Permit Information
Permit NumberFIR05-00552
StatusFinaled
Name PROTEX
Site Address 2401 W TARGEE ST
Project NamealmSCHOOL-HAWTHORNE ELEMENTARY
Customer Number 
ePlanReview 
Description
To provide total notification, manual pull stations and full area detection to an existing fire alarm system for one new and one existing portable.

8/30/2005 - FIR05-00453 is associated with BLD05-01364. The associated building permit (BLD 05-01634) 8/30/2005 - 01364) is to install a new 1404 sq. ft. one story type VB modular preschool building including foundations, tiedowns, stairs, ramp and all site improvements per approved plans and attachments, CUP05-00034. Note: This building has been approved for daycare with occupant load based on 35 sq. ft. per person with one required exit for accessible means of egress. State of Idaho Tag # 3976 CC Structures shown on the approved plans other than the above described modular building are not part of this permit. (HAWTHORNE ELEMENTARY SCHOOL)(NEW MODULAR PRESCHOOL BLDG)

8/30/2005 - FIR05-00552 is associated with BLD05-01362. The associated building permit (BLD 05-01362) is to remodel an existing 2,116 sq.ft. classroom building per approved plans. Work to include complete removal of all interior partitions, exterior stairs and landings, and construction of new interior restrooms, kitchen area and exterior ramp, landings and exiting. (HAWTHORNE ELEMENTARY)(PORTABLE BLDG REMODEL FOR "JUST FOR KIDS")
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
DOC - Permit Finaled  9/7/2005 DONE
INSP-Final Inspection9/6/20059/6/20059/6/2005PPASS
DetailsForrest France
tom --call 1st before insp ; Phone #: ###-#### This inspection to be completed by Mary Froemke.

Tested cmoke detector and took EOL Voltage reading.
INSP-Final Inspection8/31/20058/31/20059/1/2005PDEFR
DetailsForrest France
This inspection to be performed by Mary Froemke due to scheduling conflicts.
INSP-Alarm Testing9/1/20059/1/20059/1/2005 PART
Smoke detector in north east rest room was shown on plans to be new and an old one was installed. Rob could not find a compatibility listing for the FACP and the smoke, so he will change it out to a System Sensor 2WB. Will need to retest the smoke.
Case Summary  8/31/2005 DONE
Plan assigned to (Mary)8/29/2005 8/30/2005 DONE
PLANS/APPL TAKEN TO FRONT DESK  8/30/2005 DONE
Inspection Record Card- Fire8/30/2005 8/30/2005 DONE
Issue and Print Permit  8/30/2005 DONE
Application received  8/29/2005  
Alarm Plan Check  8/10/2005 PASS
Approved pending field inspection of fire alarm permit comments. FA permit appliaction was not shown to have two building permits, until one portable was ready before the second one was delivered and the school wanted occupancy.