Permit Information
Permit NumberFIR05-00562
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 8633 W FRANKLIN RD
Project NameSPR MICHAELS ARTS & CRAFT
Customer Number 
ePlanReview 
Description
MICHAELS THE ARTS & CRAFTS STORE (ADDITION AND REMODEL) - To modify and expand an existing fire sprinkler system into a new 7,650-ft/2, one story, addition on the east end of the existing Franklin Towne Plaza IV building. This addition is for the expansion of the existing Michaels Arts & Crafts tenant space. This includes the removal of two existing small entry vestibules and the construction of one new larger entry vestibule, the addition of a new 390-ft/2 classroom and a new office, cash room to the north east wall of the new expansion and add a new 800-ft/2 framing room at the southwest area of the retail space. The new building area with the addition is 51,750-ft/2, first floor 38,690-ft/2, second floor 13,060-ft/2. NOTE: The entire Franklin Towne Plaza IV building is considered one building. The sprinkler system is used for area increase. This fire protection work shall comply with the IFC 2003 and the permit review comments; each regulated by the Fire Chief. The review comments, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to BLD05-00627.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection2/15/20062/17/20062/17/2006APASS
DetailsTroy Cobbley
permit finaled
INSP-Final Inspection2/14/20062/15/20062/15/2006PFAIL
DetailsTroy Cobbley
Need to forward flush the backflow preventor and install one additional hanger at the front entrance.
INSP-Final Inspection2/1/20062/2/20062/2/2006AFAIL
DetailsTroy Cobbley
Need to provide review comments. Need to finish work work at the entrance. It appears one sprinkler needs to be added outside of the entry way. Provide spare heads and head wrench. Provide rest of ceiling tile in the framing room. Provide additional hydraulic stickers for new remote areas at the riser. Verify that the existing backflow does or does not need to be forward flushed to verify the new/higher flow rate of the storage area.
INSP-Final Inspection11/14/200511/15/200511/15/2005APART
DetailsTroy Cobbley
Could not give final with no ceiling. Piping in and around the new framing room is ok to cover
Permit Ready to Issue  10/18/2005 DONE
Inspection Record Card- Fire10/18/2005 10/18/2005 DONE
Telephone call  10/18/2005 DONE
left mess that permit is ready
Issue permit  10/18/2005 DONE
Sprinkler Plan Check10/13/2005 10/17/2005 PASS
DetailsBill Alexander
PLANS/APPL TAKEN TO FRONT DESK  10/17/2005 DONE
DetailsBill Alexander
INSP-Final Inspection10/14/200510/14/200510/14/2005PFAIL
DetailsForrest France
Approved resubmitted plans are not available for inspection or verification of compliance.
INSP-Final Inspection10/13/200510/13/200510/13/2005PPART
DetailsTroy Cobbley
Deficiencies for the 6" tie in have been corrected.
INSP-Sprinkler Rough-in10/12/200510/13/200510/13/2005AFAIL
DetailsTroy Cobbley
Inspection was for the 6" main. Need to fire caulk around the penatration to the fire riser room, provide additional clearance at thepenatrationthrough the CMU wall and provide a 4 way brace at the top of the 6" rise up piece in the future stock room.
Plan resubmittals received  10/13/2005 DONE
INSP-Sprinkler Rough-in/Hydro10/10/200510/10/200510/10/2005PFAIL
DetailsTroy Cobbley
Can not do a final as the sprinkler plans need to be resubmitted. Sprinkler piping is ok to cover in the new area.
INSP-Final Inspection10/10/200510/10/200510/10/2005PFAIL
DetailsTroy Cobbley
Can not do a final as the sprinkler plans need to be resubmitted. Sprinkler piping is ok to cover in the new area.
Permit Ready to Issue  10/7/2005 DONE
Inspection Record Card- Fire10/7/2005 10/7/2005 DONE
Telephone call  10/7/2005 DONE
left mess that permit is ready
Issue and Print Permit  10/7/2005 DONE
Plan assigned to (Bill)9/1/2005 10/6/2005 DONE
Plan resubmittals received  10/6/2005 PART
DetailsBill Alexander
Re-Submittals Of The Following Items Are Required:
1. Area #2 Hydraulic calculations (storage) design is flawed. Minimum sprinkler operating head pressure, for the Tyco Model "ELO-231" S.R., S.C., SSU, 11.2 K-factor TY5111 is 12.76 psi. All sprinklers are incorporating an 11.4 K-factor head which mean this design verification is flawed. Revise and resubmit a correct design for verification.

2. No provisions shown for forward flow testing of the backflow device. If none is provided, riser modifications will be required meeting annual requirements of NFPA 13-16.2.5.1. Address and resubmit clarification.

3. Design installation has problems. Fire sprinklers are cold soldering off the east wall of the new framing shop. The Tyco Model "ELO-231" S.R., S.C., SSU, 11.2 K-factor TY5111 pendants have a minimum fire sprinkler spacing for 9'-0". Sprinklers shall be permitted to be placed less than 8'-0" on center where the conditions of 8.8.3.4.2 are satisfied: Provide corrections and resubmit.

4. Plan FP2 of 2, seismic bracing was not provided for the new 6" main. Provide and resubmit.
PLANS/APPL TAKEN TO FRONT DESK  10/6/2005 DONE
Sprinkler Plan Check9/30/2005 10/3/2005 FAIL
DetailsTroy Cobbley
Plans still have problems with calcs, hangers, Seismic, etc.
Sprinkler Plan Check9/1/2005 9/29/2005 PART
DetailsTroy Cobbley
Re-Submittals Of The Following Items Are Required:

1. The scope of work provided on the permit application does not match what is actually going on.

2. The use of the EC-11 pendant sprinkler heads for Quick Response in ordinary hazard occupancy is not UL listed. See the provided data sheet and call Tyco technical support which is listed on the front of the data sheet as well.

3. The ELO-231 heads are shown to have a SIN number of TY3131 and be Quick Response on the head legend. But per the provided cut sheet is no TY3131 and the heads are not quick response.

4. The hydraulic calculations for Remote Area #1 are not accurate.
No dimensions or node points are given on the site plan.
Pipe size and type is not given on the site plan.
Calcs. show 4" MJ 90 but pipe entering and leaving fitting is 6".
Length of underground on calcs does not match what is scaled.
Fitting counts and point to point lengths as shown on plans don't match calcs.
Node points 40 and 42 are not shown on the plans.
The elevation changes of piping does not match center to center lengths given.

No other items reviewed except as listed above. Review all items for accuracy and resubmit. Upon resubmittal, additional items may be found upon further review.
Approval has been given to proceed with installation of the sprinkler system with the conditions set forth in the signed pre-installation letter.
Telephone call  9/26/2005 DONE
tlk to trent bice ###-#### that permit failed and needs to be picked up
Plan resubmittals received  9/22/2005 DONE
Application received  9/1/2005  
Plan assigned to (Bill)10/13/2005    
DetailsBill Alexander