Permit NumberFIR05-00482
StatusFinaled
Name MICRON TECHNOLOGY INC FA
Site Address 8000 S FEDERAL WAY
Project Namealm -
Customer NumberC8597
ePlanReview 
Description
The scope of work is similar to a TMA tool. The FACP will "control" the suppression, therefore, simply monitoring the three points as indicated below is not the case. B24D. A CS Clean Systems bulk TMA
distribution system is being installed in Photo Bay 151A. We will
monitor alarm and trouble contacts provided by the mfgr. The system
includes its own fire suppression system.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection5/19/20065/23/20065/23/2006APASS
DetailsForrest France
As-builts for address changes verified on site, permit finaled.
INSP-Sprinkler Rough-in/Hydro3/9/20063/14/20063/14/2006APASS
DetailsTroy Cobbley
Permit finaled. Addressing does not match plans. As-builts to be updated and verified.
Issue and Print Permit  11/25/2005 DONE
Alarm Plan Check  11/23/2005 PASS
Approved pending PDS Fire Inspector field verification. No comments written. INSP: FEEL FREE TO CALL IF YOU NEED INFORMATION.
PLANS/APPL TAKEN TO FRONT DESK  11/23/2005 DONE
Alarm Plan Check  11/14/2005 FAIL
Plans did not inclue the appropriate detail for the BPS aux power supplied for the solenoid valve.

Incorrect cutsheets provided.

Cutsheets missing.
Alarm Plan Check  10/19/2005 FAIL
Resubmittal required. An additional request was made by myself for the UL listing for the Vesda system for "releasing". The unit is NOT listed for releasing. Bryan Pepper is working on a solution for the cabinet.
Miscellaneous action  10/13/2005 DONE
I brought the plans back to the city to review.
Telephone call  8/19/2005 DONE
Telcon with Paul Marcolina and Bobbie Rice. Reportedly the bulk supply is to feed only one new machine at this time and will not exceed the max. allowable limits per machine stipulated under the terms of the TMA/pyrophoric special request approved by PDS/FD on 7/29/03. I requested written documentation describing this system, what equipment it supplies and specifying the quantities involved and that only one machine is to be involved. System is capable of serving multiple machines but reportedly will not be used for such unless FD approval is granted to Micron's 8/4/05 request to use the higher quantity limits allegedly to be published in a 2004 Supplement to the 2003 IFC. This request is still under review by the Fire Chief.
Miscellaneous action  8/8/2005 DONE
Plans on HOLD pending Fire Code Review/approval of undefined/descried "bulk distribution system" by Sam Rogers.
Application received  8/8/2005  
Plan assigned to (Mary)8/8/2005