Permit Information
Permit NumberFIR05-00520
StatusFinaled
Name DEBEST FIRE PROTECTION
Site Address 370 S 8TH ST
Project NameANN TAYLOR LOFT BODO 7 WEST SP
Customer Number 
ePlanReview 
Description
(ANN TAYLOR LOFT - BODO BLDG #7 - WEST SIDE) To install fire sprinklers in the creation of a new 5,292-ft/2 retail sales tenant space within a new 135,950-ft/2 building, located on the 1st story, on the West side of the building. Fire sprinkler work is related to new interior nonbearing walls, 2 restrooms and suspended ceilings. This building is required to be fully fire sprinklered. This fire protection work shall comply with the IFC 2003 and the permit review comments; each regulated by the Fire Chief. The review comments, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. The shell permit is: FIR05-00372. This permit is attached to building permit: BLD05-00850.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection4/21/20064/21/20064/21/2006PPASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection2/3/20062/6/20062/6/2006ADEFR
DetailsForrest France
Final pending the completion and final of the shell fire sprinkler permit FIR05-00372.
INSP-Final Inspection11/1/200511/1/200511/1/2005PPASS
DetailsForrest France
Fire sprinkler finaled.
INSP-Final Inspection10/27/200510/28/200510/28/2005APART
DetailsForrest France
Fire sprinkler is acceptable when shell system is operational and approved.
INSP-Final Inspection10/24/200510/24/200510/24/2005PCANC
DetailsForrest France
Scheduled by a contractor via Hello! on 10/24/2005 at 7:58:44 AM. Contact: ###-####. canc kirk
INSP-Final Inspection10/3/200510/3/200510/3/2005PPART
DetailsForrest France
Heads and escutcheons have been installed, ready for final when fire pump for water supply and riser are complete.
INSP-Sprinkler Rough-in/Hydro9/29/20059/30/20059/30/2005APART
DetailsForrest France
Branch line directly above electrical panel needs to be relocated, the remainder of overhead rough-in is good for cover.
Override - Parcel Holds  9/23/2005  
Permit Ready to Issue  9/23/2005 DONE
Override - Parcel Holds  9/23/2005  
Inspection Record Card- Fire9/23/2005 9/23/2005 DONE
Telephone call  9/23/2005 DONE
Spoke with Catherine and told her that permit is ready & fees///9/23/05 9:00am BAS
Override - Parcel Holds  9/23/2005  
Issue and Print Permit  9/23/2005 DONE
Sprinkler Plan Check9/6/2005 9/22/2005 PASS
PLANS/APPL TAKEN TO FRONT DESK  9/22/2005 DONE
Case Summary  9/6/2005 DONE
Plan resubmittals received  9/6/2005 DONE
Telephone call  8/30/2005 DONE
tlk to receptionist ###-#### that permit failed needs to be returned
Sprinkler Plan Check8/17/2005 8/29/2005 FAIL
DetailsBill Alexander
1. This first floor tenants fire sprinklers installing, existing head layout, etc., is not the same fire sprinklers and layout verified and approved in the original (ongoing FIR05-00372) shell permit. Provide a design that is compatible with the approved original shell or provide reverification of a design incorporating in this tenant space. (IFC 105.4.2, BMC 7-01-50 IFC 901.2)

2. Correct all compass reading on the plan that are incorrect, to help clarify the correct location of tenant work. (IFC 105.4.2, BMC 7-01-50 IFC 901.2)

3. Any hanger attaching to the pad deck in this tenant will require metal and concrete, not just metal decking. Revise hanger to match correct listed attachments. (IFC 105.4.2, BMC 7-01-50 IFC 901.2)
Miscellaneous action  8/29/2005 DONE
Returned documents/plan to permit desk for returning.
Application received  8/17/2005  
Plan assigned to (Bill)8/17/2005