Permit VOIDED | 11/18/2005 | 11/18/2005 | 11/18/2005 | | DONE |
|
|
|
Per Forest this company did not complete the work
|
INSP-Final Inspection | 10/25/2005 | 10/25/2005 | 10/25/2005 | P | FAIL |
Troy Cobbley
|
|
|
Strobes are not synced, end of line voltage did not meet the 21.6 required (was 18.012), need to retest the east duct smoke detector since it did not want to latch when first tested and need updated map at the facp
|
INSP-Final Inspection | 10/21/2005 | 10/24/2005 | 10/24/2005 | P | FAIL |
Forrest France
|
|
|
Orientation and length of the sample tubes in the ductwork are not correctly installed, activation of the duct smoke detector produced a weak intermittent alarm signal reading 4.5 at the EOL under battery power.
|
INSP-Final Inspection | 10/19/2005 | 10/21/2005 | 10/21/2005 | P | CANC |
Forrest France
|
|
|
No time available for this inspection today, spoke with Kelly to reschedule for monday 10/24 per our agreement.
|
Inspection Record Card- Fire | 10/17/2005 | | 10/17/2005 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 10/17/2005 | | DONE |
|
|
|
|
Telephone call | | | 10/17/2005 | | DONE |
|
|
|
called ###-#### and told Samuel that permit is ready
|
CHANGE STATUS TO (ISS) | | | 10/17/2005 | | DONE |
|
|
|
already issued previously
|
Alarm Plan Check | | | 10/14/2005 | | PASS |
|
|
|
Plan Modification. Approved pending field inspection of fire alarm permit comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 10/14/2005 | | DONE |
|
|
|
|
Plan resubmittals received | | | 10/7/2005 | | DONE |
|
|
|
|
Case Summary | | | 10/7/2005 | | DONE |
|
|
|
|
Issue and Print Permit | | | 9/28/2005 | | DONE |
|
|
|
|
Plan assigned to (Mary) | 8/31/2005 | | 9/23/2005 | | DONE |
|
|
|
|
Alarm Plan Check | | | 9/23/2005 | | PASS |
|
|
|
Approved pending field inspection of fire alarm permit comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 9/23/2005 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 9/23/2005 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 9/23/2005 | | 9/23/2005 | | DONE |
|
|
|
|
Telephone call | | | 9/23/2005 | | DONE |
|
|
|
Spoke with Sammy and told him that permit is ready & fees///9/23/05 12:10pm BAS
|
Plan resubmittals received | | | 9/14/2005 | | DONE |
|
|
|
|
Alarm Plan Check | | | 9/8/2005 | | FAIL |
|
|
|
Resubmittal required. Faxed comments to Samuel Flores.
|
Application received | | | 8/31/2005 | | |
|
|
|
|
Case Summary | | | 8/31/2005 | | DONE |
|
|
|
|