Permit Information
Permit NumberFIR05-00478
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 130 N MILWAUKEE
Project NameSPR UG THEATRE RETAIL SHOP C
Customer Number 
ePlanReview 
Description
THEATRE/RETAIL SHOP "C" - To abandon an existing 3" galvanized underground supply and install approximately 60'-0" of new 4"-C-900 PVC with two thrust blocked 45° ells, located in the main building and connect to the outbuilding (between breezeway). This work will entail two new risers (in each building) located near the outside walls, through the floor with 4" ductile iron and M.J. adapters approximately 6" above floor grade. The fire sprinkler underground work shall comply with NFPA 13-2002, NFPA 24-2002 the IFC-2003, attached review comment and conditions list, as regulated by the Fire Chief. These notes, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum fire code. This permit is not attached to a building permit.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Supply line flush8/18/20058/19/20058/19/2005APASS
DetailsTroy Cobbley
Underground hydro and flush passed.. Piping ok to cover.
INSP-Final Inspection8/19/20058/19/20058/19/2005PPASS
DetailsTroy Cobbley
Fire sprinkler permit finaled. Piping ok to cover.
INSP-Supply line flush8/18/20058/18/20058/18/2005AFAIL
DetailsTroy Cobbley
Underground hydro test failed.
INSP-Sprinkler Rough-in/Hydro8/16/20058/16/20058/16/2005PCANC
DetailsTroy Cobbley
Canceled per sam
INSP-Supply line flush8/12/20058/12/20058/12/2005PPASS
DetailsTroy Cobbley
This inspection was not for a flush but for cover. Underground piping is ok for cover.
INSP-Supply line flush8/9/20058/9/20058/9/2005PPART
DetailsTroy Cobbley
Inspection was for cover of the supply piping located under the walkway. See approved drawings for exact location. No thrust blocking has been done yet.
Plan assigned to (Bill)8/5/2005 8/8/2005 DONE
Sprinkler Plan Check8/5/2005 8/8/2005 PASS
DetailsBill Alexander
PLANS/APPL TAKEN TO FRONT DESK  8/8/2005 DONE
Permit Ready to Issue  8/8/2005 DONE
Inspection Record Card- Fire8/8/2005 8/8/2005 DONE
Issue and Print Permit  8/8/2005 DONE
Application received  8/5/2005