INSP-Final Inspection | 11/16/2005 | 11/17/2005 | 11/17/2005 | P | PASS |
Troy Cobbley
|
|
|
Fire sprinkler finaled
|
INSP-Final Inspection | 11/14/2005 | 11/15/2005 | 11/15/2005 | A | FAIL |
Troy Cobbley
|
|
|
Provide 200 degree pendant at main entrance that is next to the supply grill.
|
INSP-Sprinkler Rough-in | 11/9/2005 | 11/10/2005 | 11/10/2005 | A | CANC |
Troy Cobbley
|
|
|
no time for inspection
|
INSP-Final Inspection | 11/9/2005 | 11/10/2005 | 11/10/2005 | A | CANC |
Troy Cobbley
|
|
|
no time for inspection
|
Permit Ready to Issue | | | 11/9/2005 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 11/9/2005 | | 11/9/2005 | | DONE |
|
|
|
|
Issue and Print Permit | | | 11/9/2005 | | DONE |
|
|
|
|
Plan assigned to (Bill) | 10/14/2005 | | 11/9/2005 | | DONE |
Bill Alexander
|
|
|
|
Plan resubmittals received | | | 11/9/2005 | | DONE |
|
|
|
|
Sprinkler Plan Check | 11/9/2005 | | 11/9/2005 | | PASS |
Bill Alexander
|
|
|
Anti-freeze system.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 11/9/2005 | | DONE |
|
|
|
|
Telephone call | | | 11/8/2005 | | DONE |
|
|
|
Called on 11-8-05 @ 4:16 by BAS - pick up failed plans
|
Sprinkler Plan Check | 10/14/2005 | | 11/8/2005 | | FAIL |
Bill Alexander
|
|
|
1. Anti-freeze calculations do not match pipe installing, which includes node locations, etc., etc. Reference NFPA 13 Chapter 13 & 14 and resubmit addressing minimum requirements for correlation of plans and calcs. This was addressed in Item #5, which is now critical and will be required. (BMC 7-01-50:901.2, IFC 105.4)
2. Verify, clarify and install peak heads in overbuild meeting minimum installation codes addressed in NFPA 13 Chapter 8 Section 6.
|
INSP-Sprinkler Rough-in/Hydro | 11/3/2005 | 11/4/2005 | 11/4/2005 | A | PASS |
Troy Cobbley
|
|
|
Anti-freeze hydro test passed.
|
INSP-Sprinkler Rough-in/Hydro | 11/2/2005 | 11/3/2005 | 11/3/2005 | A | FAIL |
Troy Cobbley
|
|
|
Anti-freeze loop hydro test failed twice today.
|
INSP-Final Inspection | 11/1/2005 | 11/2/2005 | 11/3/2005 | P | CANC |
Troy Cobbley
|
|
|
jim paige; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa
|
INSP-Sprinkler Rough-in/Hydro | 11/1/2005 | 11/2/2005 | 11/2/2005 | A | CANC |
Troy Cobbley
|
|
|
Canceled hydro since anti-freeze system would hold 200lbs.
|
Miscellaneous action | | | 10/31/2005 | | DONE |
|
|
|
Approved a written request from SimplexGrinnell for early start to install the antifreeze system prior to approval of the resubmitted the plan modification (original plans did not include an AF system for the combustible concealed spaces). I denied their request for a TOC; that request will have to be considered separately after the sprinkler installation has been installed and satisfactorily inspected.
|
INSP-Sprinkler Rough-in/Hydro | 10/18/2005 | 10/19/2005 | 10/19/2005 | A | PASS |
Troy Cobbley
|
|
|
Overhead hydro test passed.
|
INSP-Sprinkler Rough-in | 10/17/2005 | 10/18/2005 | 10/18/2005 | A | PASS |
Troy Cobbley
|
|
|
Piping above the lay-in ceiling tiles is ok to cover except for the new anti-freeze system piping which has not been approved yet. Also the restrooms in the southwest corner are not to be covered until the new uprigth sprinklers are inspected.
|
Plan resubmittals received | | | 10/14/2005 | | DONE |
|
|
|
|
INSP-Sprinkler Rough-in/Hydro | 9/15/2005 | 9/16/2005 | 9/16/2005 | P | PART |
Troy Cobbley
|
|
|
Hard lid areas as marked on the plans are ok to cover.
|
Issue permit | | | 9/2/2005 | | |
|
|
|
|
Plan assigned to (Bill) | 8/18/2005 | | 9/1/2005 | | DONE |
|
|
|
|
Sprinkler Plan Check | 8/18/2005 | | 9/1/2005 | | PASS |
Bill Alexander
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 9/1/2005 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 9/1/2005 | | 9/1/2005 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 9/1/2005 | | |
|
|
|
|
Telephone call | | | 9/1/2005 | | DONE |
|
|
|
lft vm with tom easton ###-#### that permit and fees are ready to be picked up
|
Application received | | | 8/18/2005 | | |
|
|
|
|