Information based on query as of Thursday, July 18, 2024.
Permit Information
Permit NumberFIR05-00527
StatusFinaled
Name SIMPLEX/GRINNELL
Site Address 101 S CAPITOL BLVD Unit: 601
Project NameSPR LAUREN DEDISPA-US BANK
Customer Number 
ePlanReview 
Description
(LAUREN MEDISPA - US BANK - STE 601) To relocate and add fire sprinklers in the remodel of an existing 2,679-ft/2 tenant space for a Light Hazard Occupancy use "Day Spa." This space is located on the 6th story of a 19 story building. The floor area of the entire 6th story is about 14,600-ft/2. The "core" has a floor area of about 2,670-ft/2. Fire sprinkler work is related to interior nonbearing walls, suspended ceilings and a restroom. This building is required to be fully fire sprinklered because it is a high-rise. The fire sprinkler system, (and the infrastructure supporting these systems) for the 6th story are regulated under the provisions of the 2000 IBC. This fire protection work shall comply with the IFC 2003 and the permit review comments; each regulated by the Fire Chief. The review comments, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to BLD05-01821.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  9/12/2005 DONE
Sent email notice to Tom Easton addressing lack of information incorporating FlexHead connectors.
INSP-Final Inspection9/8/20059/8/20059/9/2005PFAIL
DetailsForrest France
One head as shown on approved plans is not installed in the reception area, review notes and submitted plans do not include the flex heads as used throughout the space.
INSP-Final Inspection9/8/20059/9/20059/9/2005APASS
DetailsForrest France
Fire sprinkler passed inspection, verification is pending for approval of the flex heads as used throughout the space and not submitted for on the plans.
Plan resubmittals received  9/8/2005 DONE
Issue permit  9/8/2005  
Permit Ready to Issue  9/7/2005 DONE
Telephone call  9/7/2005 DONE
left mess that permit is ready
Plan assigned to (Bill)8/19/2005 9/6/2005 DONE
Sprinkler Plan Check8/19/2005 9/6/2005 PASS
DetailsBill Alexander
PLANS/APPL TAKEN TO FRONT DESK  9/6/2005 DONE
Application received  8/19/2005