Information based on query as of Sunday, August 18, 2024.
Permit Information
Permit NumberFIR05-00531
StatusFinaled
Name SIMPLEX/GRINNELL
Site Address 370 S 8TH ST
Project NameANN TAYLOR LOFT BODO 7 WEST AL
Customer Number 
ePlanReview 
Description
The shell and core fire alarm permit (FIR05-00076) must be finaled prior to occupancy for this fire alarm permit. This permit is to provide HVAC shutdown, total notification (speaker/strobes) to an existing fire alarm system. The required manual fire alarm system includes HVAC shutdown, fire/smoke damper control, door release and notification throughout (voice/evac).

9/30/2005 - Plan Modification. The only tenant in the BODO #7 building required to have voice/evac is the Edwards Theater. There is a two-hour separation between the theater and all other tenants. A manual fire alarm system with total notification (horn/strobe) is still required in the remainder of the building based upon the expected occupancies.

RESUBMITTAL required for incorrect module (expansion audio card) as shown on the battery calculation, BOM and with the cut sheets. Provide the appropriate information, update the battery calculation and BOM.

2/28/2006 - Plan Modification. Plans corrected to indicate the appropriate locations of the airhandlers.

The associated building permit (BLD 05-00850) is to create a new 5,292 square foot retail sales tenant space within a new 135,950 square foot building. This space is located on the 1st story, on the West side of the building. Work is to include interior nonbearing walls, 2 restrooms accessible to the disabled, millwork, suspended ceilings, and finishes. All work shall comply with the approved drawings, the plan review report, and all applicable codes. The fire sprinkler system shall comply with 2002 NFPA 13 as regulated by the Fire Department. **CJW** (ANN TAYLOR LOFT - BODO BLDG #7 - WEST SIDE) This building is required to be fully fire sprinklered.

Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection3/10/20063/13/20063/13/2006APASS
DetailsForrest France
Shell alarm permit is complete, TI alarm finaled.
INSP-Final Inspection2/27/20062/28/20062/28/2006PPART
DetailsForrest France
c/n items are complete, final pending shell alarm permit final.
Alarm Plan Check  2/28/2006 PASS
Plan Modification, received plans with the appropriate locations of all AHU duct detectors. Approved pending field inspection of fire alarm permit comments.
PLANS/APPL TAKEN TO FRONT DESK  2/28/2006 DONE
CHANGE STATUS TO (ISS)  2/28/2006 DONE
per mary change status to issued
Plan resubmittals received  2/15/2006  
INSP-Final Inspection2/3/20062/6/20062/6/2006ADEFR
DetailsForrest France
Require approved resubmitted plans for the AHU addresses and changed av location for verification prior to final.
Alarm Plan Check  11/17/2005 FAIL
Resubmittal required for the AHU duct detector locations. Will accept the revised plan only.

Phoned Charlie Bayne (Simplex-applicant) to inform him. No written comments at this time.
Plan resubmittals received  11/4/2005  
INSP-Final Inspection11/1/200511/1/200511/1/2005PNR
DetailsForrest France
Pending shell life safety, sprinkler and alarm permit approvals prior to TI finals.
INSP-Final Inspection11/1/200511/1/200511/1/2005PPART
DetailsForrest France
Temp occupancy approval per D.Hanneman pending resubmittals reflecting changes.
INSP-Alarm Testing10/31/200510/31/200510/31/2005PPART
DetailsForrest France
Devices tested satisfactory, final pending resubmittals for relocated av and address changes on duct detectors.
INSP-Sprinkler Rough-in10/27/200510/28/200510/28/2005AFAIL
DetailsForrest France
AHU #1 and #2 do not match approved plan with respect to location and addressing, AV at back wall adjacent to registers is obstructed by clothing racks, AHU #3 detector needs to be relocated as discussed, provide resubmittals reflecting the required changes.
INSP-Alarm Testing10/24/200510/24/200510/24/2005PCANC
DetailsForrest France
Scheduled by a contractor via Hello! on 10/24/2005 at 8:01:03 AM. Contact: ###-####. cancel
(F) Reprint permit  10/11/2005 DONE
CHANGE STATUS TO (ISS)  10/11/2005 DONE
already issued previously
Alarm Plan Check  10/10/2005 PASS
Plan Modification. Approved pending field inspection of fire alarm permit comments.
PLANS/APPL TAKEN TO FRONT DESK  10/10/2005 DONE
Permit Ready to Issue  10/10/2005 DONE
Inspection Record Card- Fire10/10/2005 10/10/2005 DONE
Telephone call  10/10/2005 DONE
Left voice message for Charlie that permit is ready & fees///10/10/05 4:00pm BAS
Plan resubmittals received  10/3/2005  
Case Summary  10/3/2005 DONE
Alarm Plan Check  9/30/2005 FAIL
Resubmittal required. Faxed comments to Charlie Bayne.
Plan resubmittals received  9/23/2005 DONE
added build materials per Mary///9/23/05 BAS
Plan resubmittals received  9/22/2005 DONE
Telephone call  9/12/2005 DONE
Phoned Ralph Costelli (architect) to inform him that the FAS for Ann Taylor Loft was designed as a voice/evac system. It now appears that there were circumstances involved with the theatre that required a separation, which in turn created two separate fire areas. Hence only the theatre required voice/evac. The remainder of the first floor of the building is considered an M over 500 and a required manual FAS is required (horn/strobes only).
Inspection Record Card- Fire8/31/2005 8/31/2005 DONE
Permit Ready to Issue  8/31/2005 DONE
Telephone call  8/31/2005 DONE
tlk to peter ###-#### that permit and fees are ready to be picked up
Issue and Print Permit  8/31/2005 DONE
Plan assigned to (Mary)8/19/2005 8/30/2005 DONE
Alarm Plan Check  8/30/2005 PASS
Approved pending field inspection of fire alarm permit comments.
PLANS/APPL TAKEN TO FRONT DESK  8/30/2005 DONE
Case Summary  8/25/2005 DONE
Alarm Plan Check  8/24/2005 FAIL
Resubmittal required. Faxed comments to Ronnie Zahm.
Application received  8/19/2005  
Case Summary  8/19/2005 DONE