Permit Information
Permit NumberFIR05-00473
StatusFinaled
Name SIMPLEX/GRINNELL
Site Address 3101 W MAIN ST Unit: 210
Project NameSPR THORTON BYRON
Customer Number 
ePlanReview 
Description
THORNTON BYRON-RIVERFRONT PLAZA - 2ND FLR - STE 210 * To add 60 pendant fire sprinklers in the construction of a new 6,653-ft/2 office space for a new tenant, located in the south half of the second floor, in a new shell building. The fire sprinkler work is related to new interior walls, a new suspended ceiling and some soffit work. This building is fully fire sprinklered for area increase. This fire protection work shall comply with the IFC 2003 and the permit review comments; each regulated by the Fire Chief. The review comments, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to BLD05-00859.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection10/13/200510/13/200510/13/2005PPASS
DetailsForrest France
Fire sprinkler permit finaled.
INSP-Final Inspection10/10/200510/11/200510/11/2005AFAIL
DetailsTroy Cobbley
Canopies are all on but one sprinkler pendant in the northwest end of the building was installed using the small room rule. The room the pendant is in is not separated from the ajoining corridor by a wall or lintel therefore the corridor is considered part of the room which makes it exceed 800 sq. ft. An additional pendant will be required.
INSP-Sprinkler Rough-in9/22/20059/23/20059/23/2005APART
DetailsForrest France
Overhead sprinkler rough-in is good for cover, will final when ceiling tile and escutcheons are installed and verification is made at closet that shelving has been installed to the ceiling and a sprinkler is indeed not required.
INSP-Sprinkler Rough-in8/22/20058/22/20058/22/2005PFAIL
DetailsForrest France
Two arm overs in the lobby area have overspaced hangers, one pendent head in the lobby is overspaced from the adjacent wall.
Issue and Print Permit  8/18/2005 DONE
Permit Ready to Issue  8/16/2005  
Inspection Record Card- Fire8/16/2005 8/16/2005 DONE
Telephone call  8/16/2005 DONE
left mess that permit is ready
Plan assigned to (Bill)8/4/2005 8/15/2005 DONE
Sprinkler Plan Check8/4/2005 8/15/2005 PASS
DetailsBill Alexander
PLANS/APPL TAKEN TO FRONT DESK  8/15/2005 DONE
Application received  8/4/2005