INSP-Final Inspection | 11/29/2006 | 12/4/2006 | 12/5/2006 | P | PASS |
Forrest France
|
|
|
Required corrections have been completed, inspection passed, permit finaled.
|
INSP-Final Inspection | 10/13/2006 | 10/16/2006 | 10/17/2006 | P | FAIL |
Forrest France
|
|
|
Two items on the previous correction notice dated 2/16/06 are not complete including inadequate dB in the storage room and a penthouse av which is non-functional.
|
CHANGE STATUS TO (ISS) | | | 7/13/2006 | | DONE |
|
|
|
already pd fees
|
Alarm Plan Check | 7/12/2006 | | 7/12/2006 | | PASS |
|
|
|
Plan modification requested by fire inspector; adding 2 smoke detectors and 2 strobes for proper coverage. Approved subject to inspection. No review comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 7/12/2006 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 7/12/2006 | | DONE |
|
|
|
|
Telephone call | | | 7/12/2006 | | DONE |
|
|
|
left vc for charlie@###-####/told permit was ready and no fee
|
Plan resubmittals received | | | 7/6/2006 | | |
|
|
|
|
INSP-Final Inspection | 2/15/2006 | 2/16/2006 | 2/17/2006 | P | FAIL |
Forrest France
|
|
|
"Office" room 905 is now a confrence room requiring visual notification, provide smoke detection at the restroom and telephone rooms, relocate SD in the lobby to afford proper coverage, the "closet" room lacks proper visual notification, provide an additional strobe to cover the blind spot at the east common area, dB level in the storage room is not adequate, the penthouse AV is non-functional on audio, provide resubmittals reflecting all modifications and required changes.
|
INSP-Final Inspection | 2/13/2006 | 2/15/2006 | 2/15/2006 | P | CANC |
Forrest France
|
|
|
Inspection cancelled per conversation with contractor due to schedule conflicts.
|
Issue and Print Permit | | | 12/13/2005 | | DONE |
|
|
|
|
Alarm Plan Check | | | 12/12/2005 | | PASS |
|
|
|
Approved pending field inspection of fire alarm permit comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 12/12/2005 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 12/12/2005 | | 12/12/2005 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 12/12/2005 | | DONE |
|
|
|
|
Telephone call | | | 12/12/2005 | | DONE |
|
|
|
tlk to ronnie zahm that permit is ready to be picked up
|
Plan assigned to (Mary) | 8/9/2005 | | 12/12/2005 | | DONE |
|
|
|
|
Plan resubmittals received | | | 12/6/2005 | | |
|
|
|
|
Telephone call | | | 8/30/2005 | | DONE |
|
|
|
Spoke with George Eidam, we discussed each response to the comments. He will work a Co for the FA vendor and the plans will be resubmitted. He will send a copy of his Co to me.
|
Miscellaneous action | | | 8/25/2005 | | DONE |
|
|
|
Received responses to comments from George Eidam.
|
Alarm Plan Check | | | 8/22/2005 | | FAIL |
|
|
|
Resubmittal Required. Faxed comments to Ronnie Zahm.
|
Plan resubmittals received | | | 8/10/2005 | | DONE |
|
|
|
Ronnie Zahm brought in the generator info for IPCo bldg. Apparently it wasn't included in the original submittal.
|
Application received | | | 8/9/2005 | | |
|
|
|
|
Plan resubmittals received | | | 8/9/2005 | | DONE |
|
|
|
|