Information based on query as of Thursday, July 18, 2024.
Permit Information
Permit NumberFIR05-00584
StatusFinaled
Name SIMPLEX/GRINNELL
Site Address 104 N MILWAUKEE
Project NameSPR CLEARWIRE
Customer Number 
ePlanReview 
Description
CLEARWIRE * To add and relocate sprinklers to accommodate the new tenant walls.
The building scope of work is to remodel an existing 5964-ft/2 tenant space for a new retail tenant per approved plans. Fire sprinkler work is related to selective demolition of interior nonbearing partitions, new ceilings for the relocation of the restrooms, construction of new interior partitions, to create sales room, breakroom, storage area, office area and small conference room. This fire protection work shall comply with the IFC 2003 and the permit review comments; each regulated by the Fire Chief. The review comments, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to BLD05-02155.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
DOC - Permit Finaled  10/27/2005 DONE
Passed Fire Life Safety by Troy on 9/29/05 he asked me to doc final this permit///10/27/05 BAS
INSP-Sprinkler Rough-in9/27/20059/27/20059/27/2005PFAIL
DetailsTroy Cobbley
Fitters are still installing piping
INSP-Final Inspection9/26/20059/27/20059/27/2005AFAIL
DetailsTroy Cobbley
Work not started yet. To be rescheduled for afternoon
Plan resubmittals received  9/26/2005  
Voided per email request from Tom Easton-Grinnell
Please disregard our last submittal for Clear Wire FIR05-00584.

Tyco/Fire & Security/SimplexGrinnell
Tom Easton
Design Manager
12443 W. Executive Dr.
Boise, ID. 83713
Phone ###-####
Fax ###-####
Cell ###-####
September 27, 2005
www.simplexgrinnell.com
INSP-Final Inspection9/22/20059/22/20059/22/2005PFAIL
DetailsTroy Cobbley
See approved drawings for pendant that needs added as shown on plans, insulation is causing obstructions to the upright sprinkler heads in many locations. Do not install ceiling tile untill re-inspection. Remove wire from sprinkler piping at location shown on plans. Drawings as submitted state ordinary hazard II occupancy. No room names or occupancys are shown on the plans. Pendant heads along south wall in smaller rooms are overspaced. Resubmit plans with spacing and occupancy changes or install per plans. Plans state 120 sq. ft. max. Repair the fire alarm panel. There are currently two troubles on panel.
Issue and Print Permit  9/22/2005 DONE
Sprinkler Plan Check9/20/2005 9/21/2005 PASS
DetailsTroy Cobbley
Approved with review comments
PLANS/APPL TAKEN TO FRONT DESK  9/21/2005 DONE
Permit Ready to Issue  9/21/2005 DONE
Inspection Record Card- Fire9/21/2005 9/21/2005 DONE
Telephone call  9/21/2005 DONE
Left voice message for Tom and told him that permit is ready & fees///9/21/05 12:00pm BAS
Plan resubmittals received  9/20/2005 DONE
Sprinkler Plan Check9/8/2005 9/19/2005 FAIL
DetailsTroy Cobbley
Plans failed. Comments faxed to contractor.
Case Summary  9/8/2005 DONE
Application received  9/8/2005  
Plan assigned to (Bill)9/8/2005