DOC - Permit Finaled | | | 10/27/2005 | | DONE |
|
|
|
Passed Fire Life Safety by Troy on 9/29/05 he asked me to doc final this permit///10/27/05 BAS
|
INSP-Sprinkler Rough-in | 9/27/2005 | 9/27/2005 | 9/27/2005 | P | FAIL |
Troy Cobbley
|
|
|
Fitters are still installing piping
|
INSP-Final Inspection | 9/26/2005 | 9/27/2005 | 9/27/2005 | A | FAIL |
Troy Cobbley
|
|
|
Work not started yet. To be rescheduled for afternoon
|
Plan resubmittals received | | | 9/26/2005 | | |
|
|
|
Voided per email request from Tom Easton-Grinnell
Please disregard our last submittal for Clear Wire FIR05-00584.
Tyco/Fire & Security/SimplexGrinnell
Tom Easton
Design Manager
12443 W. Executive Dr.
Boise, ID. 83713
Phone ###-####
Fax ###-####
Cell ###-####
September 27, 2005
www.simplexgrinnell.com
|
INSP-Final Inspection | 9/22/2005 | 9/22/2005 | 9/22/2005 | P | FAIL |
Troy Cobbley
|
|
|
See approved drawings for pendant that needs added as shown on plans, insulation is causing obstructions to the upright sprinkler heads in many locations. Do not install ceiling tile untill re-inspection. Remove wire from sprinkler piping at location shown on plans. Drawings as submitted state ordinary hazard II occupancy. No room names or occupancys are shown on the plans. Pendant heads along south wall in smaller rooms are overspaced. Resubmit plans with spacing and occupancy changes or install per plans. Plans state 120 sq. ft. max. Repair the fire alarm panel. There are currently two troubles on panel.
|
Issue and Print Permit | | | 9/22/2005 | | DONE |
|
|
|
|
Sprinkler Plan Check | 9/20/2005 | | 9/21/2005 | | PASS |
Troy Cobbley
|
|
|
Approved with review comments
|
PLANS/APPL TAKEN TO FRONT DESK | | | 9/21/2005 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 9/21/2005 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 9/21/2005 | | 9/21/2005 | | DONE |
|
|
|
|
Telephone call | | | 9/21/2005 | | DONE |
|
|
|
Left voice message for Tom and told him that permit is ready & fees///9/21/05 12:00pm BAS
|
Plan resubmittals received | | | 9/20/2005 | | DONE |
|
|
|
|
Sprinkler Plan Check | 9/8/2005 | | 9/19/2005 | | FAIL |
Troy Cobbley
|
|
|
Plans failed. Comments faxed to contractor.
|
Case Summary | | | 9/8/2005 | | DONE |
|
|
|
|
Application received | | | 9/8/2005 | | |
|
|
|
|
Plan assigned to (Bill) | 9/8/2005 | | | | |
|
|
|
|