INSP-Final Inspection | 5/19/2006 | 5/23/2006 | 5/23/2006 | A | PASS |
Forrest France
|
|
|
As-builts for address changes verified on site, permit finaled.
|
INSP-Sprinkler Rough-in/Hydro | 3/9/2006 | 3/14/2006 | 3/14/2006 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled. Addressing does not match plans. As-builts to be updated and verified.
|
Issue and Print Permit | | | 11/25/2005 | | DONE |
|
|
|
|
Alarm Plan Check | | | 11/23/2005 | | PASS |
|
|
|
Approved pending PDS Fire Inspector field verification. No comments written. INSP: FEEL FREE TO CALL IF YOU NEED INFORMATION.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 11/23/2005 | | DONE |
|
|
|
|
Alarm Plan Check | | | 11/14/2005 | | FAIL |
|
|
|
Plans did not inclue the appropriate detail for the BPS aux power supplied for the solenoid valve.
Incorrect cutsheets provided.
Cutsheets missing.
|
Alarm Plan Check | | | 10/19/2005 | | FAIL |
|
|
|
Resubmittal required. An additional request was made by myself for the UL listing for the Vesda system for "releasing". The unit is NOT listed for releasing. Bryan Pepper is working on a solution for the cabinet.
|
Miscellaneous action | | | 10/13/2005 | | DONE |
|
|
|
I brought the plans back to the city to review.
|
Telephone call | | | 8/19/2005 | | DONE |
|
|
|
Telcon with Paul Marcolina and Bobbie Rice. Reportedly the bulk supply is to feed only one new machine at this time and will not exceed the max. allowable limits per machine stipulated under the terms of the TMA/pyrophoric special request approved by PDS/FD on 7/29/03. I requested written documentation describing this system, what equipment it supplies and specifying the quantities involved and that only one machine is to be involved. System is capable of serving multiple machines but reportedly will not be used for such unless FD approval is granted to Micron's 8/4/05 request to use the higher quantity limits allegedly to be published in a 2004 Supplement to the 2003 IFC. This request is still under review by the Fire Chief.
|
Miscellaneous action | | | 8/8/2005 | | DONE |
|
|
|
Plans on HOLD pending Fire Code Review/approval of undefined/descried "bulk distribution system" by Sam Rogers.
|
Application received | | | 8/8/2005 | | |
|
|
|
|
Plan assigned to (Mary) | 8/8/2005 | | | | |
|
|
|
|