Permit Information
Permit NumberFIR05-00496
StatusFinaled
Name AUDIO ELECTRONICS INC
Site Address 12785 W ASHCREEK ST
Project Namealm -ROLLING HILLS CHARTER SCH
Customer Number 
ePlanReview 
Description
Scope
To provide a required manual fire alarm system in Buildings A, B and to extend it into C (non-required). The required manual fire alarm system includes sprinkler monitoring, (Building A only), manual pull stations and notification throughout.

FIR05-00494 is associated with building permit (BLD 05-02037) is to install a 440 sq. ft. one story modular office building with a new pier foundation with holdowns and new ramps and stairs. Other work includes all site improvements and landscaping per approved plans and attachments, DRH05-00247, CUP05-00061. SEE ESC05-01261 & PWK05-03770 Idaho State Tag # 8341CC- Unit C -

FIR05-00495 is associated with building permit (BLD 05-02035) is to install a 1,792 sq. ft. one story modular classroom building with a new pier foundation and holdowns and new ramps and stairs. Other work includes all site improvements and landscaping per approved plans and attachments, DRH05-00247, CUP05-00061. See ESC05-01261, PWK05-03770 This building is equipped with a manual fire alarm system. Idaho State Tag # 9045CC Unit B -

FIR05-00496 is associated with building permit (BLD 05-02034) is to install a 8,316 sq. ft. one story modular classroom building with a new pier foundation and holdowns and new ramps and stairs. Other work includes all site improvements and landscaping per approved plans and attachments, DRH05-00247, CUP05-00061. This building is fully fire sprinklered and has a fire alarm system. Fire sprinklers for area. State of Idaho Tag # 8597CC - Serial #'s 01101A, 01101B, 01101C, 01101D, 01101E, 01101F, 01101G, 01101H, 01101I Unit A

5/22/2006 - An exterior PIV monitoring point has been added at zone 6
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection9/22/20069/22/20069/22/2006PPASS
DetailsTroy Cobbley
Permit finaled
CHANGE STATUS TO (ISS)  5/23/2006 DONE
(F) Reprint permit  5/23/2006 DONE
Alarm Plan Check  5/22/2006 PASS
Plan Modification. Approved pending field inspection of fire alarm permit comments. The PDS Fire Inspector has field verified and this permit will be finaled upon pick up and payment of fees.
PLANS/APPL TAKEN TO FRONT DESK  5/22/2006 DONE
Telephone call  5/22/2006 DONE
Spoke with Lisa and told her that they have fees of $1.05 that must be paid so this can be doc finaled per Mary F.///5/22/06 @12:42 BAS
Permit Ready to Issue  5/22/2006 DONE
INSP-Final Inspection5/18/20065/19/20065/19/2006APASS
DetailsTroy Cobbley
Permit finaled
Plan resubmittals received  5/18/2006 DONE
Case Summary  5/18/2006 DONE
INSP-Conference5/17/20065/17/20065/17/2006PDONE
DetailsTroy Cobbley
Correction notice left with Carolyn Mauer that all FIR permits to be finaled by 5-23-2006 or the school will be shutdown. I called Ken at AEI, Brad at SimplexGrinnell and left a message for Randy at DeBest about their permits needing finaled. I also contacted Dave Hanniman about what is going on.
INSP-Final Inspection9/6/20059/6/20059/7/2005PPART
DetailsForrest France
Need to provide re-submitalls showing added PIV tamper switch, provide sign at door to fire alarm control panel. A temporary occupancy was granted with Dave Hannemans permission.
Case Summary  9/6/2005 DONE
INSP-Final Inspection8/31/20059/2/20059/2/2005PFAIL
DetailsForrest France
Troy, We would like to schedule these (3) Buildings for inspection at the same time, since they are on the same Fire Alarm Panel, and in the same location. If you have any questions, or problems, please call me at the office, or on my cell at ###-####. Thanks, Jason; Phone #: ###-#### Internet Inspection Request from: Jason Minnick

Fire Sprinklers not activated. Could not verify flow or tampers. A PIV has been added, not included on the plans, nor was it connected to the FAS. 8 classrooms had insufficient visual coverage based on location in the room. (marked on plans). Resubmittal will be required prior to finaling the permit.

Tested all pull stations and smoke, remainder of notification is acceptable.
Issue and Print Permit  8/11/2005 DONE
Plan assigned to (Mary)8/9/2005 8/10/2005 DONE
Alarm Plan Check  8/10/2005 PASS
Approved pending field inspection of fire alarm permit comments.
PLANS/APPL TAKEN TO FRONT DESK  8/10/2005 DONE
Permit Ready to Issue  8/10/2005 DONE
Inspection Record Card- Fire8/10/2005 8/10/2005 DONE
Telephone call  8/10/2005 DONE
Left message for Jason that permit is ready & fees///8/10/005 4:25pm BAS
Case Summary  8/9/2005 DONE
Application received  8/9/2005