Permit Information
Permit NumberFIR05-00542
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 850 W GOWEN RD
Project NameSPR OH NORCO ACETYLENE PLANT
Customer Number 
ePlanReview 
Description
NORCO ACETYLENE COMPRESSING PLANT * To install fire sprinkler protection within a portion of a new 8,260-ft/2, one story, steel framed industrial building used as an acetylene gas compressing plant and a 1,950-ft/2, steel framed, roof covered dock. The acetylene plant will consist of a 1,360-ft/2 equipment room, a 285-ft/2 mechanical room, a 455-ft/2 office space with single restroom and small break room, a 4,400-ft/2 acetylene gas charging room and two 880-ft/2 covered loading docks at the east and west sides of the charging room. This building will be fully fire sprinklered with the exception of Equipment Room #104 (calcium carbide storage). The remote 1,950-ft/2 covered dock is determined to be an outside storage area for hazardous materials. The fire sprinkler system work shall comply with the IFC 2003, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. The underground fire service supply was permitted previously under FIR05-00458. This permit is attached to building permit: BLD05-00978.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection3/29/20063/29/20063/29/2006PPASS
DetailsForrest France
Outstanding items have been completed, fire sprinkler finaled.
INSP-Final Inspection3/24/20063/27/20063/27/2006ANR
DetailsForrest France
The underground supply line is not activated at this time.
INSP-Final Inspection3/23/20063/24/20063/24/2006PFAIL
DetailsForrest France
Need to complete c/n items, perform forward flow, certify backflow preventer, provide mfg. data sheet for the expansion tank listing for fire protection service, test related alarms.
INSP-Sprinkler Rough-in/Hydro3/23/20063/24/20063/24/2006APART
DetailsForrest France
Overhead hydrostatic test for the wet and antifreeze systems is satisfactory, one row of heads in the charging room is too low, need to certifiy the backflow, perform forward flow test.
INSP-Sprinkler Rough-in1/31/20062/1/20062/1/2006AFAIL
DetailsForrest France
One head in the mechanical room is blocked by close proximity to a unistrut support, the hose stations are not installed at this time, heads on the branch lines at exterior covered canopies need minor adjustment with respect to the deflector orientation and pitch of roof, the FDC is poorly located (partially obstructed by adjacent stairs, handrails, and door when in the open position) see review notes for comments and NFPA 13 8.16.2.4.6, IFC 508.5.4, IFC 903.3.7 for requirements.
INSP-Supply line flush1/16/20061/17/20061/17/2006ACANC
DetailsTroy Cobbley
No time for inspection. Per Brian it will be called in for tomorrow.
Issue and Print Permit  12/9/2005 DONE
Plan assigned to (Bill)8/24/2005 12/8/2005 DONE
Sprinkler Plan Check11/10/2005 12/8/2005 PASS
DetailsBill Alexander
PLANS/APPL TAKEN TO FRONT DESK  12/8/2005 DONE
Permit Ready to Issue  12/8/2005 DONE
Inspection Record Card- Fire12/8/2005 12/8/2005 DONE
Telephone call  12/8/2005 DONE
left mess that permit is ready
Plan resubmittals received  11/10/2005 DONE
Case Summary  11/10/2005 DONE
Sprinkler Plan Check8/24/2005 9/13/2005 FAIL
DetailsBill Alexander
The data has been moved to a Word document attached to this case.
Miscellaneous action  9/13/2005 DONE
Returned submittals to permit desk for returning and corrections.
Telephone call  9/13/2005 DONE
tlk to jeff anderson ###-#### that permit and fees are ready to be picked up
Application received  8/24/2005