INSP-Final Inspection | 9/22/2006 | 9/22/2006 | 9/22/2006 | P | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
CHANGE STATUS TO (ISS) | | | 5/23/2006 | | DONE |
|
|
|
|
(F) Reprint permit | | | 5/23/2006 | | DONE |
|
|
|
|
Alarm Plan Check | | | 5/22/2006 | | PASS |
|
|
|
Plan Modification. Approved pending field inspection of fire alarm permit comments. The PDS Fire Inspector has field verified and this permit will be finaled upon pick up and payment of fees.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 5/22/2006 | | DONE |
|
|
|
|
Telephone call | | | 5/22/2006 | | DONE |
|
|
|
Spoke with Lisa and told her that they have fees of $1.05 that must be paid so this can be doc finaled per Mary F.///5/22/06 @12:42 BAS
|
Permit Ready to Issue | | | 5/22/2006 | | DONE |
|
|
|
|
INSP-Final Inspection | 5/18/2006 | 5/19/2006 | 5/19/2006 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
Plan resubmittals received | | | 5/18/2006 | | DONE |
|
|
|
|
Case Summary | | | 5/18/2006 | | DONE |
|
|
|
|
INSP-Conference | 5/17/2006 | 5/17/2006 | 5/17/2006 | P | DONE |
Troy Cobbley
|
|
|
Correction notice left with Carolyn Mauer that all FIR permits to be finaled by 5-23-2006 or the school will be shutdown. I called Ken at AEI, Brad at SimplexGrinnell and left a message for Randy at DeBest about their permits needing finaled. I also contacted Dave Hanniman about what is going on.
|
INSP-Final Inspection | 9/6/2005 | 9/6/2005 | 9/7/2005 | P | PART |
Forrest France
|
|
|
Need to provide re-submitalls showing added PIV tamper switch, provide sign at door to fire alarm control panel. A temporary occupancy was granted with Dave Hannemans permission.
|
Case Summary | | | 9/6/2005 | | DONE |
|
|
|
|
INSP-Final Inspection | 8/31/2005 | 9/2/2005 | 9/2/2005 | P | FAIL |
Forrest France
|
|
|
Troy, We would like to schedule these (3) Buildings for inspection at the same time, since they are on the same Fire Alarm Panel, and in the same location. If you have any questions, or problems, please call me at the office, or on my cell at ###-####. Thanks, Jason; Phone #: ###-#### Internet Inspection Request from: Jason Minnick
Fire Sprinklers not activated. Could not verify flow or tampers. A PIV has been added, not included on the plans, nor was it connected to the FAS. 8 classrooms had insufficient visual coverage based on location in the room. (marked on plans). Resubmittal will be required prior to finaling the permit.
Tested all pull stations and smoke, remainder of notification is acceptable.
|
Issue and Print Permit | | | 8/11/2005 | | DONE |
|
|
|
|
Plan assigned to (Mary) | 8/9/2005 | | 8/10/2005 | | DONE |
|
|
|
|
Alarm Plan Check | | | 8/10/2005 | | PASS |
|
|
|
Approved pending field inspection of fire alarm permit comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 8/10/2005 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 8/10/2005 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 8/10/2005 | | 8/10/2005 | | DONE |
|
|
|
|
Telephone call | | | 8/10/2005 | | DONE |
|
|
|
Left message for Jason that permit is ready & fees///8/10/005 4:25pm BAS
|
Case Summary | | | 8/9/2005 | | DONE |
|
|
|
|
Application received | | | 8/9/2005 | | |
|
|
|
|