DOC - Permit Finaled | | | 9/7/2005 | | DONE |
|
|
|
|
INSP-Final Inspection | 9/6/2005 | 9/6/2005 | 9/6/2005 | P | PASS |
Forrest France
|
|
|
tom --call 1st before insp ; Phone #: ###-#### This inspection to be completed by Mary Froemke.
Tested cmoke detector and took EOL Voltage reading.
|
INSP-Final Inspection | 8/31/2005 | 8/31/2005 | 9/1/2005 | P | DEFR |
Forrest France
|
|
|
This inspection to be performed by Mary Froemke due to scheduling conflicts.
|
INSP-Alarm Testing | 9/1/2005 | 9/1/2005 | 9/1/2005 | | PART |
|
|
|
Smoke detector in north east rest room was shown on plans to be new and an old one was installed. Rob could not find a compatibility listing for the FACP and the smoke, so he will change it out to a System Sensor 2WB. Will need to retest the smoke.
|
Case Summary | | | 8/31/2005 | | DONE |
|
|
|
|
Plan assigned to (Mary) | 8/29/2005 | | 8/30/2005 | | DONE |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 8/30/2005 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 8/30/2005 | | 8/30/2005 | | DONE |
|
|
|
|
Issue and Print Permit | | | 8/30/2005 | | DONE |
|
|
|
|
Application received | | | 8/29/2005 | | |
|
|
|
|
Alarm Plan Check | | | 8/10/2005 | | PASS |
|
|
|
Approved pending field inspection of fire alarm permit comments. FA permit appliaction was not shown to have two building permits, until one portable was ready before the second one was delivered and the school wanted occupancy.
|