Permit Information
Permit NumberFIR05-00486
StatusFinaled
Name SIMPLEX/GRINNELL
Site Address 1221 W IDAHO ST
Project Namealm - IPCo 9th floor TI
Customer Number 
ePlanReview 
Description
To provide total area automatic detection and notification in the TI space located on the 9th floor (partial). The required manual fire alarm system includes sprinkler monitoring, HVAC shutdown, fire/smoke damper control, door release, elevator recall/shutdown, required automatic detection and notification throughout (voice/evac; high rise).

The associated building permit (BLD 05-01469) is to remodel an existing 1610 sq ft office space located on the 9th floor per approved plans. Work to include, construction of interior noncombustible partitions to create new office areas, conference room and reception area, replacement of ceiling tiles in existing suspended ceiling system, modify HVAC System, new lighting, and miscellaneous related finishes. NOTE This building is fully fire sprinklered and has an audible/visual fire alarm system. Separate permits are required for ANY fire sprinkler modifications and alarm work. (rmh) *(Idaho Power)* (9th Floor/Idaho Power Building)*
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection11/29/200612/4/200612/5/2006PPASS
DetailsForrest France
Required corrections have been completed, inspection passed, permit finaled.
INSP-Final Inspection10/13/200610/16/200610/17/2006PFAIL
DetailsForrest France
Two items on the previous correction notice dated 2/16/06 are not complete including inadequate dB in the storage room and a penthouse av which is non-functional.
CHANGE STATUS TO (ISS)  7/13/2006 DONE
already pd fees
Alarm Plan Check7/12/2006 7/12/2006 PASS
Plan modification requested by fire inspector; adding 2 smoke detectors and 2 strobes for proper coverage. Approved subject to inspection. No review comments.
PLANS/APPL TAKEN TO FRONT DESK  7/12/2006 DONE
Permit Ready to Issue  7/12/2006 DONE
Telephone call  7/12/2006 DONE
left vc for charlie@###-####/told permit was ready and no fee
Plan resubmittals received  7/6/2006  
INSP-Final Inspection2/15/20062/16/20062/17/2006PFAIL
DetailsForrest France
"Office" room 905 is now a confrence room requiring visual notification, provide smoke detection at the restroom and telephone rooms, relocate SD in the lobby to afford proper coverage, the "closet" room lacks proper visual notification, provide an additional strobe to cover the blind spot at the east common area, dB level in the storage room is not adequate, the penthouse AV is non-functional on audio, provide resubmittals reflecting all modifications and required changes.
INSP-Final Inspection2/13/20062/15/20062/15/2006PCANC
DetailsForrest France
Inspection cancelled per conversation with contractor due to schedule conflicts.
Issue and Print Permit  12/13/2005 DONE
Alarm Plan Check  12/12/2005 PASS
Approved pending field inspection of fire alarm permit comments.
PLANS/APPL TAKEN TO FRONT DESK  12/12/2005 DONE
Inspection Record Card- Fire12/12/2005 12/12/2005 DONE
Permit Ready to Issue  12/12/2005 DONE
Telephone call  12/12/2005 DONE
tlk to ronnie zahm that permit is ready to be picked up
Plan assigned to (Mary)8/9/2005 12/12/2005 DONE
Plan resubmittals received  12/6/2005  
Telephone call  8/30/2005 DONE
Spoke with George Eidam, we discussed each response to the comments. He will work a Co for the FA vendor and the plans will be resubmitted. He will send a copy of his Co to me.
Miscellaneous action  8/25/2005 DONE
Received responses to comments from George Eidam.
Alarm Plan Check  8/22/2005 FAIL
Resubmittal Required. Faxed comments to Ronnie Zahm.
Plan resubmittals received  8/10/2005 DONE
Ronnie Zahm brought in the generator info for IPCo bldg. Apparently it wasn't included in the original submittal.
Application received  8/9/2005  
Plan resubmittals received  8/9/2005 DONE