INSP-Final Inspection | 8/15/2006 | 8/15/2006 | 8/15/2006 | P | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
CHANGE STATUS TO (ISS) | | | 8/15/2006 | | DONE |
|
|
|
8/15/06 as per troy//blb
|
INSP-Final Inspection | 8/10/2006 | 8/14/2006 | 8/14/2006 | A | FAIL |
Troy Cobbley
|
|
|
Remove the switch for the air compressor and straighten the dry pendant as discussed. (This activity was added in error so we have changed the case status back to Issued.)
|
INSP-Sprinkler Rough-in/Hydro | 4/26/2006 | 4/27/2006 | 4/27/2006 | P | PART |
Troy Cobbley
|
|
|
Trip Test and Forward Flow passed. Several dry pendants need straightened and the missing canopies replaced. Also missing is the ball drip, data sheets for the general air compressor, the switch for the air compressor blanked off, pressure relief valve installed and other misc. items as marked in red ink on the approval notes. The fire alarm interconnection has not been tested yet either.
|
INSP-Sprinkler Rough-in/Hydro | 4/25/2006 | 4/26/2006 | 4/26/2006 | A | PASS |
Troy Cobbley
|
|
|
24 hour air test for the dry pipe system has passed. Air pressure was actually gained due to outside temperature.
|
INSP-Sprinkler Rough-in/Hydro | 4/24/2006 | 4/25/2006 | 4/25/2006 | P | PART |
Troy Cobbley
|
|
|
24 Hr Air Test started at 12:35 with 44 1/2psi showing on the guage.
|
INSP-Sprinkler Rough-in | 4/18/2006 | 4/19/2006 | 4/19/2006 | P | FAIL |
Troy Cobbley
|
|
|
called in wrong permit no final per Troy
|
INSP-Sprinkler Rough-in | 4/14/2006 | 4/18/2006 | 4/19/2006 | P | CANC |
Troy Cobbley
|
|
|
Dave; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong
|
Override - Parcel Holds | 1/1/1900 | 1/1/1900 | 4/18/2006 | | |
|
|
|
|
INSP-Sprinkler Rough-in/Hydro | 4/13/2006 | 4/14/2006 | 4/14/2006 | A | PASS |
Troy Cobbley
|
|
|
Above ground hydro test passed.
|
Override - Parcel Holds | 1/1/1900 | 1/1/1900 | 4/14/2006 | | |
|
|
|
OK to override per Rita 4-14-06 eus
|
Override - Parcel Holds | 1/1/1900 | 1/1/1900 | 4/13/2006 | | |
|
|
|
|
INSP-Sprinkler Rough-in/Hydro | 4/10/2006 | 4/10/2006 | 4/10/2006 | P | NR |
Forrest France
|
|
|
Per phone conversation with contractor, project is not ready for a hydrostatic test at this time as scheduled.
|
Issue permit | | | 1/27/2006 | | |
|
|
|
|
Sprinkler Plan Check | 1/10/2006 | | 1/26/2006 | | PASS |
Bill Alexander
|
|
|
|
Plan assigned to (Bill) | 1/26/2006 | | 1/26/2006 | | DONE |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 1/26/2006 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 1/26/2006 | | 1/26/2006 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 1/26/2006 | | 1/26/2006 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 1/26/2006 | | |
|
|
|
|
INSP-Supply line flush | 1/23/2006 | 1/24/2006 | 1/24/2006 | P | PASS |
Troy Cobbley
|
|
|
Underground supply line flush passed.
|
INSP-Supply line flush | 1/20/2006 | 1/23/2006 | 1/23/2006 | A | PART |
Troy Cobbley
|
|
|
Inspection was for the underground hydro test which passed. The flush is to be scheduled for later.
|
Plan resubmittals received | | | 1/10/2006 | | DONE |
|
|
|
|
Plan resubmittals received | | | 11/1/2005 | | DONE |
|
|
|
|
INSP-Sprinkler Rough-in | 10/17/2005 | 10/18/2005 | 10/18/2005 | A | PART |
Troy Cobbley
|
|
|
The rest of the underground supply piping is ok to cover. The installation of the 6" gate valve and road box will need to be verified when United Water finishes the underground tie-in. I pointed out to the sprinkler contractor that there are concealed combustible spaces throughout the entire canopy system that do not have sprinkler protection and will need addressed prior to finaling the permit. This was not an overhead inspection just underground today.
|
INSP-Sprinkler Rough-in | 10/17/2005 | 10/17/2005 | 10/17/2005 | P | PART |
Troy Cobbley
|
|
|
Underground supply piping is ok to cover from United Waters tie in up thrust block.
|
Issue permit | | | 9/29/2005 | | DONE |
|
|
|
|
Plan assigned to (Bill) | 9/8/2005 | | 9/28/2005 | | DONE |
|
|
|
|
Sprinkler Plan Check | 9/8/2005 | | 9/28/2005 | | PASS |
Bill Alexander
|
|
|
Plans approved with conditions
|
PLANS/APPL TAKEN TO FRONT DESK | | | 9/28/2005 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 9/28/2005 | | 9/28/2005 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 9/28/2005 | | |
|
|
|
|
Telephone call | | | 9/28/2005 | | DONE |
|
|
|
left mess that permit is ready
|
Application received | | | 9/8/2005 | | |
|
|
|
|
INSP-Sprinkler Rough-in/Hydro | 1/16/2005 | 1/18/2006 | 1/18/2005 | A | PART |
Troy Cobbley
|
|
|
Roughin in general looks ok but per note #7 the plans need to be resubmitted with a 30% increase in the size of the remote area due to the deck slope. This may effect pipe sizing. The only items inspected was the sprinkler piping inside the canopy itself.
|