fire | 8/16/2005 | | 8/16/2005 | | DONE |
|
|
|
|
Telephone call | | | 8/16/2005 | | DONE |
|
|
|
left mess that permit is ready
|
Plan assigned to (Bill) | 8/4/2005 | | 8/15/2005 | | DONE |
|
|
|
|
Sprinkler Plan Check | 8/4/2005 | | 8/15/2005 | | PASS |
Bill Alexander
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 8/15/2005 | | DONE |
|
|
|
|
Application received | | | 8/4/2005 | | |
|
|
|
|