Permit Information
Permit NumberFIR05-00519
StatusFinaled
Name HONEYWELL INC
Site Address 190 E BANNOCK ST
Project Namealm - ST LUKES 5th; Epilepsy
Customer Number 
ePlanReview 
Description
To provide notification throughout the 5th floor and relocate two smoke detectors and one in-duct smoke detector. A new NAC extender panel will be added to the 5th floor. There is no fire alarm modifications required for the 4th floor. The existing fire alarm system includes sprinkler monitoring, required automatic detection, HVAC shutdown, fire/smoke damper control, door release, elevator recall/shutdown and notification throughout (high rise).

The associated building permit (BLD 05-01624) is to remodel within existing 1,500 sq. ft. EKG lab floor area of the 4th floor, Central Wing, to create new work stations with millwork, electrical & data lines to serve the remodeled area and equipment. To remodel existing area, 235 sq. ft., across from public elevators on the 5th floor to become a Tech Work Room for Epilepsy Treatment / Monitoring to include new finishes, suspended ceiling grid system, millwork, electrical, mechanical, sprinkler & alarm upgrades; to add a vented materials storage unit in an existing 107 sq. ft. Soiled Utility room, 5th floor, and install new switch controlled mechanical exhaust units above the ceiling of four existing patient rooms of 1,238 sq. ft. total area and add visual monitor system to each room. All per approved plans, notes on plans and attached plan review comments / conditions as part of the approved plans. (drs) (ST LUKES- CENTRAL TOWER-4TH FL & EAST TOWER - 5TH FL)(EPILEPSY TREATMENT)
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection11/9/200511/10/200511/10/2005APASS
DetailsTroy Cobbley
Permit finaled
INSP-Alarm Testing10/28/200510/31/200510/31/2005APASS
DetailsForrest France
Fire alarm inspected by Mary Froemke passed inspection, permit finaled.
INSP-Conference10/31/200510/31/200510/31/2005PDONE
DetailsTroy Cobbley
I spoke to Mary and notified her about the switch to shut off the strobes located inside a facp in the 3rd floor broom closet. The 5th floor has been removed from it but it still controls the 3rd, 4th and 6th floors.
INSP-Final Inspection10/26/200510/27/200510/27/2005AFAIL
DetailsTroy Cobbley
See city approved plans for strobes that are overspaced. Need to retest after strobes are relocated. Main panel received trouble signals from the new NAC. I noticed that the existing strobe circuits on the 3rd, 4th and 5th floors that are controlled from the 3rd floor janitors closet have an after market "light switch" that can shut off strobes mounted in a fire alarm panel.
Plan assigned to (Mary)8/17/2005 9/2/2005 DONE
Alarm Plan Check  9/2/2005 PASS
Approved pending field inspection of fire alarm permit comments.
PLANS/APPL TAKEN TO FRONT DESK  9/2/2005 DONE
Inspection Record Card- Fire9/2/2005 9/2/2005 DONE
Permit Ready to Issue  9/2/2005 DONE
Telephone call  9/2/2005 DONE
tlk to jim shilton ###-#### that permit and fees are ready to be picked up
Issue permit  9/2/2005  
Plan resubmittals received  8/29/2005 DONE
Alarm Plan Check  8/23/2005 FAIL
Resubmittal required. Faxed comments to Jim Shilton
Application received  8/17/2005  
Case Summary  8/17/2005 DONE